Introduces the Unimotive 27w-XT unit and its main features
Specpp. 1-2
Operating data, temperatures, capacities and dimensions per DIN 12876
Orderingp. 2
Model variants and ordering codes for the unit
p. 2table, 22 rows
p. 1table, 26 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
1530 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
12 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/23
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-45...150 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
I / NFL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
35 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
25 kW
at -20°C
14,5 kW
at -30°C
6,5 kW
at -40°C
2,6 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
3,6 kg
CO2 equivalent
7,7 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
12 facts · every claim linked to a page
Selection
The unit is purpose-built for water-ethylene glycol mixtures with corrosion protection down to -45 °C, so it should be selected for automotive-type applications rather than general lab use.
Confirms the intended heat transfer fluid and low-temperature capability before specifying the unit.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so the site cooling water must be compatible with these materials.
Prevents corrosion or fouling of the water-cooled condenser from unsuitable site water.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
Cooling water inlet temperature must stay between 5 °C and 20 °C, and pipes must be insulated if condensation conditions occur.
Defines the required site cooling water supply conditions and condensation protection.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Rated cooling power is only valid at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure, so higher water temperatures reduce capacity.
Allows correct derating of cooling capacity for actual site conditions.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -outlet.”
Installation
The unit requires a 400 V 3~ 50 Hz supply, and three-phase devices under 63 A are delivered with cable but without plug.
Electrical installation must provide a suitable 400 V three-phase supply and a plug/connection on site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Conformité
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.
Ensures the site power quality is checked against the permitted voltage/frequency envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
Leakage current exceeds 3.5 mA, which affects protective earthing and RCD selection.
Needed for electrical safety design and choice of residual current protection.
Source
“Attention: leakage current > 3,5mA”
Installation
Cooling water connections are G3/4 male and the minimum cooling water differential pressure is 1 bar, with maximum system pressure 12 bar.
Sets the piping and supply pressure requirements for the cooling water loop.
Source
“min. cooling water differential pressure”
Installation
Pump connections are M38x1,5 male and pipework must use ball socket per DIN 3863 and sleeve nut per DIN 3870.
Ensures correct mating fittings and hoses are procured for the external circuit.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Operation
The unit is IP20 and must be operated between 5 °C and 40 °C ambient, so it cannot be placed in wet or hot environments.
Defines the permissible installation environment and protection level.
Source
“max. ambient temperature”
Selection
The refrigerant is R-452A with GWP 2141 and 3.6 kg charge, giving 7.7 t CO2 equivalent, which matters for F-gas reporting.
Needed for refrigerant leak reporting and environmental compliance.
Source
“CO2 equivalent”
Maintenance
The unit has an electronic level indicator and adjustable overtemperature protection per DIN 12876, which must be checked during servicing.