Peter Huber Kältemaschinenbau RotaCool
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau RotaCool

Peter Huber Kältemaschinenbau RotaCool — Recirculating chillers with Noise level 59 dB.

The RotaCool is a space-saving L-design recirculating chiller with a 208–240 V 1~/2~ 50/60 Hz supply, built specifically for conventional rotary evaporators. Its -10…40 °C working range and 1 K stability distinguish it as a dedicated evaporator cooling thermostat rather than a general-purpose process chiller. It serves as the cooling source for condenser loops in laboratory rotary evaporation setups.

Noise level
59 dB

Full specifications

Core Performance & Functional Specifications
Noise level 59 dB(A)
Expansion volume 1 l
Pump connection M16x1 AG male
Pump speed adjustable no
Pump type Yes
Temperature range -10...40 °C
Temperature stability 1 K
Dimensions, Weight & Mechanical Design
Weight 32 kg
Electrical, Power & Drive Specifications
Power supply 208-240V 1~/2~ 50/60Hz
Interfaces, Connections & Control
Controller MPC
Temperature display LED Display
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Protection rating IP20
Standards, Safety & General Data
Safety class I / NFL

Description

Construction and series positioning

Working behavior and media

Installation and operation

Integration & Operating Notes

Electrical
Supply tolerances must be met simultaneously, not individually

The 208–240 V 1~/2~ 50/60 Hz supply must satisfy voltage and frequency tolerances at the same time; a combination such as -5% voltage with +2% frequency is explicitly not allowed. Verify the actual supply envelope before connection, because a supply that appears acceptable on each parameter alone may still be outside the combined allowed range.

Datasheet, Specifications, page 1
Electrical
Country-specific plug must be specified at ordering

Single/two-phase devices are delivered with a power cable and a country-specific plug. The plug type must be stated when ordering; otherwise commissioning can be delayed until the correct plug or adapter is obtained.

Datasheet, Installation, page 2
Process Limits
Cooling capacity is rated at 20 °C room temperature

The published cooling capacity is valid at 20 °C room temperature and may drop at higher ambient temperatures. Selection and duty planning must use the actual ambient conditions at the installation site, which must remain between 5 °C and 40 °C.

Datasheet, Specifications, page 1
Cooling & Media
R-290 refrigerant imposes flammability handling requirements

The unit uses R-290 (A3, H220), a flammable natural refrigerant. This affects handling, service access and room requirements; the installation location must be assessed accordingly rather than treated as an inert-refrigerant chiller.

Datasheet, Specifications, page 1
Mounting
IP20 enclosure requires a dry indoor location

With IP20 protection, the unit must be installed in a dry indoor location protected from water ingress and splashes. The air-cooled natural-draft refrigeration machine also needs adequate ventilation around the unit to avoid overheating and loss of cooling capacity.

Datasheet, Specifications, page 1
Process Limits
Minimum filling volume sets the loop inventory

Minimum filling capacity is 1.5 l and expansion volume is 1 l. The connected bath and loop must provide at least this inventory; underfilling risks pump operation and leaves insufficient expansion volume for the thermal fluid.

Datasheet, Specifications, page 1
Process Limits
Pump head must overcome the external circuit resistance

The pressure pump delivers up to 14 l/min at 0.25 bar head and the suction pump up to 10.5 l/min at 0.17 bar suction head. Verify that the connected loop's pressure drop is compatible with these heads before commissioning.

Datasheet, Specifications, page 1
Electrical
EMC Class A may need extra measures in residential areas

The equipment is classified EMC Class A, Group 1 to EN55011. In residential environments this may require additional measures to avoid disturbance; plan the installation location with this classification in mind.

Datasheet, Compliance, page 2

Selection & Integration Q&A

When should I choose the RotaCool rather than another Rotacool variant?

The verified facts list no sibling models, so selection is limited to this configuration. Choose it when the application is a conventional rotary evaporator whose cooling capacity and circulation quantity match the unit's ratings; otherwise verify against the actual evaporator load.

What must I provide on the hydraulic and electrical side to connect the RotaCool?

Provide M16x1 female mating fittings for the M16x1 male pump connections, a loop with at least 1.5 l filling capacity plus 1 l expansion volume, and a 208–240 V 1~/2~ 50/60 Hz supply fused between 10 A and 16 A with simultaneous voltage/frequency tolerances.

What ambient and installation limits apply to the RotaCool?

Install in a dry indoor location with IP20 protection, ambient between 5 °C and 40 °C, and adequate ventilation for the air-cooled natural-draft refrigeration machine. Cooling capacity is rated at 20 °C room temperature and may drop at higher ambient.

What is not included in the base delivery and must be ordered or procured separately?

The country-specific plug must be specified when ordering; mating M16x1 female fittings and the thermal fluid/loop inventory are not part of the unit. No maintenance schedule or accessory list is given in the verified facts, so service intervals cannot be stated.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
RotaCool Umwälzkühler für Rotationsverdampfer
Datasheet ·75,7 КБ ·2 pp.
View PDF