No photo available yet
Peter Huber Kältemaschinenbau Unistat P645w Dynamisches
Peter Huber Kältemaschinenbau Unistat P645w Dynamisches — Temperature control units.
The Unistat P645w Dynamisches is a water-cooled, free-standing temperature control unit with a magnetically coupled stainless-steel pump, covering -60 to 200 °C with 36 kW heating capacity. It is the high-capacity water-cooled variant of the Unistat 6xx series, distinguished by DN32 PN10/40 process and cooling-water flanges and a 70 A / 460 V 3~ 60 Hz supply. It serves closed-loop temperature control of large externally closed applications requiring high heating power and dynamic performance.
Peter Huber Kältemaschinenbau Unistat Series — Model Comparison & Selection
| Model | Noise level, dB | Display resolution | Heating capacity, W | Pump connection | Pump type | Temperature range, °C |
|---|---|---|---|---|---|---|
| Unistat P645w Dynamisches Current | — | 0, 01 | 36000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat 510w Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat 515w Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat 520w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 525 Dynamisches | 56 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 525w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 527w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 530w Dynamisches | 59 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 540w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 545w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat 610w Dynamisches | 62 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 615w Dynamisches | 62 | 0, 01 | 12000 | M30x1, 5 AG male | Pressure pump, variable | -60–200 |
| Unistat 620w Dynamisches | 68 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 625w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 630w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 635w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 640w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat 645w Dynamisches | — | 0, 01 | 36000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat 650w Dynamisches | 73 | 0, 01 | 48000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
| Unistat 680w Dynamisches | — | 0, 01 | 96000 | DN50 PN16 (DIN EN 1092-1 | magnetically coupled, st | -60–200 |
| Unistat GL 530w Dynamisches | 61 | 0, 01 | 6000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 535w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 540w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 550w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 560w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL 570w Dynamisches | — | 0, 01 | 48000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P530w Dynamisches | 61 | 0, 01 | 6000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P535w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P540w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P550w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P560w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat GL P570w Dynamisches | — | 0, 01 | 48000 | M38x1, 5 AG male | magnetically coupled, st | -50–200 |
| Unistat P510 Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P510w Dynamisches | 60 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P515w Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -50–250 |
| Unistat P520 Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P520w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P525 Dynamisches | 56 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P525w Dynamisches | 61 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P527w Dynamisches | 57 | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P530w Dynamisches | 62 | 0.01 | 12000 | M38x1,5 AG male | magnetically coupled, st | -55–250 |
| Unistat P540w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P545w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -55–250 |
| Unistat P610 Dynamisches | — | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P610w Dynamisches | 62 | 0, 01 | 6000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P615 Dynamisches | — | 0, 01 | 12000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P615w Dynamisches | 62 | 0, 01 | 12000 | M30x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P620w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P625w Dynamisches | — | 0, 01 | 12000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P630w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P635w Dynamisches | — | 0, 01 | 24000 | M38x1, 5 AG male | magnetically coupled, st | -60–200 |
| Unistat P650w Dynamisches | — | 0, 01 | 48000 | flange DN32 PN10/40 EN10 | magnetically coupled, st | -60–200 |
Full specifications
| Control output | POKO ONE (potential-free contact) |
| Expansion volume | 30 l |
| Filling volume | 30 l (min) |
| Heating capacity | 36 kW |
| Pump connection | flange DN32 PN10/40 EN1092-1 |
| Pump speed adjustable | Yes |
| Pump type | magnetically coupled, stainless steel |
| External sensor connection | Pt100 |
| Temperature range | -60...200 °C |
| Weight | 2150 kg (net) |
| Current consumption | 70 A (max) |
| Power supply | 460V 3~ 60Hz |
| Controller | Pilot ONE |
| Display resolution | 0, 01 K |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Maximum viscosity | 50 mm²/s (max permissible) |
| Ambient temperature limit | 5...40 °C (permissible) |
| Cooling water connection | flange DN32 PN10/40 EN1092-1 |
| Cooling water consumption | 6000 l/h (at 15°C, flow 0°C) |
| Cooling water differential pressure | 3 bar (min) |
| Cooling Water Pressure | 6 bar (max) |
| Protection rating | IP20 |
| Safety class | III / FL |
Description
Construction and series positioning
- Free-standing, water-cooled (w suffix) Unistat 6xx-class unit; net weight 2150 kg, IP20 protection, ambient range 5–40 °C.
- Process and cooling-water connections both use flange DN32 PN10/40 EN1092-1; pump is magnetically coupled, stainless steel, with adjustable speed.
- Controller is Pilot ONE with POKO ONE potential-free contact output; interfaces Ethernet, USB (Host and Device) and RS232; external Pt100 sensor input.
- Safety class III / FL per DIN 12876; 30 l expansion volume and 30 l minimum filling volume.
- Sibling models in the series (Unistat 510w, 515w, 520w, 525 Dynamisches) are smaller air- or water-cooled units; this P645w is the high-power water-cooled member with 36 kW heating and 70 A maximum current.
Behavior under load and media
- Working range -60 to 200 °C with 0.01 K display resolution; maximum permissible kinematic viscosity of the heat transfer fluid is 50 mm²/s.
- Cooling is water-side dependent: 6000 l/h cooling-water consumption at 15 °C with 0 °C flow, minimum differential pressure 3 bar, maximum pressure 6 bar. Cooling power drops as cooling-water temperature rises and flow rate may need to increase.
- FL-rated fluid must have a fire point ≥ 65 °C; ethanol use is permitted only under supervision.
- Process Safety mode releases maximum cooling capacity at the overtemperature trigger instead of switching off all poles, and requires the compressor set to Permanently ON.
Installation, connection and control
- Requires 460 V 3~ 60 Hz supply, maximum 70 A, 3×80 A fuses; leakage current >3.5 mA so UL 489 branch protection is mandatory. Units >63 A are delivered without cable and plug; hard-wiring must be done by an electrician.
- Voltage tolerance ±5% with frequency ±2%, but the combination -5% voltage and +2% frequency is not allowed.
- Cooling-water intake temperature 5–20 °C; insulate pipes if condensation occurs. Install a drip tray below the unit where required by local legislation.
- Expansion vessel must remain unlocked for externally closed applications and locked for externally open (bath) applications.
- Power-interruption response is configurable via Pilot ONE: Off/Standby (default) or ON/Temperature control active with a short INFO window to cancel automatic restart.
Integration & Operating Notes
The 70 A maximum current and >3.5 mA leakage current require external UL 489 branch-circuit protection, and because current exceeds 63 A the unit ships without cable and plug. The installer must size conductors, fuses (3×80 A) and the disconnect means before the unit can be energised.
The cooling circuit needs at least 3 bar differential pressure but must not exceed 6 bar, while consuming 6000 l/h at 15 °C. Supply pressure below 3 bar will starve the condenser; above 6 bar the plate heat exchanger and connections are at risk. Intake temperature must stay between 5 and 20 °C.
For an externally closed circuit the expansion vessel must remain unlocked; locking it causes overpressure damage to the application. For an externally open bath the vessel must be locked to prevent fluid loss. Verify the isolating sleeve or shut-off valve position before filling and venting.
In Process Safety mode the controller releases maximum cooling capacity at the overtemperature trigger rather than switching off all poles. This behaviour depends on the compressor being configured to Permanently ON; otherwise the safety response will not deliver the intended heat extraction under exothermic conditions.
The unit must be transported and stored upright only, and moved only when emptied. After moving between cold and warm environments, allow about 2 hours acclimation before switching on to avoid condensation-induced electrical faults. Leveling feet must be activated and caster brakes engaged before commissioning.
Shut off the cooling-water supply even for overnight downtime to avoid unnecessary load and water damage. Hoses and hose connections must be checked periodically for leaks and quality and replaced as required; the hat-type strainer/dirt trap requires draining the cooling circuit before dismantling.
Selection & Integration Q&A
Pick the P645w when the application needs 36 kW heating, a 70 A 460 V 3~ supply and DN32 PN10/40 flanges for high flow. The 510w/515w/520w/525 siblings are lower-capacity units; choose them when the heating load and cooling-water flow (6000 l/h here) cannot be supported on site.
A 460 V 3~ 60 Hz supply with 3×80 A fuses and UL 489 branch protection, on-site power cabling (no cable/plug supplied above 63 A), a cooling-water supply of 3–6 bar differential at 6000 l/h and 5–20 °C, and mating DN32 PN10/40 EN1092-1 flanges with DIN 3863 ball sockets and DIN 3870 sleeve nuts.
Install only outside ATEX zones, indoors in a dry IP20-protected location, ambient 5–40 °C, on a level floor with a drip tray where required. Transport upright and emptied, allow 2 h acclimation after temperature changes, and shut off cooling water during overnight downtime.
The base unit ships without power cable and plug, without heat transfer fluid, and without the optional gas detection sensor or processing unit. Periodic tasks include hose and connection inspection/replacement, cleaning the liquefier fins and hat-type strainer, and heat transfer fluid inspection/replacement with circuit rinsing.