TC100-F Temperature Controller Datasheet

Contents

  1. Overview p. 1
    General description and key features of TC100-F controllers
  2. Spec p. 1
    Electrical, thermal, and mechanical specifications of the controller
  3. Ordering p. 1
    Model codes and available configurations for ordering
  4. p. 1 table, 35 rows

Technical data according to DIN 12876

ParameterValue
Operating temperature range-100...40 °C
Cooling power
at 0°C0,16 kW
at -20°C0,15 kW
at -30°C0,14 kW
at -50°C0,13 kW
at -60°C0,12 kW
at -80°C0,12 kW
at -90°C0,07 kW
at -100°C0,01 kW
Safety classificationI / NFL
Refrigeration machineair-cooled, natural
refrigerant
Refrigerant (ASHRAE, GHS)R-1270 (A3, H220)
Global Warming Potential (GWP)0
Refrigerant quantity0,114 kg
CO2 equivalent0,0 t
Refrigerant 2nd stage (ASHRAE, GHS)R-1150 (A3, H220)
Global Warming Potential (GWP)4
Refrigerant quantity 2nd stage0,056 kg
CO2-Äquivalent 2.Stufe0,0 t
Nominal diameter probe13 mm
Length of probe900 mm
Length flexible connection1150 mm
Overall dimensions WxDxH **295x500x570 mm
Net weight57 kg
sound pressure level +/- 4 dB(A)58 dB(A)
Power supply requirement220-240V 1~/2~ 50/60Hz
max. current7 A
min. Fuse10A
max. Fuse16A
Pressure equipment categoryArt. 4.3 PED
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.S569390

** Please respect space requirements. See operating conditions at www.huber-online.com

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit is rated for an operating temperature range of -100 to 40 °C, so it must be selected only for processes within that envelope.

Defines the process temperature window the immersion cooler can serve.

Source
“Operating temperature range -100...40 °C”
Performance

Cooling capacity drops sharply near the cold end, from 0.12 kW at -80 °C to 0.07 kW at -90 °C and only 0.01 kW at -100 °C, so the lowest temperatures are practical only with very small heat loads.

Prevents oversizing expectations at the extreme low end of the range.

Source
“at -90°C 0,07 kW at -100°C 0,01 kW”
Performance

Published cooling capacities are valid at 20 °C room temperature and may fall at higher ambient, so capacity margins must be checked against the actual site ambient.

Site ambient directly affects achievable cooling power.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation

The unit may only be operated with ambient temperature between 5 °C and 40 °C, so the installation location must stay within this range.

Ambient limits constrain where the air-cooled unit can be installed.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The power supply must be 220-240 V single or two-phase at 50/60 Hz with a maximum current of 7 A and a fuse between 10 A and 16 A.

Determines electrical supply and protection sizing at the installation site.

Source
“Power supply requirement 220-240V 1~/2~ 50/60Hz max. current 7 A min. Fuse 10A max. Fuse 16A”
Installation

Voltage and frequency tolerances are coupled: ±5% voltage is allowed only with ±2% frequency, and combinations such as -5% voltage with +2% frequency are not allowed.

Prevents installation on a supply whose combined voltage/frequency deviation exceeds the permitted envelope.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

Single- and two-phase devices are delivered with a power cable and country-specific plug that must be specified at ordering, while three-phase devices below 63 A come with cable but without plug.

Affects ordering configuration and on-site electrical connection work.

Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Safety

The refrigerant is R-1270 (A3, H220) with GWP 0 and a charge of 0.114 kg, and the second stage uses R-1150 (A3, H220) with 0.056 kg, so both circuits are flammable A3 refrigerants requiring appropriate site precautions.

Flammable refrigerant classification drives ventilation, ignition-source and handling requirements.

Source
“Refrigerant (ASHRAE, GHS) R-1270 (A3, H220)”
Compliance

The equipment is classified as pressure equipment category Art. 4.3 PED, which defines the applicable pressure-equipment compliance route.

Determines which pressure-equipment documentation and conformity requirements apply.

Source
“Pressure equipment category Art. 4.3 PED”
Compliance

The unit is EMC-classified as Class A, Group 1 to EN55011, so it is intended for industrial environments and may cause interference in residential areas.

Class A equipment has installation restrictions regarding residential/light-industrial use.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

Space requirements around the unit must be respected, as referenced in the operating conditions.

Air-cooled units need clearance for heat rejection and service access.

Source
“** Please respect space requirements. See operating conditions at www.huber-online.com”
Selection

The probe has a nominal diameter of 13 mm and a length of 900 mm with a 1150 mm flexible connection, which must fit the vessel and routing at the point of use.

Probe and connection geometry determine mechanical fit in the application.

Source
“Nominal diameter probe 13 mm Length of probe 900 mm Length flexible connection 1150 mm”
Installation

The unit weighs 57 kg net and measures 295x500x570 mm, so handling and floor/bench loading must be planned accordingly.

Weight and footprint affect transport, lifting and installation space.

Source
“Overall dimensions WxDxH ** 295x500x570 mm Net weight 57 kg”
Operation

The refrigeration unit works continuously, which must be considered in operating strategy and energy/heat-load planning.

Continuous operation affects heat rejection, noise and wear expectations.

Source
“The refrigeration unit works continiously.”