Peter Huber Kältemaschinenbau Unimotive 20w
Peter Huber Kältemaschinenbau Unimotive 20w — Temperature control units.
The Unimotive 20w is a water-cooled temperature control unit with a magnetically coupled stainless steel pump, rated for -45 to 95 °C in externally closed circuits. Its 12 kW heating capacity and 920 l/h cooling-water demand at 15 °C distinguish it from smaller Unimotive 10w siblings. It serves as a central temperature source for closed process loops requiring sub-ambient to near-boiling control.
Peter Huber Kältemaschinenbau Unimotive Series — Model Comparison & Selection
| Model | Display resolution | Heating capacity, W | Power supply | Pump connection | Refrigerant | Safety class |
|---|---|---|---|---|---|---|
| Unimotive 20w Current | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | III / FL |
| Unimotive 10w | 0.01 | 12000 | 400V 3~ 50Hz | M38x1,5 AG male | R-452A (A1, H280) | III / FL |
| Unimotive 10w-XT | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | I / NFL |
| Unimotive 20w-XT | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | I / NFL |
| Unimotive 26w | 0, 01 K | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | III / FL |
| Unimotive 26w-XT | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | I / NFL |
| Unimotive 27w | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | III / FL |
| Unimotive GL 07w | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 07w-XT | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
| Unimotive GL 10w | 0, 01 | 24000 | 460V 3~ 60Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 10w-XT | 0, 01 | 24000 | 460V 3~ 60Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
| Unimotive GL 20w | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 20w-XT | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
| Unimotive GL 30w | 0, 01 | 24000 | 460V 3~ 60Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 50w | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 50w-XT | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
| Unimotive GL 60w | 0, 01 | 48000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 60w-XT | 0, 01 | 48000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
Full specifications
| Control output | POKO ONE |
| Heating capacity | 12 kW |
| Pump connection | M38x1, 5 AG male |
| Pump speed adjustable | no |
| Pump type | magnetically coupled, stainless steel |
| External sensor connection | Pt100 |
| Temperature range | -45...95 °C |
| Weight | 446 kg |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Display resolution | 0, 01 K |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Refrigerant | R-452A (A1, H280) (1st stage) |
| Maximum viscosity | 200 mm²/s |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G3/4 male |
| Cooling water consumption | 920 l/h (at 15°C, flow 0°C) |
| Cooling water differential pressure | 1 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
The Unimotive 20w is a water-cooled temperature control unit built for externally closed applications, using a magnetically coupled stainless steel pump with fixed speed and M38x1.5 AG male pump connections. Within the Unimotive series it sits above the 10w and 10w-XT in heating capacity (12 kW) and below the 26w; the -XT siblings are separate variants not to be conflated with this model. The refrigerant circuit uses R-452A in the first stage, and the unit carries safety class III / FL with adjustable overtemperature protection per DIN 12876. The controller is Pilot ONE with POKO ONE control output, a display resolution of 0.01 K, and interfaces including Ethernet, USB (host and device) and RS232.
Working range and media behavior
The temperature range spans -45 to 95 °C. The unit is constructed for water-ethylene glycol mixtures with corrosion protection (e.g. Glysantin®) down to -45 °C, so fluid selection must follow this constraint. Cooling water intake must be between 5 and 20 °C; as cooling water temperature rises, cooling power drops and cooling water flow rate may increase, so site performance must be derated accordingly. The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, limiting acceptable cooling water quality. Only drinking water or filtered river/sea water may be used; sea water is prohibited.
Installation and operation specifics
The unit requires a 400 V 3~ 50 Hz supply with voltage tolerance ±5% only with simultaneous frequency tolerance ±2%, and leakage current exceeds 3.5 mA, so protective earthing and RCD selection must account for this. Three-phase devices below 63 A are delivered with cable but without plug. Cooling water connections are G3/4 male, with a minimum differential pressure of 1 bar and maximum pressure of 6 bar. A building-side backflow preventer is mandatory, and cooling water supply should be shut off during downtimes because flow can occur even when the unit is switched off. The unit must not be installed in an ATEX zone, and a drip tray must be installed below it by the responsible body. Outdoor installation requires frost-protected cooling water lines and a minimum cooling water temperature of 5 °C.
Integration & Operating Notes
Operating outside this intake temperature window invalidates the published cooling performance and may stress the refrigerant circuit. Site cooling water supply must be verified before commissioning, and performance derating must be applied as intake temperature rises toward 20 °C.
The unit's leakage current exceeds 3.5 mA, so protective earthing must be verified and the RCD type/rating selected accordingly. Three-phase devices below 63 A arrive with cable but no plug, so a suitable plug must be provided on site by the installer.
The responsible body must install a condensation water / heat transfer fluid drip tray below the unit, and a building-side backflow preventer must protect the drinking water supply. Neither is part of the unit delivery, so both must be planned before commissioning.
The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only drinking water or filtered river/sea water may be used. Sea water must not be used. When cooling water temperatures fall below the condensation point, the cooling water pipes in the unit must be insulated.
Cooling water flow can occur even when the unit is switched off, so the supply should be shut off for shorter downtimes such as overnight. Before switching off, the heat transfer fluid must be brought to room temperature to avoid overpressure in the system.
The maximum flow pressure of the unit must be taken into account for pressure-sensitive applications such as glass reactors; an external bypass may be required. The pump is fixed-speed with no adjustment, so the hydraulic circuit must be designed around its fixed flow-pressure characteristic.
Selection & Integration Q&A
Pick the 20w when the process needs 12 kW heating and the -45 to 95 °C range in an externally closed loop. The 10w offers less heating capacity; the 26w is larger. The -XT variants are separate modifications and should not be specified interchangeably with the 20w.
Provide G3/4 male cooling water connections with 5–20 °C intake, minimum 1 bar differential and maximum 6 bar pressure; expect about 920 l/h at 15 °C intake with 0 °C flow. A building-side backflow preventer and a drip tray below the unit are mandatory.
Ambient must be 5–40 °C, IP20, no ATEX zone, and refrigerant charge versus room size must be checked. Outdoor siting requires frost-protected cooling water lines and intake never below 5 °C. Shut off cooling water during overnight downtimes since flow can occur even when switched off.
Three-phase units below 63 A ship with cable but without plug, so a plug must be supplied. Pump connections are M38x1.5 male requiring DIN 3863 ball socket and DIN 3870 sleeve nut fittings; tempering hoses with inside diameter at least matching the pump connections are not included.