Unimotive GL 20w-XT

Sommaire

  1. Overview p. 1
    Product introduction and general description of the unit
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 2 table, 23 rows
  4. p. 1 table, 26 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity200 mm²/s
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 0°C2100 l/h
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure12 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Net weight700 kg
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/24

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unimotive GL 20w-XT (Order-No.: 5033.0002.01)

ParameterValue
Operating temperature range-45...150 °C
Temperature stability at -10°C0,05 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationI / NFL
Heating power24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C28 kW
Cooling power with Water/ Glysantin 40/60 at 0°C25 kW
at -20°C18,6 kW
at -30°C11 kW
at -40°C6,8 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
Refrigerant quantity3,3 kg
CO2 equivalent0,0 t
Circulation pump:MK pump
max. delivery201 l/min
max. delivery pressure5,3 bar

Значения приведены дословно; строки 'Cooling power with Water/ Glysantin 40/60' и последующие 'at ...' относятся к охлаждающей мощности при соответствующих температурах.

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so it suits automotive temperature simulation and material testing rather than plain water duty.

Confirms the intended heat transfer fluid and low-temperature capability before specifying the unit for a given application.

Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation

Cooling water must be supplied between 5°C and 20°C, and if it drops below the condensation point the cooling water pipes inside the unit must be insulated.

Defines the site cooling water conditions and the need for pipe insulation to avoid condensation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

The cooling water circuit requires a differential pressure between 1 and 4 bar and must not exceed 6 bar static pressure.

Sets the facility cooling water supply requirements for correct and safe operation.

Source
“min. cooling water differential pressure 1 bar”
Installation

The unit needs a 400 V three-phase 50 Hz supply and, being above 63 A, is delivered without cable and without plug.

Affects electrical installation planning, cabling and on-site connection responsibility.

Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Installation

Voltage and frequency tolerances are ±5% and ±2% respectively, but the combination of -5% voltage with +2% frequency is not allowed.

Prevents specifying the unit on a supply where the combined tolerance window is exceeded.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

The unit is IP20 and must be operated between 5°C and 40°C ambient, so it needs a protected indoor location with adequate space.

Constrains the installation room and ventilation/space planning.

Source
“max. ambient temperature 40 °C”
Performance

Cooling capacity falls with lower temperature, from 28 kW at 20°C to 6.8 kW at -40°C, so the duty point must be checked against the actual process temperature.

Prevents oversizing assumptions based only on the 20°C figure when the process runs cold.

Source
“at -40°C 6,8 kW”
Performance

Cooling capacity figures are valid only at 20°C room temperature, 15°C cooling water inlet and 1 bar differential pressure, and higher cooling water temperature reduces capacity.

Requires derating of the published cooling capacity for actual site conditions.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Performance

The circulation pump delivers 201 l/min at zero head but only 42 l/min at 5.0 bar, so the operating point must be matched to the external circuit resistance.

Ensures the pump curve is checked against the pressure drop of the external application.

Source
“Delivery at 5,0 bar 42 l/min”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s, which limits fluid choice at low temperatures.

Prevents selecting a fluid that becomes too viscous at the low end of the temperature range.

Source
“max. permissible kin. viscosity 200 mm²/s”
Safety

The refrigerant is R-744 (CO2) with GWP 1 and 3.3 kg charge, giving 0.0 t CO2 equivalent, which simplifies refrigerant compliance and leak reporting.

Relevant for refrigerant regulations, risk assessment and environmental reporting.

Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280)”
Safety

The unit has adjustable overtemperature protection according to DIN 12876 and safety classification I/NFL, which must be set for the actual fluid and application.

Defines the safety device that must be configured correctly during commissioning.

Source
“With adjustable overtemperature protection according to DIN 12876.”
Installation

The pump connection is M38x1.5 male with bore shape Y (60°) per DIN 3863, requiring matching ball socket and sleeve nut fittings.

Ensures correct hose and fitting selection for leak-free connection.

Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Maintenance

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and treatment to avoid corrosion and fouling of the cooling circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”