Product introduction and main features of the Unimotive 20w
Specpp. 1-2
Technical data, performance figures and operating limits
Specp. 2
DIN 12876 compliant technical parameters table
p. 2table, 25 rows
p. 1table, 26 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
920 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,2 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Net weight
446 kg
Power supply requirement
400V 3~ 50Hz
max. current
31,5 A
Fuse
3x32A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S548098
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-45...95 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
12 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
21 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
17,5 kW
at -20°C
9,5 kW
at -30°C
5,5 kW
at -40°C
3 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
2,9 kg
CO2 equivalent
6,2 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
12 facts · every claim linked to a page
Selection
The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so the heat transfer fluid must be selected accordingly.
Determines the permissible heat transfer fluid and prevents unsuitable fluids from being used.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water intake temperature must be between 5°C and 20°C, which constrains the site cooling water supply.
Needed to verify the available cooling water temperature at the installation site before commissioning.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water falls below the condensation point, the cooling water pipes in the unit must be insulated.
Prevents condensation and corrosion damage in the cooling water circuit.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling power drops and cooling water flow rate may increase as cooling water temperature rises, so performance must be derated accordingly.
Affects sizing of the cooling water supply and expected performance at the site.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and material compatibility to avoid corrosion or clogging.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Compliance
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Must be checked against the site power supply to ensure compliant operation.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety
Leakage current exceeds 3.5 mA, which requires appropriate protective earthing and RCD selection.
Affects electrical installation and protective device selection.
Source
“Attention: leakage current > 3,5mA”
Installation
Three-phase devices below 63 A are delivered with cable but without plug, so a suitable plug must be provided on site.
Needed for planning the electrical connection and ordering the correct plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Space requirements must be respected, so the installation layout must account for the specified clearances.
Ensures adequate access and ventilation at the installation site.
Source
“Please respect space requirements. See operating conditions at www.huber-online”
Operation
The unit has an adjustable overtemperature protection according to DIN 12876, which must be set for safe operation.
Safety setting that must be configured before operation.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Selection
The unit is intended for externally closed applications, which limits the hydraulic circuit design.
Determines whether the unit suits the intended process loop.
Source
“For externally closed applications.”
Installation
Pump connections use bore shape Y (60°) per DIN 3863 with ball socket and sleeve nut per DIN 3870, so matching fittings are required.
Ensures correct mating fittings and hoses are procured for installation.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”