Product introduction and general description of the Unistat P925w unit
Specpp. 1-2
Technical data and performance specifications according to DIN 12876
p. 2table, 26 rows
p. 1table, 31 rows
Technical data according to DIN 12876
Parameter
Value
Circulation pump
MK pump
max. delivery
191 l/min
max. delivery pressure
5,5 bar
Delivery at 1,0 bar
167 l/min
Delivery at 2,0 bar
140 l/min
Delivery at 3,0 bar
107 l/min
Delivery at 4,0 bar
67 l/min
Delivery at 5,0 bar
22 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
50 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
1300 l/h
min. cooling water differential pressure
1 bar
max. cooling water pressure
6 bar
min. filling capacity
12 l
Filling capacity expansion tank
29 l
Overall dimensions WxDxH **
950x1205x1650 mm
Net weight
994 kg
Power supply requirement
400V 3~ 50Hz
max. current
52 A
Fuse
3x63A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S517345
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Characteristic
Unistat P925w
Order-No.
1081.0003.01
Operating temperature range
-90...200 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
12 kW
Cooling power with Thermooil at 200°C
16 kW
Cooling power with Thermooil at 100°C
16 kW
Cooling power with Thermooil at 20°C
16 kW
Cooling power with Ethanol at 0°C
16 kW
Cooling power with Ethanol at -20°C
16 kW
Cooling power with Ethanol at -40°C
15 kW
Cooling power with Ethanol at -60°C
13,5 kW
Cooling power with Ethanol at -80°C
3,5 kW
Cooling power with Ethanol at -90°C
1,8 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
5 kg
CO2 equivalent
10,7 t
Refrigerant 2nd stage (ASHRAE, GHS)
R-23 (A1, H280)
Global Warming Potential (GWP)
14800
Refrigerant quantity 2nd stage
2,2 kg
CO2 equivalent 2nd stage
32,6 t
Engineering Facts
14 facts · every claim linked to a page
Installation
The unit requires a 400 V 3~ 50 Hz supply with a maximum current of 52 A and 3x63 A fusing, so the electrical installation must be sized accordingly.
Determines the site power distribution, cable cross-section and breaker rating needed before installation.
Source
“Power supply requirement 400V 3~ 50Hz max. current 52 A Fuse 3x63A”
Installation
Cooling water must be supplied at 5–20 °C with at least 1 bar differential pressure and no more than 6 bar, and the specified flow is 1300 l/h at 15 °C.
Sizing the cooling water circuit and verifying available pressure/flow is mandatory for achieving rated cooling capacity.
Source
“Consumption at water 15°C, flow 0°C 1300 l/h min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Prevents corrosion and fouling that would degrade heat transfer and damage the water-cooled refrigeration machine.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.
Avoids condensation, dripping and corrosion on the unit when using cold cooling water.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation
The pump connection is M38x1.5 male and the cooling water connection is G3/4 male, so matching hoses and adapters must be provided.
Ensures correct mechanical interface for process piping and cooling water hook-up.
Source
“Pump connection M38x1,5 male”
Installation
Three-phase devices with current consumption less than 63 A are delivered with cable but without plug, so a suitable plug must be sourced on site.
Affects electrical commissioning planning and the bill of materials for the installation.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The leakage current exceeds 3.5 mA, which requires attention to protective earthing and residual current device selection.
Impacts electrical safety design and choice of RCD type for the supply circuit.
Source
“Attention: leakage current > 3,5mA”
Safety
The refrigerant R-452A has a GWP of 2141 and 5 kg charge (10.7 t CO2e), while the second stage R-23 has a GWP of 14800 and 2.2 kg charge (32.6 t CO2e).
Relevant for F-gas compliance, leak monitoring obligations and environmental reporting.
Source
“Global Warming Potential (GWP) 2141 Refrigerant quantity 5 kg CO2 equivalent 10,7 t”
Safety
The unit has safety classification III / FL and adjustable overtemperature protection according to DIN 12876.
Confirms suitability for flammable or high-risk temperature control applications and defines the safety concept.
Source
“Safety classification III / FL”
Operation
The operating temperature range is -90 to 200 °C with a display resolution of 0.01 K and a Pt100 internal sensor plus external Pt100 connection.
Defines the process window and the need for an external sensor for process control.
Source
“Operating temperature range -90...200 °C”
Performance
Cooling power drops sharply at low temperatures, from 16 kW at -20 °C to 3.5 kW at -80 °C and 1.8 kW at -90 °C.
Critical for sizing the unit to the actual heat load at the lowest required process temperature.
Source
“at -80°C 3,5 kW at -90°C 1,8 kW”
Performance
The MK circulation pump delivers up to 191 l/min and 5.5 bar, with 22 l/min still available at 5.0 bar.
Determines whether the pump can overcome the pressure drop of the external process loop.