Product introduction and general description of the unit
Specp. 2
Technical data according to DIN 12876
p. 2table, 25 rows
p. 1table, 27 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
3100 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Net weight
820 kg
Power supply requirement
460V 3~ 60Hz
max. current
57 A
Fuse
3x63A
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S589778
** Please respect space requirements. See operating conditions at www.huber-online.com
Unimotive GL 30w — Technical data according to DIN 12876
Parameter
Value
Order-No.
5009.0003.01
Operating temperature range
-45...95 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
35 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
35 kW
at -20°C
22 kW
at -30°C
14 kW
at -40°C
8,5 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
Refrigerant quantity
8,7 kg
CO2 equivalent
0,0 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
14 facts · every claim linked to a page
Selection
The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so it suits automotive temperature simulation and material testing rather than plain-water loops.
Confirms the intended heat transfer fluid and application envelope before specifying the unit.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water supply must be kept between 5°C and 20°C, and pipes must be insulated if the water can drop below the condensation point.
Defines the facility cooling water requirement and condensation/insulation precaution at the installation site.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
Cooling water differential pressure must stay between 1 bar and 4 bar, with a maximum cooling water pressure of 6 bar.
Sets the allowable cooling water circuit pressure window for correct flow and safe operation.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit requires a 460 V 3-phase 60 Hz supply with 57 A max current and 3x63 A fusing, and three-phase devices below 63 A are delivered with cable but without plug.
Drives electrical supply sizing, branch protection and the need to procure a plug/connection on site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
Leakage current exceeds 3.5 mA and an external branch circuit protection per UL 489 is required.
Mandates proper external branch protection and grounding design for the electrical installation.
Source
“Attention: leakage current > 3,5mA”
Conformité
Voltage and frequency tolerances are ±5% and ±2% respectively, but they may not be combined in the unfavorable direction.
Prevents specifying the unit on a supply where combined voltage/frequency deviation exceeds EN60034-1 limits.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
Pump connections are M38x1.5 male with bore shape Y (60°) per DIN 3863, requiring matching ball socket and sleeve nut per DIN 3870.
Ensures correct mating fittings and hoses are ordered for the process circuit.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Operation
The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s.
Limits fluid selection at low temperatures where viscosity rises and pump performance degrades.
Source
“max. permissible kin. viscosity 200 mm²/s”
Installation
The unit needs at least 8.9 l filling capacity and has a 19.9 l expansion tank, with a maximum system pressure of 6 bar.
Sizes the fluid charge and expansion volume for the external loop.
Source
“min. filling capacity 8,9 l”
Installation
Ambient temperature must be kept between 5°C and 40°C, and the unit is IP20 rated.
Defines room conditions and ingress protection limits for siting the equipment.
Source
“max. ambient temperature 40 °C”
Performance
Cooling power falls from 35 kW at 0°C to 8.5 kW at -40°C, so low-temperature duty must be checked against the load curve.
Prevents oversizing assumptions at deep negative temperatures during selection.
Source
“at -40°C 8,5 kW”
Operation
Cooling water consumption is 3100 l/h at 15°C water and 0°C flow, and cooling power drops as cooling water temperature rises.
Sizes the facility cooling water supply and anticipates derating with warmer water.
Source
“Consumption at water 15°C, flow 0°C 3100 l/h”
Safety
The refrigerant is R-744 (A1, H280) with GWP 1 and 8.7 kg charge, and the unit is safety class III / FL.
Informs refrigerant handling, room ventilation and safety classification requirements.
Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280)”
Maintenance
The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and material compatibility to avoid corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”