Selection
The chiller is rated for an operating temperature range of -20 to 40 °C, so the process must stay within these limits.
Defines the application window and excludes processes requiring lower or higher temperatures.
Source
“Operating temperature range
-20...40 °C”
Performance
Cooling capacity drops from 2 kW at 0 °C to 0.8 kW at -20 °C, so low-temperature duty needs a larger unit or reduced heat load.
Sizing must account for the reduced capacity at the coldest operating point.
Source
“at -20°C
0,8 kW”
Installation
The unit requires a 230 V single-phase 50 Hz supply with a 16 A fuse and draws up to 13 A.
Determines the electrical circuit, breaker rating and cabling for installation.
Source
“Power supply requirement
230V 1~ 50Hz
max. current
13 A
Fuse
16 A”
Installation
The chiller is air-cooled and needs adequate space and ambient conditions, with ambient temperature between 5 and 40 °C.
Air-cooled units reject heat to the room, so ventilation and ambient limits must be respected.
Source
“min. ambient temperature
5 °C”
Performance
Cooling capacity is quoted for 20 °C room temperature and may fall if ambient temperature rises.
Prevents overestimating capacity in warm plant rooms.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Compliance
Voltage and frequency tolerances are ±5% and ±2% respectively, but they must not be combined in opposite directions.
Ensures the supply quality is acceptable and avoids invalid tolerance combinations.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety
The refrigerant is R-449A with GWP 1397 and a charge of 1.2 kg, giving 1.7 t CO2 equivalent.
Affects refrigerant handling, leak reporting and environmental compliance.
Source
“Refrigerant (ASHRAE, GHS)
R-449A (A1, H280)
Global Warming Potential (GWP)
1397
Refrigerant quantity
1,2 kg
CO2 equivalent
1,7 t”
Installation
The pump connection is G3/4 male, so hoses and fittings must match this thread.
Prevents mismatch of process connections during installation.
Source
“Pump connection
G3/4 male”
Performance
The circulation pump delivers 25 l/min maximum and 5 l/min at 3 bar, so system pressure drop must be checked against the pump curve.
Ensures the pump can overcome the external circuit resistance.
Source
“max. delivery
25 l/min
max. delivery pressure
3 bar
Delivery at 3,0 bar
5 l/min”
Installation
The unit has IP20 protection, so it must be installed in a dry indoor location protected from water and dust ingress.
Restricts installation environment and prevents moisture or dust damage.
Source
“Degree of Protection
IP20”
Operation
The unit is intended for externally closed applications, so an open process circuit is not suitable.
Defines the hydraulic configuration and prevents incorrect use with open tanks.
Source
“For externally closed applications.”
Maintenance
The minimum filling capacity is 2.5 l and expansion volume is 2 l, which sets the heat-transfer fluid charge and expansion allowance.
Needed to prepare the correct fluid volume and expansion vessel capacity.
Source
“min. filling capacity
2,5 l
Volume of expansion
2 l”
Compliance
The equipment is classified as Class A, Group 1 for electromagnetic disturbance to EN55011.
Class A equipment may require additional EMC measures in residential or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation
Single-phase devices are supplied with a power cable and country-specific plug, which must be specified at order.
Avoids delays and ensures the correct plug for the installation site.
Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”