Huber CS 550 OD Circulating Bath Datasheet

Sommaire

  1. Overview p. 1
    Product identification and general description of the CS 550 OD unit
  2. Spec pp. 1-2
    Technical data, performance figures and operating limits per DIN 12876
  3. p. 2 table, 14 rows
  4. p. 1 table, 40 rows

Technical data according to DIN 12876

ParameterValue
max. delivery pressure4,7 bar
Pump connectionG1 male
min. filling capacity160 l
Bath volume advance warning175 l
max. filling capacity195 l
Overall dimensions WxDxH **1400x1000x1800 mm
Net weight540 kg
sound pressure level +/- 4 dB(A)79 dB(A)
Power supply (3 Phase)460V 3~ 60Hz
max. current (3 Phase)50 A
Fuse (3 phase)3x60A
min. ambient temperature-20 °C
max. ambient temperature50 °C
from Serial-No.:1.0/20

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-20...15 °C
temperature set point / displaycolour LED Touchscreen
Internal temperature sensorPt100
Temperature stability at -10°C2 K
Interface digitalRS232
Safety classificationI / NFL
Kälteleistung bei Umgebungstemperatur 5°C
at 15°C61 kW
at 10°C54 kW
at 0°C29 kW
at -10°C15 kW
at -20°C9 kW
Cooling power at ambient temperature 20°C
at 15°C70 kW
at 10°C60 kW
at 0°C33 kW
at -10°C20 kW
at -20°C12 kW
Kälteleistung bei Umgebungstemperatur 35°C
at 15°C63 kW
at 10°C55 kW
at 0°C29 kW
at -10°C16 kW
at -20°C9 kW
Kälteleistung bei Umgebungstemperatur 40°C
at 15°C55 kW
at 10°C49 kW
at 0°C25 kW
at -10°C13 kW
at -20°C7 kW
Kälteleistung bei Umgebungstemperatur 50°C
at 15°C44 kW
at 10°C41 kW
at 0°C19 kW
at -10°C9 kW
Refrigeration machineair-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Refrigerant quantity16 kg
CO2 equivalent22,35 t
Circulation pump:

Engineering Facts

14 facts · every claim linked to a page
Selection

The chiller's cooling capacity drops significantly as ambient temperature rises, so selection must be based on the actual site ambient temperature.

Cooling capacity at 50°C ambient is much lower than at 20°C, so undersizing risk exists if ambient is underestimated.

Source
“If the ambient temperature rises, the cooling capacity may drop.”
Installation

The unit is suitable for outdoor mounting down to -20°C ambient, which affects enclosure and freeze protection planning.

Outdoor installation requires considering low ambient temperatures and possible freezing of heat transfer fluid.

Source
“Suitable for outside mounting (min. environmental temperature -20°C)”
Installation

The remote control panel is connected via a 20 m cable, so the operating panel can be located away from the chiller.

Cable length constrains where the control panel can be mounted relative to the chiller.

Source
“Delivered with remote control: operating panel connected via 20m cable”
Installation

The electrical components have IP54 protection, which is relevant for outdoor or washdown-adjacent installations.

IP54 limits dust and water ingress but is not waterproof; installation environment must match.

Source
“Protection classification of the electrical components IP54”
Installation

Three-phase devices under 63 A are supplied with cable but without a plug, so the site must provide a suitable disconnect and plug.

Electrical installation planning must include a plug and suitable power connection by the customer.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation

Voltage and frequency tolerances are interdependent: -5% voltage with +2% frequency is not allowed, but -5% voltage with -2% frequency is allowed.

Site power quality must be checked against the combined tolerance rule to avoid invalid supply conditions.

Source
“-5% voltage and +2% frequency -> not allowed!”
Safety

The refrigerant is R-449A with GHS hazard H280, so refrigerant handling and leak response procedures must account for a pressurized gas hazard.

H280 indicates gas under pressure; service and ventilation requirements must be planned accordingly.

Source
“R-449A (A1, H280)”
Safety

The unit contains 16 kg of R-449A with a CO2 equivalent of 22.35 t, which triggers refrigerant leak-check and reporting obligations in many jurisdictions.

CO2 equivalent above certain thresholds requires periodic leak checks and record keeping.

Source
“CO2 equivalent 22,35 t”
Operation

The recommended thermofluid is a 50:50 water-monoethylene glycol mixture, which sets the freeze protection and heat transfer basis.

Using the wrong fluid can cause freezing, corrosion, or reduced heat transfer at low temperatures.

Source
“Recommended thermofluid: Water - Monoethylene Glycol 50:50”
Operation

The flow rate can be adjusted via a manual bypass valve on the backside of the chiller, allowing matching to the application.

Bypass adjustment is needed to set correct flow and pressure for the connected load.

Source
“The flow rate can be adjusted via the manual bypass valve on the backside of the chiller.”
Performance

The pump delivers up to 125 l/min at up to 4.7 bar, which defines the achievable flow and pressure for the external circuit.

External circuit pressure drop must be checked against the pump curve to ensure adequate flow.

Source
“max. delivery pressure 4,7 bar”
Performance

The bath volume ranges from 160 l minimum to 195 l maximum, with a warning at 175 l, which affects fluid charge and expansion planning.

Fluid volume and expansion space must be planned within the stated filling limits.

Source
“min. filling capacity 160 l”
Conformité

The equipment is classified as EN55011 Class A Group 1, which means it is intended for industrial electromagnetic environments and may cause interference in residential areas.

Class A equipment may require additional EMC measures if installed near sensitive or residential equipment.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Conformité

The US-SNAP end-use for this equipment is industrial process refrigeration, which limits its permitted application in the US.

Application must fall within the SNAP end-use to remain compliant in the US market.

Source
“The US-SNAP end-use for this equipment is the industrial process refrigeration.”