Installation
The chiller requires cooling water with a differential pressure between 3 and 6 bar, so the facility water supply must be sized accordingly.
Insufficient differential pressure will prevent proper cooling and may trip the unit.
Source
“min. cooling water differential pressure 3 bar”
Installation
Cooling water inlet temperature must be kept between 5°C and 20°C, and pipes must be insulated if condensation occurs.
Out-of-range water temperature reduces cooling capacity or causes condensation and corrosion risk.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these fluids must be avoided or a more resistant pump specified.
Using incompatible fluids will damage the pump and void reliable operation.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Safety
The unit uses flammable refrigerant R-290 (A3, H220), so ignition sources and ventilation must be considered during installation.
A3 refrigerant requires attention to room ventilation and avoidance of ignition sources.
Source
“R-290 (A3, H220)”
Selection
Cooling power is rated 1 kW at 15°C with 15°C cooling water and 3 bar differential pressure, so actual capacity depends on site conditions.
Rated cooling capacity cannot be assumed at other water temperatures or pressures.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 3 bar differential pressure between cooling water inlet and -”
Installation
The unit is IP20 and must be installed in an environment between 5°C and 40°C ambient temperature.
Exceeding ambient limits or exposing to water/dust (IP20) risks malfunction.
Source
“max. ambient temperature 40 °C”
Compliance
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Supply quality outside these limits may cause unreliable operation or damage.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so water quality must be compatible.
Aggressive or scaling water can corrode or foul these materials and reduce performance.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Operation
Whisper mode reduces sound pressure to 51 dB(A) but also reduces pump delivery to 14 l/min and 0.2 bar.
Selecting whisper mode trades hydraulic performance for lower noise.
Source
“Pump data for whisper mode:”
Selection
The pressure-suction pump delivers up to 24 l/min at 0.7 bar pressure and 18 l/min at 0.4 bar suction.
External circuit pressure drop must be checked against these pump limits.
Source
“max. delivery 24 l/min”
Installation
The unit requires a 16 A fuse and draws up to 12 A from a 208–240 V single/two-phase supply.
Electrical supply and protection must be sized for 12 A continuous and 16 A fusing.
Source
“max. current 12 A”
Maintenance
The unit has a level indicator with sight glass, so fill level must be monitored during operation.
Low fill level can cause pump cavitation and poor temperature control.
Source
“Level indicator with sight glass.”