Peter Huber Kältemaschinenbau Unimotive GL 50w-XT
Peter Huber Kältemaschinenbau Unimotive GL 50w-XT — Temperature control units.
The Unimotive GL 50w-XT is a water-cooled temperature control unit built for water-ethylene glycol mixtures down to -45 °C, covering a -45...150 °C working range with 24 kW heating capacity. Within the Unimotive series it is the large GL modification with R-744 refrigerant and a magnetically coupled stainless-steel pump, intended for automotive test benches and process circuits requiring sub-zero glycol temperature control.
Peter Huber Kältemaschinenbau Unimotive Series — Model Comparison & Selection
| Model | Display resolution | Heating capacity, W | Power supply | Pump connection | Refrigerant | Safety class |
|---|---|---|---|---|---|---|
| Unimotive GL 50w-XT Current | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
| Unimotive 10w | 0.01 | 12000 | 400V 3~ 50Hz | M38x1,5 AG male | R-452A (A1, H280) | III / FL |
| Unimotive 10w-XT | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | I / NFL |
| Unimotive 20w | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | III / FL |
| Unimotive 20w-XT | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | I / NFL |
| Unimotive 26w | 0, 01 K | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | III / FL |
| Unimotive 26w-XT | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | I / NFL |
| Unimotive 27w | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-452A (A1, H280) | III / FL |
| Unimotive GL 07w | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 07w-XT | 0, 01 | 12000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
| Unimotive GL 10w | 0, 01 | 24000 | 460V 3~ 60Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 10w-XT | 0, 01 | 24000 | 460V 3~ 60Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
| Unimotive GL 20w | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 20w-XT | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
| Unimotive GL 30w | 0, 01 | 24000 | 460V 3~ 60Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 50w | 0, 01 | 24000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 60w | 0, 01 | 48000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | III / FL |
| Unimotive GL 60w-XT | 0, 01 | 48000 | 400V 3~ 50Hz | M38x1, 5 AG male | R-744 (A1, H280) | I / NFL |
Full specifications
| Control output | POKO ONE |
| Heating capacity | 24 kW |
| Pump connection | M38x1, 5 AG male |
| Pump speed adjustable | no |
| Pump type | magnetically coupled, stainless steel |
| External sensor connection | Pt100 |
| Temperature range | -45...150 °C |
| Power supply | 400V 3~ 50Hz |
| Controller | Pilot ONE |
| Display resolution | 0, 01 K |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Refrigerant | R-744 (A1, H280) (1st stage) |
| Maximum viscosity | 200 mm²/s |
| Ambient temperature limit | 5...40 °C |
| Cooling water connection | G3/4 male |
| Cooling water differential pressure | 1 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
- Water-cooled refrigeration machine using natural refrigerant R-744 (A1, H280) in the first stage; no air-cooled condenser, so a plant cooling water loop is mandatory.
- Magnetically coupled stainless-steel pump with fixed speed (not adjustable), M38x1.5 AG male pump connections.
- Pilot ONE controller with POKO ONE control output; display resolution 0.01 K; external Pt100 sensor connection.
- Positioned above the smaller Unimotive 10w/20w and their -XT variants; the GL 50w-XT is the high-capacity glycol unit of the series.
Working range and media
- Temperature range -45...150 °C, purpose-built for water-ethylene glycol mixtures with corrosion protection (e.g. Glysantin®) down to -45 °C.
- Maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s, which constrains fluid selection at the cold end.
- Maximum system pressure 12 bar (pressure equipment category II); pressure-sensitive downstream apparatus must account for the unit's maximum flow pressure.
- Heating capacity 24 kW; no digitized performance curves were supplied, so part-load cooling behavior cannot be stated here.
Installation, connection and control
- 400 V 3~ 50 Hz supply; three-phase units below 63 A are delivered with cable but without plug.
- Cooling water connections G3/4 male, minimum differential pressure 1 bar, maximum cooling water pressure 6 bar; intake temperature designed for 5...20 °C.
- Interfaces: Ethernet, USB (host and device), RS232.
- IP20 protection, ambient temperature 5...40 °C; EN55011 Class A Group 1 (industrial EMC environment only).
Integration & Operating Notes
The water-cooled refrigeration machine needs a plant cooling water supply connected to G3/4 male ports with at least 1 bar differential pressure and no more than 6 bar static pressure. Verify the loop in the piping design before the unit is delivered, since without adequate differential pressure the refrigerant stage cannot reject heat.
The unit is designed for cooling water intake between 5 °C and 20 °C. Higher intake temperatures reduce available cooling power and may increase flow demand, so a site survey of the summer cooling water temperature is required. Below the condensation point, the internal cooling water pipes must be insulated to prevent condensation and corrosion.
The 400 V 3~ 50 Hz supply is permitted only within ±5% voltage and ±2% frequency, and certain combinations such as -5% voltage with +2% frequency are explicitly not allowed. Check the site power quality against this envelope; the unit is EN55011 Class A Group 1 and is intended for industrial EMC environments only.
Three-phase devices with current consumption below 63 A are delivered with a cable but without a plug, so a suitable plug must be sourced and fitted on site. Replacement power cables are limited to 4 m for three-phase connections; hardwiring must be performed by a certified electrician and the unit must always be connected to a socket with protective earth.
The responsible body must install a condensation water / heat transfer fluid drip tray below the unit. Refrigerant charge (see rating plate) and room size must be checked during installation to avoid dangerous refrigerant concentration. The unit must not be installed or started inside an ATEX zone, and minimum wall clearances per the manual table must be respected.
The heat transfer fluid must always be adjusted to room temperature before switching off to avoid overpressure in the system. The maximum system pressure is 12 bar, and pressure-sensitive downstream apparatus such as glass reactors must account for the unit's maximum flow pressure, possibly with an external bypass. Hose inside diameters must at least match the M38x1.5 pump connections.
Cooling water flow can occur even when the unit is switched off, so the supply should be shut off overnight and during other downtimes to prevent water damage and unnecessary consumption. Only drinking water or filtered river water may be used; sea water is prohibited. A building-side backflow preventer is required to protect the drinking water supply.
Selection & Integration Q&A
Pick the GL 50w-XT when the process needs the full -45...150 °C glycol range with 24 kW heating and a water-cooled R-744 stage. The 10w/20w siblings suit lower heat loads; the GL 50w-XT is the high-capacity glycol modification of the series.
A 400 V 3~ 50 Hz supply within ±5% voltage / ±2% frequency (plug not included), a G3/4 cooling water loop at 1...6 bar with 5...20 °C intake, a drip tray below the unit, and a building-side backflow preventer.
Ambient 5...40 °C, IP20, no ATEX zone, EN55011 Class A Group 1 industrial EMC environment only. Refrigerant charge versus room size must be checked, and cooling water must be shut off during downtimes since flow can occur with the unit switched off.
The three-phase cable is supplied but the plug is not; the drip tray and backflow preventer are site-provided. Plan glycol mixture with corrosion protection, cooling water treatment compatible with copper/1.4401/EPDM, and periodic checks of the cooling water circuit per the manual.