Installation
The chiller requires a three-phase 400 V supply with a 3x20 A fuse, so the electrical installation must be sized accordingly.
Determines the site power supply, cable and protection device rating before installation.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation
The unit is delivered for three-phase connection below 63 A with a cable but without a plug, so a suitable plug must be provided on site.
Affects electrical installation planning and the bill of materials for commissioning.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances must be respected simultaneously, and some combinations such as -5% voltage with +2% frequency are not allowed.
Prevents selecting a site supply or generator that would violate the permissible operating envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The chiller must be operated within an ambient temperature range of 5 °C to 32 °C.
Defines the allowable plant-room conditions and rules out cold or hot locations outside this range.
Source
“min. ambient temperature 5 °C”
Performance
Cooling capacity is rated at 20 °C room temperature and may drop if the ambient temperature rises.
Prevents oversizing assumptions based on nominal capacity when the actual plant room is warmer.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Selection
The unit uses refrigerant R-449A with a CO2 equivalent of 6.29 t, which matters for refrigerant reporting and safety classification.
Needed for refrigerant inventory, leak reporting and safety classification of the installation.
Source
“R-449A (A1, H280)”
Installation
The chiller has IP52 protection, so it is protected against dust and dripping water but not against water jets or immersion.
Constrains cleaning methods and placement in wet or washdown environments.
Source
“Degree of Protection IP52”
Selection
The tank filling capacity is between 160 l and 175 l, which sets the required heat-transfer fluid volume.
Used to size the fluid charge and expansion volume for the system.
Source
“min. filling capacity 160 l”
Selection
The recommended thermofluid is a 50:50 water-monoethylene glycol mixture.
Ensures compatible fluid selection for the operating temperature range down to -20 °C.
Source
“Recommended thermofluid: Water - Monoethylene Glycol 50:50”
Installation
The pump connection is G3/4 male, so mating hoses or adapters must match this thread.
Determines the connection hardware needed for the hydraulic circuit.
Source
“Pump connection G3/4 male”
Operation
Flow rate can be adjusted via the manual bypass valve on the back of the chiller, allowing the pump delivery to be matched to the application.
Important for commissioning and for avoiding excessive flow or pressure in the external circuit.
Source
“The flow rate can be adjusted via the manual bypass valve on the backside of the chiller.”
Cumplimiento
The equipment is classified as EN55011 Class A Group 1, which has implications for electromagnetic compatibility in residential areas.
Class A equipment may not be suitable for residential environments without additional EMC measures.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation
Space requirements around the unit must be respected according to the operating conditions.
Affects layout planning and air-cooled condenser clearance for reliable operation.
Source
“Please respect space requirements. See operating conditions at www.huber-online.com”