Product name and general description of the CS 330-H OD unit
Specp. 2
Technical data according to DIN 12876, including performance and dimensions
p. 1table, 40 rows
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-20...85 °C
temperature set point / display
colour LED Touchscreen
Internal temperature sensor
Pt100
Temperature stability at -10°C
1,5 K
Interface digital
RS232
Safety classification
I / NFL
Heating power
8 kW
Kälteleistung bei Umgebungstemperatur 5°C
at 15°C
40 kW
at 10°C
32 kW
at 0°C
22 kW
at -10°C
15 kW
at -20°C
10 kW
Cooling power at ambient temperature 20°C
at 15°C
42 kW
at 10°C
35 kW
at 0°C
25 kW
at -10°C
17 kW
at -20°C
11 kW
Kälteleistung bei Umgebungstemperatur 35°C
at 15°C
40 kW
at 10°C
33 kW
at 0°C
22 kW
at -10°C
15 kW
at -20°C
9,5 kW
Kälteleistung bei Umgebungstemperatur 40°C
at 15°C
38 kW
at 10°C
27 kW
at 0°C
21 kW
at -10°C
13 kW
at -20°C
7,5 kW
Kälteleistung bei Umgebungstemperatur 50°C
at 15°C
31 kW
at 10°C
26 kW
at 0°C
18 kW
at -10°C
11 kW
at -20°C
6,5 kW
Refrigeration machine
air-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Refrigerant quantity
9 kg
Engineering Facts
13 facts · every claim linked to a page
Installation
The chiller is suitable for outdoor installation down to -20 °C ambient, so site planning must account for weather exposure and frost protection of the loop.
Determines whether an indoor plant room is required or outdoor placement with freeze protection is acceptable.
Source
“Suitable for outside mounting (min. environmental temperature -20°C)”
Installation
Electrical components are rated IP54, which limits acceptable washdown and dust exposure at the installation site.
Affects enclosure placement and cleaning regime in industrial environments.
Source
“Protection classification of the electrical components IP54”
Installation
The operating panel is delivered as a remote control on a 20 m cable, so panel routing and cable path must be planned at installation.
Requires allocating cable route and panel mounting location separate from the chiller.
Source
“Delivered with remote control: operating panel connected via 20m cable”
Performance
Cooling capacity is only guaranteed up to +35 °C ambient and derates above that, so sizing must use the capacity at the actual site ambient temperature.
Prevents undersizing when the chiller is installed in a hot room or outdoors in summer.
Source
“Reduction of cooling power above +35°C environmental temperature”
Installation
The unit requires a 460 V 3-phase 60 Hz supply with 49 A max current and 3x60 A fusing, so the electrical feed and protection must be sized accordingly.
Defines the site power supply, cable cross-section and breaker rating before delivery.
Source
“Fuse (3 phase)
3x60A”
Installation
Three-phase devices below 63 A are supplied with cable but without a plug, so the customer must provide the site-side connection.
Avoids assuming a ready-to-plug unit and allows planning of the electrical termination.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances are ±5 % and ±2 % but not simultaneously in the unfavorable direction, so supply quality must be checked.
Unstable site power can void performance or damage the compressor and must be assessed.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Compliance
The unit is EMC Class A Group 1, which is intended for industrial environments and may cause interference in residential areas.
Affects installation location and EMC coordination with sensitive equipment nearby.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Operation
The recommended thermofluid is a 50:50 water–monoethylene glycol mixture, which sets the freeze protection and heat transfer basis.
Determines fluid selection, freeze protection and compatibility with the circuit materials.
Source
“Recommended thermofluid: Water - Monoethylene Glycol 50:50”
Installation
The pump connection is G1 male with 125 l/min max flow and 4.7 bar max pressure, so the external circuit must be sized for these limits.
Defines the piping adapter and the allowable pressure drop of the external loop.
Source
“Pump connection
G1 male”
Operation
The tank holds 160–175 l, so the loop volume and expansion/fluid inventory must be planned within this range.
Affects fluid quantity, expansion volume and commissioning fill.
Source
“min. filling capacity
160 l”
Safety
The refrigerant is R-449A (A1, H280) with 9 kg charge and 12.57 t CO2 equivalent, so refrigerant safety and F-gas reporting obligations apply.
Triggers refrigerant handling, leak detection and CO2-equivalent reporting requirements.
Source
“R-449A (A1, H280)”
Installation
The unit is 1400x1000x1800 mm and 530 kg, so floor loading, transport route and clearance must be verified.
Determines rigging, doorway clearance and structural floor requirements.