Unimotive GL 50w-XT

Contents

  1. Overview p. 1
    Introduces the Unimotive GL 50w-XT unit and its main features
  2. Spec p. 2
    Lists technical data according to DIN 12876 standard
  3. p. 2 table, 19 rows
  4. p. 1 table, 26 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 3,0 bar124 l/min
Delivery at 4,0 bar87 l/min
Delivery at 5,0 bar42 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity200 mm²/s
Cooling water connectionG3/4 male
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure12 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/24

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-45...150 °C
Temperature stability at -10°C0,05 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationI / NFL
Heating power24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C40 kW
Cooling power with Water/ Glysantin 40/60 at 0°C35 kW
at -20°C31 kW
at -30°C23 kW
at -40°C14 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
Circulation pump:MK pump
max. delivery201 l/min
max. delivery pressure5,3 bar
Delivery at 1,0 bar179 l/min
Delivery at 2,0 bar154 l/min

Engineering Facts

14 facts · every claim linked to a page
Selection

The unit is purpose-built for automotive applications using water-ethylene glycol mixtures down to -45°C, so it should be chosen only for such media and duty.

Confirms the intended heat transfer fluid and low-temperature capability before specifying the unit.

Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation

The cooling machine is water-cooled, so a cooling water supply with adequate differential pressure must be provided at the installation site.

Dictates that cooling water infrastructure is mandatory for installation.

Source
“Refrigeration machine water-cooled, natural refrigerant”
Installation

Cooling water connections are G3/4 male and require a differential pressure between 1 and 4 bar, which must be verified in the plant piping design.

Ensures the site cooling water loop meets the minimum pressure requirement for proper operation.

Source
“min. cooling water differential pressure 1 bar”
Installation

The unit requires a 400 V three-phase 50 Hz supply, so the electrical installation must be sized accordingly.

Determines the electrical supply and cabling needed at the installation site.

Source
“Power supply requirement 400V 3~ 50Hz”
Installation

Three-phase devices below 63 A are delivered with cable but without plug, so a suitable plug must be sourced and fitted on site.

Prevents delays at commissioning by planning the plug and connection in advance.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

The unit is designed for cooling water intake between 5°C and 20°C, and higher intake temperatures reduce cooling power and may increase flow demand.

Sets the allowable cooling water temperature window and warns of performance loss outside it.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.

Prevents condensation and corrosion damage when cold cooling water is used.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation

Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and treatment to avoid corrosion of the cooling circuit.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance

Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.

Ensures the site power quality is checked against the permitted tolerance envelope.

Source
“-5% voltage and +2% frequency -> not allowed!”
Compliance

The equipment is classified as EN55011 Class A Group 1, which has implications for electromagnetic compatibility in the installation environment.

Class A equipment may require EMC measures depending on the installation location.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

The unit has IP20 protection and must be installed in an ambient temperature between 5°C and 40°C.

Defines the environmental limits and ingress protection for the installation room.

Source
“max. ambient temperature 40 °C”
Installation

The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s, which limits fluid selection at low temperatures.

Prevents pump overload and ensures proper circulation when selecting the fluid.

Source
“max. permissible kin. viscosity 200 mm²/s”
Safety

The unit has a maximum system pressure of 12 bar and pressure equipment category II, which must be respected in the external circuit design.

Sets the pressure limit for connected pipework and components.

Source
“max. System pressure 12 bar”
Operation

The refrigerant is R-744 (A1, H280) with GWP 1, which is relevant for safety classification and environmental compliance.

Informs refrigerant safety handling and environmental reporting requirements.

Source
“R-744 (A1, H280)”