Induztr
Engineering Digest Document Viewer Related Models

Unimotive GL 10w

Contents

  1. Overview p. 1
    Product introduction and general description of the unit
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 2 table, 25 rows
  4. p. 1 table, 26 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity200 mm²/s
Cooling water connectionG3/4 male
Consumption at water 15°C, flow 0°C2100 l/h
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **730x804x1738 mm
Net weight600 kg
Power supply requirement460V 3~ 60Hz
max. current47 A
Fuse3x63A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.1.0/23

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-45...95 °C
Temperature stability at -10°C0,05 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C21,5 kW
Cooling power with Water/ Glysantin 40/60 at 0°C17,5 kW
at -20°C11,5 kW
at -30°C7,5 kW
at -40°C4,5 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
Refrigerant quantity3,3 kg
CO2 equivalent0,0 t
Circulation pump:MK pump
max. delivery201 l/min
max. delivery pressure5,3 bar

Order-No.: 5008.0003.01; Unimotive GL 10w

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit is purpose-built for automotive applications using water-ethylene glycol mixtures down to -45°C, so it should be selected only for that fluid family and temperature envelope.

Confirms fluid compatibility and minimum temperature before specifying the unit for a test bench.

Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation

Cooling water must be supplied between 5°C and 20°C; below the condensation point the cooling water pipes inside the unit must be insulated.

Defines the facility cooling water supply requirement and condensation protection needed at installation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

The cooling water circuit requires a differential pressure between 1 and 4 bar and must never exceed 6 bar.

Sets the allowable cooling water supply pressure window for safe connection to the building loop.

Source
“min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Installation

The unit draws 47 A at 460 V 3~ 60 Hz and requires 3x63 A fuses plus external branch circuit protection per UL 489.

Determines the electrical supply, fuse rating and mandatory external protection for the installation.

Source
“External branch circuit protection according to UL 489 required.”
Installation

Three-phase devices below 63 A are delivered with cable but without plug, so the site must provide a suitable connection.

Affects electrical installation planning because no plug is included with the unit.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Voltage and frequency tolerances are ±5% and ±2% but must not be combined in opposite directions; -5% voltage with +2% frequency is not allowed.

Prevents specifying a supply that appears within individual tolerances but is outside the permitted combined envelope.

Source
“-5% voltage and +2% frequency -> not allowed!”
Operation

Cooling power drops as cooling water temperature rises and cooling water flow rate may need to increase, so performance must be derated for warmer site water.

Avoids overestimating available cooling capacity when the facility cooling water is warmer than 15°C.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Operation

The pump delivers 201 l/min at zero head but only 42 l/min at 5.0 bar, so system pressure drop must be checked against the pump curve.

Ensures the external circuit resistance is compatible with the required flow rate.

Source
“Delivery at 5,0 bar 42 l/min”
Safety

The refrigerant is R-744 (A1, H280) with GWP 1 and a charge of 3.3 kg, which simplifies refrigerant reporting and requires H280 pressure-gas handling awareness.

Informs refrigerant safety classification and environmental reporting for the installed unit.

Source
“R-744 (A1, H280)”
Safety

The unit has adjustable overtemperature protection according to DIN 12876 and safety classification III/FL.

Confirms the built-in safety function required for unattended temperature control of external circuits.

Source
“With adjustable overtemperature protection according to DIN 12876.”
Maintenance

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water may be used.

Guides water quality and material compatibility checks to avoid corrosion or fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance

The unit is EMC class A group 1 to EN55011, which is industrial-grade emission classification and may require separation from sensitive equipment.

Affects EMC planning and placement relative to sensitive laboratory or test equipment.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Selection

The maximum permissible kinematic viscosity of the thermal fluid is 200 mm²/s, which limits fluid choice at low temperatures.

Prevents selecting a fluid that becomes too viscous for the pump at the lowest operating temperature.

Source
“max. permissible kin. viscosity 200 mm²/s”
Installation

The unit weighs 600 kg and measures 730x804x1738 mm, so floor loading and access route must be verified.

Needed for rigging, floor loading and room access planning before delivery.

Source
“Overall dimensions WxDxH ** 730x804x1738 mm Net weight 600 kg”