Peter Huber Kältemaschinenbau Unimotive GL 50w
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unimotive GL 50w

Peter Huber Kältemaschinenbau Unimotive GL 50w — Temperature control units.

The Unimotive GL 50w is a water-cooled temperature control unit with a magnetically coupled stainless-steel pump, 24 kW heating capacity and a -45...95 °C working range, built for water-ethylene glycol mixtures with corrosion protection. Within the Unimotive series it is the larger GL modification, distinguished by its 24 kW heater and G3/4 cooling-water connection. It serves automotive test benches and process circuits requiring sub-ambient to near-boiling temperature control.

Peter Huber Kältemaschinenbau Unimotive Series — Model Comparison & Selection

Model Display resolutionHeating capacity, WPower supplyPump connectionRefrigerantSafety class
Unimotive GL 50w Current 0, 0124000400V 3~ 50HzM38x1, 5 AG maleR-744 (A1, H280)III / FL
Unimotive 10w 0.0112000400V 3~ 50HzM38x1,5 AG maleR-452A (A1, H280)III / FL
Unimotive 10w-XT 0, 0112000400V 3~ 50HzM38x1, 5 AG maleR-452A (A1, H280)I / NFL
Unimotive 20w 0, 0112000400V 3~ 50HzM38x1, 5 AG maleR-452A (A1, H280)III / FL
Unimotive 20w-XT 0, 0112000400V 3~ 50HzM38x1, 5 AG maleR-452A (A1, H280)I / NFL
Unimotive 26w 0, 01 K24000400V 3~ 50HzM38x1, 5 AG maleR-452A (A1, H280)III / FL
Unimotive 26w-XT 0, 0124000400V 3~ 50HzM38x1, 5 AG maleR-452A (A1, H280)I / NFL
Unimotive 27w 0, 0124000400V 3~ 50HzM38x1, 5 AG maleR-452A (A1, H280)III / FL
Unimotive GL 07w 0, 0112000400V 3~ 50HzM38x1, 5 AG maleR-744 (A1, H280)III / FL
Unimotive GL 07w-XT 0, 0112000400V 3~ 50HzM38x1, 5 AG maleR-744 (A1, H280)I / NFL
Unimotive GL 10w 0, 0124000460V 3~ 60HzM38x1, 5 AG maleR-744 (A1, H280)III / FL
Unimotive GL 10w-XT 0, 0124000460V 3~ 60HzM38x1, 5 AG maleR-744 (A1, H280)I / NFL
Unimotive GL 20w 0, 0124000400V 3~ 50HzM38x1, 5 AG maleR-744 (A1, H280)III / FL
Unimotive GL 20w-XT 0, 0124000400V 3~ 50HzM38x1, 5 AG maleR-744 (A1, H280)I / NFL
Unimotive GL 30w 0, 0124000460V 3~ 60HzM38x1, 5 AG maleR-744 (A1, H280)III / FL
Unimotive GL 50w-XT 0, 0124000400V 3~ 50HzM38x1, 5 AG maleR-744 (A1, H280)I / NFL
Unimotive GL 60w 0, 0148000400V 3~ 50HzM38x1, 5 AG maleR-744 (A1, H280)III / FL
Unimotive GL 60w-XT 0, 0148000400V 3~ 50HzM38x1, 5 AG maleR-744 (A1, H280)I / NFL

Full specifications

Core Performance & Functional Specifications
Control output POKO ONE (potential-free contact)
Heating capacity 24 kW
Pump connection M38x1, 5 AG male
Pump speed adjustable no
Pump type magnetically coupled, stainless steel
External sensor connection Pt100
Temperature range -45...95 °C
Electrical, Power & Drive Specifications
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Display resolution 0, 01 K
Digital interface Ethernet, USB (Host u. Device), RS232
Materials, Media & Process Compatibility
Refrigerant R-744 (A1, H280) (1st stage)
Maximum viscosity 200 mm²/s
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G3/4 male
Cooling water differential pressure 1 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

Behavior under load and media

Installation, control and operation

Integration & Operating Notes

Process Limits
Cooling water must stay within 5–20 °C intake

The unit is designed for cooling water intake between 5 °C and 20 °C. Outside this window the published cooling capacity is invalid and the site supply must be verified or modified before installation; below the condensation point the internal cooling water pipes must be insulated.

Datasheet, Specifications, page 2
Electrical
Voltage and frequency tolerances are coupled

Supply tolerance is ±5% voltage with ±2% frequency, but the combination of -5% voltage and +2% frequency is explicitly not allowed. Plan the site supply and any generator/transformer configuration so this corner condition cannot occur.

Datasheet, Specifications, page 2
Electrical
Plug scope depends on current draw

Three-phase devices drawing less than 63 A are delivered with cable but without a plug, so a suitable plug must be provided on site. Devices above 63 A are supplied without cable and without plug, requiring full on-site cabling by a certified electrician.

Datasheet, Specifications, page 2
Mounting
Drip tray and refrigerant room-size check required

The responsible body must install a condensation water / heat transfer fluid drip tray below the unit. Refrigerant charge and room size must be checked during installation to avoid dangerous refrigerant concentration from the R-744 charge.

Operation Manual, Commissioning, page 15
Mounting
ATEX zones are excluded

The unit must not be installed or started inside an ATEX zone. Site classification must be confirmed before placement, regardless of the IP20 protection rating of the enclosure.

Operation Manual, page 13
Cooling & Media
Cooling water quality and backflow protection

Only drinking water or filtered river/sea water may be used; sea water is prohibited. A building-side backflow preventer is required to protect the drinking water supply, and the mixed-material circuit (copper, 1.4401, MS, PA, PPE, PTFE, EPDM) constrains water treatment.

Operation Manual, page 28
Cooling & Media
Shut off cooling water during downtimes

Cooling water can flow even when the unit is switched off, so the supply should be shut off even for short downtimes such as overnight. Outdoor installation additionally requires frost-protected lines and a minimum cooling water temperature of 5 °C.

Operation Manual, page 28
Process Limits
Pressure-sensitive loads need bypass evaluation

The pump is not speed-adjustable, so the maximum flow pressure is fixed. For pressure-sensitive applications such as glass reactors, the maximum flow pressure must be taken into account and an external bypass may be required. Hose inside diameters must at least match the M38x1.5 pump connections.

Operation Manual, page 34
Operation
Return fluid to room temperature before shutdown

The heat transfer fluid must always be adjusted to room temperature before switching off to avoid overpressure in the system. The adjustable overtemperature protection to DIN 12876 must be set for the application before commissioning.

Operation Manual, page 34; Datasheet, page 1

Selection & Integration Q&A

When should I choose the Unimotive GL 50w rather than the 10w or 20w variants?

Pick the GL 50w when the duty needs the 24 kW heater and the -45...95 °C range with water-ethylene glycol. The 10w/20w and their -XT variants are the smaller series members; confirm heating capacity and circuit size against your load before downsizing.

What must be provided on the cooling-water and electrical side for this unit?

Provide G3/4 male cooling-water connections with 1 bar minimum differential and 6 bar maximum pressure, drinking or filtered river water (no sea water), and a building-side backflow preventer. Electrically, 400 V 3~ 50 Hz within ±5%/±2%; below 63 A the unit arrives with cable but no plug.

Where can the unit be installed and what site provisions does the manual require?

Not inside an ATEX zone. Install with the specified wall clearances, a drip tray below the unit, and a room-size check against the R-744 charge. Cooling water intake must be 5–20 °C; outdoor siting needs frost-protected lines and a minimum 5 °C cooling water temperature.

What maintenance and consumables are outside the base delivery?

The base delivery excludes the power plug (below 63 A) or cable and plug (above 63 A), the drip tray, the building-side backflow preventer, and the water-ethylene glycol mixture with corrosion protection. Cooling water must be shut off during downtimes; the adjustable DIN 12876 overtemperature protection must be configured on site.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unimotive GL 50w
Datasheet ·31,4 КБ ·2 pp.
View PDF