Unimotive GL 50w

Contents

  1. Overview p. 1
    Product introduction and general description of the unit
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 2 table, 19 rows
  4. p. 1 table, 26 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity200 mm²/s
Cooling water connectionG3/4 male
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/24

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-45...95 °C
Temperature stability at -10°C0,05 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C40 kW
Cooling power with Water/ Glysantin 40/60 at 0°C35 kW
at -20°C31 kW
at -30°C23 kW
at -40°C14 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
Circulation pump:MK pump
max. delivery201 l/min
max. delivery pressure5,3 bar
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit is purpose-built for automotive applications using water-ethylene glycol mixtures with corrosion protection down to -45 °C, so it should be chosen for that fluid and duty rather than general-purpose use.

Confirms the intended fluid and application envelope before specifying the unit.

Source
“The Unimotive model series is specially designed for applications in the automotive industry.”
Selection

The temperature control systems are constructed for operation with water-ethylene glycol mixture including corrosion protection down to -45 °C, which defines the permissible heat transfer fluid.

Prevents selecting an incompatible fluid that could damage the circuit.

Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation

The cooling water intake temperature must be between 5 °C and 20 °C, so the site cooling water supply must be verified before installation.

Cooling water outside this range invalidates the published cooling capacity and may require site modifications.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.

Prevents condensation and corrosion damage on the cooling water circuit.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Published cooling capacities are valid only at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure, so actual capacity will differ at other site conditions.

Allows correct derating of cooling power for the actual installation conditions.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -outlet.”
Performance

Higher cooling water temperature reduces cooling power and may increase the required cooling water flow rate.

Must be accounted for when sizing the cooling water supply and predicting performance.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and treatment to avoid corrosion of mixed materials.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Installation

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and the combination -5% voltage with +2% frequency is not allowed.

Defines the acceptable power supply quality for reliable operation.

Source
“-5% voltage and +2% frequency -> not allowed!”
Installation

Three-phase devices drawing less than 63 A are supplied with cable but without a plug, so a suitable plug must be provided on site.

Affects electrical installation planning and the scope of supply.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Three-phase devices drawing more than 63 A are supplied without cable and without plug, requiring full on-site cabling.

Affects electrical installation scope and cost.

Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Compliance

The equipment is classified Class A, Group 1 for electromagnetic disturbance to EN55011, which has implications for the installation environment.

Class A equipment may require EMC measures in residential or sensitive environments.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

Space requirements must be respected, with operating conditions referenced at the manufacturer's website.

Ensures adequate clearance for operation and maintenance.

Source
“** Please respect space requirements. See operating conditions at www.huber-online.com”
Safety

The unit uses R-744 (A1, H280) refrigerant, which is a high-pressure, asphyxiation-hazard substance requiring appropriate handling awareness.

Informs safety planning and refrigerant handling requirements.

Source
“R-744 (A1, H280)”
Operation

The unit has adjustable overtemperature protection according to DIN 12876, which must be set for the application.

Critical safety setting to protect the application and the unit.

Source
“With adjustable overtemperature protection according to DIN 12876.”