Performance, temperature, and technical data per DIN 12876
p. 2table, 3 rows
p. 1table, 33 rows
Technical data according to DIN 12876
Parameter
Value
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/26
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-20...40 °C
temperature set point / display
5,7" colour Touchscreen
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Temperature stability at -10°C
0,2 K
Interface digital
Ethernet, USB (Host u. Device), RS232
Safety classification
I / NFL
Cooling power at 20°C
100 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
UN-number
UN 2857
max. delivery
320 l/min
max. delivery pressure
4 bar
Delivery at 0,5 bar
305 l/min
Delivery at 1,0 bar
285 l/min
Delivery at 1,5 bar
260 l/min
Delivery at 2,0 bar
240 l/min
Delivery at 2,5 bar
215 l/min
Delivery at 3,0 bar
185 l/min
Delivery at 3,5 bar
150 l/min
Delivery at 4,0 bar
110 l/min
Delivery at 4,5 bar
50 l/min
Pump connection
G1 1/4 male
Cooling water connection
G1 1/4 male
min. cooling water differential pressure
1 bar
max. cooling water pressure
6 bar
min. filling capacity
17,5 l
Volume of expansion
50 l
Overall dimensions WxDxH **
918x963x1772 mm
Power supply (3 Phase)
460V 3~ 60Hz
Pressure equipment category
II
Degree of Protection
IP20
** Overall dimensions WxDxH
Engineering Facts
14 facts · every claim linked to a page
Selection
The chiller is rated for 100 kW cooling at 20 °C, so verify the process heat load does not exceed this at the stated conditions.
Cooling capacity determines whether the unit can handle the process load at the specified operating point.
Source
“Cooling power at 20°C 100 kW”
Installation
The unit requires a water-cooled refrigeration circuit with cooling water inlet between 5 °C and 20 °C and at least 1 bar differential pressure.
Cooling water temperature and pressure limits dictate facility utility requirements and pipe sizing.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature falls below the condensation point, the cooling water pipes inside the unit must be insulated.
Condensation on internal pipes can cause corrosion or electrical issues, so insulation is a mandatory installation measure.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation
The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so the cooling water must be compatible with these materials.
Water quality and treatment must be selected to avoid corrosion or fouling of these materials.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and the combination of -5% voltage with +2% frequency is not allowed.
Supply power quality must be checked to avoid operating the unit outside its allowed voltage/frequency envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
Leakage current exceeds 3.5 mA, so protective earthing and residual current protection must be designed accordingly.
High leakage current affects earth conductor sizing and RCD selection for safe electrical installation.
Source
“Attention: leakage current > 3,5mA”
Cumplimiento
External branch circuit protection according to UL 489 is required for this unit.
The electrical panel must include a UL 489 listed breaker to meet installation compliance.
Source
“External branch circuit protection according to UL 489 required.”
Installation
Three-phase devices with current consumption less than 63 A are supplied with cable but without a plug.
The installer must provide a suitable plug or hardwired connection for this 460 V three-phase unit.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation
The unit is rated for ambient temperatures from 5 °C to 40 °C, so the installation location must stay within this range.
Ambient temperature outside this range can affect cooling performance and reliability.
Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection
The pump delivers 320 l/min maximum and 110 l/min at 4.0 bar, so the external circuit pressure drop must be matched to the pump curve.
Pump flow and pressure capability determine whether the external loop can be supplied at the required rate.
Source
“max. delivery 320 l/min”
Installation
The pump and cooling water connections are G1 1/4 male, so mating hoses and fittings must be specified accordingly.
Connection thread size and type determine the hose couplings and adapters needed for installation.
Source
“Pump connection G1 1/4 male”
Safety
The unit has adjustable overtemperature protection according to DIN 12876, which must be set for the application.
Overtemperature protection is a safety function that must be configured to protect the process and equipment.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Operation
The unit is for externally closed applications, so it must not be used with an open external circuit.
Using the unit outside its intended circuit type can cause overflow, contamination, or unsafe operation.
Source
“For externally closed applications.”
Maintenance
The refrigerant is R-744 (A1, H280) with GWP 1, and the UN number is UN 2857, which affects handling and service requirements.
Refrigerant safety class and GWP influence service procedures, leak detection, and environmental compliance.