  1. Overview p. 1
    Product introduction and main features of the chiller
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 2 table, 16 rows
  4. p. 1 table, 34 rows

Technical data according to DIN 12876

ParameterValue
Consumption at water 15°C, flow -20°C276 l/h
min. cooling water differential pressure1 bar
max. cooling water pressure6 bar
min. filling capacity6,5 l
Volume of expansion5,5 l
Overall dimensions WxDxH **600x600x1450 mm
Net weight227 kg
sound pressure level +/- 4 dB(A)65 dB(A)
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)12 A
Fuse (3 phase)3x16A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.S417606

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unichiller 100Tw (Order-No.: 3017.0040.01)

CharacteristicValue
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at 15°C10 kW
Cooling power at 0°C10 kW
Cooling power at -10°C6,5 kW
Cooling power at -20°C3 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity1,75 kg
CO2 equivalent2,4 t
Circulation pumpC3
max. delivery96 l/min
max. delivery pressure5,6 bar
Delivery at 0,5 bar92 l/min
Delivery at 1,0 bar86 l/min
Delivery at 1,5 bar81 l/min
Delivery at 2,0 bar75 l/min
Delivery at 2,5 bar68 l/min
Delivery at 3,0 bar62 l/min
Delivery at 3,5 bar54 l/min
Delivery at 4,0 bar46 l/min
Delivery at 4,5 bar37 l/min
Delivery at 5,0 bar24 l/min
Pump connectionG1 1/4 male
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 15°C510 l/h
Consumption at water 15°C, flow 0°C510 l/h
Consumption at water 15°C, flow -10°C375 l/h

Engineering Facts

12 facts · every claim linked to a page
Installation

The chiller is water-cooled and requires a cooling water supply with a differential pressure between 1 and 6 bar.

To ensure the cooling water circuit can provide adequate flow and pressure without exceeding component ratings.

Source
“min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”
Installation

The unit must be operated with cooling water intake temperature between 5°C and 20°C; below the condensation point, cooling water pipes must be insulated.

To prevent condensation and ensure specified cooling performance.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C. When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase.

To correctly size the cooling water supply and predict performance under actual site conditions.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water may be used.

To avoid corrosion or damage to the cooling water circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Compliance

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.

To verify site power quality meets the allowed voltage/frequency envelope before installation.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2% Example -5% voltage and +2% frequency -> not allowed! -5% voltage and - 2% frequency -> allowed”
Installation

Three-phase devices with current consumption less than 63A are supplied with cable but without a plug.

To plan for a suitable plug and electrical connection on site.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety

The refrigerant R-449A has safety group A1 and GHS hazard H280, with a GWP of 1397 and a charge of 1.75 kg (2.4 t CO2 equivalent).

To assess refrigerant safety, environmental impact and reporting obligations.

Source
“R-449A (A1, H280) Global Warming Potential (GWP) 1397 Refrigerant quantity 1,75 kg CO2 equivalent 2,4 t”
Operation

The unit has a maximum ambient temperature of 40°C and minimum of 5°C, and IP20 protection.

To ensure the installation location meets environmental and ingress protection requirements.

Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The pump connection is G1 1/4 male and the cooling water connection is G3/4 male.

To select matching hoses and fittings for process and cooling water connections.

Source
“Pump connection G1 1/4 male Cooling water connection G3/4 male”
Performance

The circulation pump delivers a maximum of 96 l/min and 5.6 bar, with flow decreasing as pressure rises.

To verify the pump can meet the required flow and pressure in the external circuit.

Source
“max. delivery 96 l/min max. delivery pressure 5,6 bar”
Installation

The minimum filling capacity is 6.5 l and expansion volume is 5.5 l.

To determine the required heat transfer fluid volume and expansion allowance.

Source
“min. filling capacity 6,5 l Volume of expansion 5,5 l”
Compliance

The equipment is classified for electromagnetic disturbance as EN55011 Class A, Group 1.

To assess EMC compatibility and potential interference in the installation environment.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”