Product introduction and general description of the unit
Specp. 2
Technical data according to DIN 12876
p. 2table, 22 rows
p. 1table, 24 rows
Technical data according to DIN 12876
Parameter
Value
max. delivery pressure
5,3 bar
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
12 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/24
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unimotive GL 60w-XT (Order-No.: 5034.0002.01)
Parameter
Value
Operating temperature range
-45...150 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
I / NFL
Heating power
48 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
56 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
48 kW
at -20°C
34 kW
at -30°C
27 kW
at -40°C
18 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
UN-number
UN 2857
Circulation pump:
MK pump
max. delivery
201 l/min
Engineering Facts
14 facts · every claim linked to a page
Selection
The unit is intended for water-ethylene glycol mixtures with corrosion protection down to -45°C, so it suits automotive temperature simulation and material testing rather than general lab use.
Confirms the heat transfer fluid and application envelope before specifying the circulator.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water supply must be between 5°C and 20°C and provide at least 1 bar differential pressure, which dictates the facility water system design.
Cooling water outside this range reduces cooling capacity or requires additional infrastructure.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water falls below the condensation point, the cooling water pipes inside the unit must be insulated to prevent condensation.
Prevents condensation damage and electrical risk in low-temperature cooling water operation.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling power is rated at 20°C room temperature, 15°C cooling water inlet and 1 bar differential pressure, so actual capacity will differ if site conditions deviate.
Needed to compare quoted cooling capacity against real plant conditions.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -outlet.”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Incompatible water chemistry can corrode or degrade wetted materials.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Conformité
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and combinations such as -5% voltage with +2% frequency are not allowed.
Defines acceptable site power quality for warranty and reliable operation.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
Three-phase devices below 63A are supplied with cable but without plug, so the customer must provide a suitable plug and connection.
Affects electrical installation planning and scope of supply.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Three-phase devices above 63A are supplied without cable and without plug, requiring full customer-side power cabling.
Major installation cost and responsibility item for high-power units.
Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Installation
Pump connections use M38x1.5 male threads with bore shape Y (60°) per DIN 3863, and mating hoses need ball socket per DIN 3863 and sleeve nut per DIN 3870.
Ensures correct fittings and leak-free hose connections are ordered.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Operation
Maximum permissible kinematic viscosity of the thermal fluid is 200 mm²/s, limiting fluid choice at low temperatures.
Prevents pump overload and poor circulation with viscous fluids.
Source
“max. permissible kin. viscosity”
Safety
Maximum system pressure is 12 bar, so the external circuit and expansion vessel must be rated accordingly.
Defines pressure rating required for connected pipework and components.
Source
“max. System pressure”
Installation
The unit requires 400V 3~ 50Hz supply, which must be confirmed at the installation site.