Product introduction and general description of the Unistat P645w unit
Specpp. 1-2
Technical performance data, dimensions, and operating parameters
Specp. 2
Compliance specifications according to DIN 12876 standard
p. 2table, 19 rows
p. 1table, 29 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 5,0 bar
50 l/min
Pump connection
flange DN32 PN10/40 EN1092-1
max. permissible kin. viscosity
50 mm²/s
Cooling water connection
flange DN32 PN10/40 EN1092-1
Consumption at water 15°C, flow 0°C
6000 l/h
min. cooling water differential pressure
3 bar
max. cooling water pressure
6 bar
min. filling capacity
30 l
Filling capacity expansion tank
30 l
Overall dimensions WxDxH **
2210x1300x2160 mm
Net weight
2150 kg
Power supply requirement
460V 3~ 60Hz
max. current
70 A
Fuse
3x80A
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S611392
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876 — Unistat P645w (Order-No.: 1063.0006.01)
Characteristic
Value
Operating temperature range
-60...200 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
36 kW
Cooling power with Thermooil at 200°C
45 kW
Cooling power with Thermooil at 100°C
45 kW
Cooling power with Ethanol at 0°C
45 kW
Cooling power with Ethanol at -20°C
42 kW
Cooling power with Ethanol at -40°C
21 kW
Cooling power with Ethanol at -60°C
6 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-507 (A1, H280)
Global Warming Potential (GWP)
3985
Refrigerant quantity
24 kg
CO2 equivalent
95,6 t
Circulation pump: MK pump max. delivery
343 l/min
max. delivery pressure
5,5 bar
Delivery at 1,0 bar
300 l/min
Delivery at 2,0 bar
250 l/min
Delivery at 3,0 bar
191 l/min
Delivery at 4,0 bar
135 l/min
Таблица приведена как напечатана (характеристика — значение); строки 'Cooling power with Thermooil/Ethanol' объединяют подзаголовок и температуру в одну характеристику.
Engineering Facts
12 facts · every claim linked to a page
Selection
The unit is water-cooled and requires a cooling water supply with a minimum differential pressure of 3 bar and maximum pressure of 6 bar.
Cooling water infrastructure must be verified before selection to ensure adequate pressure and flow.
Source
“min. cooling water differential pressure 3 bar”
Installation
The cooling water intake temperature must be between 5°C and 20°C, and pipes must be insulated if condensation occurs.
Ensures proper cooling performance and prevents condensation damage during installation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
The unit requires a 460V 3~ 60Hz power supply with a maximum current of 70 A and 3x80A fuses.
Electrical infrastructure must be sized accordingly before installation.
Source
“Power supply requirement 460V 3~ 60Hz”
Safety
Leakage current exceeds 3.5 mA, so external branch circuit protection according to UL 489 is required.
Mandatory for electrical safety compliance and proper breaker selection.
Source
“Attention: leakage current > 3,5mA”
Installation
Three-phase devices with current consumption greater than 63A are delivered without cable and without plug.
Installer must plan for on-site power cabling and connection.
Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Operation
Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase.
Operators must account for reduced performance at higher cooling water temperatures.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
Pump connections use flange DN32 PN10/40 per EN1092-1, and pipework must use ball socket per DIN 3863 and sleeve nut per DIN 3870.
Correct mating hardware must be procured for leak-free installation.
Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Selection
The refrigerant R-507 has a GWP of 3985 and a CO2 equivalent of 95.6 t, which matters for environmental compliance and reporting.
Refrigerant charge and GWP affect regulatory compliance and environmental reporting.
Source
“Global Warming Potential (GWP) 3985”
Operation
The unit operates within an ambient temperature range of 5°C to 40°C.
Site ambient conditions must be within this range for reliable operation.
Source
“min. ambient temperature 5 °C”
Installation
The unit has a protection degree of IP20, so it must be installed in a dry, protected environment.
Prevents ingress of water and dust that could damage electronics.
Source
“Degree of Protection IP20”
Selection
The maximum permissible kinematic viscosity of the heat transfer fluid is 50 mm²/s.
Ensures proper pump performance and avoids excessive pressure drop.
Source
“max. permissible kin. viscosity 50 mm²/s”
Installation
Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations like -5% voltage and +2% frequency are not allowed.
Prevents improper power supply combinations that could damage the unit.