The chiller's cooling capacity drops as ambient temperature rises, so selection must account for actual room conditions.
Cooling capacity is rated at 20°C ambient; higher ambient reduces available cooling and may require a larger unit.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
Three-phase units below 63 A are supplied with cable but without a plug, so the installer must provide a suitable plug.
Affects electrical installation planning and procurement of the mating plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances must be respected simultaneously; some combinations are not allowed.
Prevents connecting the unit to a supply whose combined voltage/frequency deviation exceeds permitted limits.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The unit requires 400 V three-phase 50 Hz supply.
Determines the electrical supply and cabling required at the installation site.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation
The unit has IP20 protection, so it must be installed in a dry, protected environment.
IP20 is not water- or dust-tight; installation location must avoid moisture and conductive dust.
Source
“Degree of Protection IP20”
Installation
Space requirements around the unit must be respected per the manufacturer's operating conditions.
Air-cooled unit needs adequate clearance for heat rejection and service access.
Source
“** Please respect space requirements. See operating conditions at www.huber-online.com”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280 (pressurized gas).
Affects handling, labeling and safety measures for refrigerant and pressure equipment.
Source
“R-449A (A1, H280)”
Compliance
The unit is EMC Class A Group 1, which may require additional measures in residential environments.
Class A equipment is intended for industrial environments and may cause interference in residential areas.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Operation
The unit is intended for externally closed applications only.
Prevents use in open-loop or vented setups that could damage the pump or system.
Source
“For externally closed applications.”
Operation
Ambient temperature must stay between 5°C and 40°C for proper operation.
Operating outside this range may affect cooling performance and reliability.
Source
“min. ambient temperature 5 °C”
Performance
The circulation pump delivers 210 l/min max at 4.7 bar max, with flow decreasing as pressure rises.
Needed to match pump curve to the external circuit's pressure drop.
Source
“max. delivery 210 l/min”
Maintenance
The expansion tank is atmospheric open and has a 39 l expansion volume.
Determines fluid fill limits and expansion allowance for the loop.
Source
“Volume of expansion 39 l”
Selection
Minimum filling capacity is 14 l, which sets the minimum system volume for proper operation.
Ensures the external loop has sufficient thermal mass and pump stability.
Source
“min. filling capacity 14 l”
Compliance
The equipment complies with US-SNAP and applicable EU laws for industrial process refrigeration.
Confirms regulatory suitability for industrial process refrigeration applications.
Source
“This equipment is compliant to US-SNAP and all applicable EU laws.”