The unit is rated for an operating temperature range of -20 to 100 °C, so it cannot be used outside this window.
Defines the process temperature envelope for which the chiller can be selected.
Source
“Operating temperature range -20...100 °C”
The unit is rated for an operating temperature range of -20 to 100 °C, so it cannot be used outside this window.
Defines the process temperature envelope for which the chiller can be selected.
“Operating temperature range -20...100 °C”
Cooling capacity drops from 1.5 kW at 15 °C to 0.3 kW at -20 °C, so low-temperature duty requires derating the load.
Needed to match the chiller to the actual heat load at the intended set point.
“at 15°C 1,5 kW at 0°C 1 kW at -10°C 0,7 kW at -20°C 0,3 kW”
The power supply must be 220–240 V single-phase 50 Hz with a 16 A fuse and 13.5 A max current.
Determines site electrical supply, breaker sizing and cabling for installation.
“Power supply requirement 220-240V 1~ 50Hz max. current 13,5 A Fuse 16 A”
The unit is IP20 and must be installed where ambient temperature stays between 5 °C and 40 °C.
Constrains the installation location and room conditions; IP20 is not suitable for wet or dusty environments.
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Cooling capacity figures are valid at 20 °C room temperature and may drop if ambient temperature rises.
Prevents overestimating available cooling in a warm plant room.
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Voltage and frequency tolerances are ±5% and ±2% respectively, but they must not be combined in opposite directions.
Affects acceptance of the site power quality and risk of nuisance trips or damage.
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
The refrigerant is R-449A (A1, H280) with GWP 1397 and 0.35 kg charge, giving 0.5 t CO2 equivalent.
Required for refrigerant safety classification, leak response and F-gas reporting.
“Refrigerant (ASHRAE, GHS) R-449A (A1, H280) Global Warming Potential (GWP) 1397 Refrigerant quantity 0,35 kg CO2 equivalent 0,5 t”
The plastic pump is not resistant to acetone or polyglycols, so these media must be avoided or a more resistant pump specified.
Prevents chemical attack and premature pump failure when choosing the heat transfer fluid.
“Special Case: Acetone and Polyglycol: The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than used pure.
Guides correct coolant preparation for sub-zero operation.
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Single/two-phase devices are supplied with a power cable and country-specific plug that must be specified at order.
Avoids a missing or wrong plug on delivery and rework at commissioning.
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Space requirements around the unit must be respected per the operating conditions.
Air-cooled units need clearance for airflow; ignoring this reduces cooling capacity.
“** Please respect space requirements. See operating conditions at www.huber-online.com”
An optional Pt100 sensor connection can display (not control) process temperature and is only available factory fitted.
Must be decided at ordering; cannot be retrofitted in the field.
“Option: Pt100 sensor connection #10519 to display (not control) e.g. of the process temperature (only available factory fitted, additional charge)”
The controller has an autostart function for power failure, so the unit restarts automatically after mains recovery.
Affects unattended operation and restart behavior after power interruptions.
“Autostart function for power failure”