Installation
The chiller requires a three-phase 400 V supply with a 3x16 A fuse, so the electrical installation must be sized accordingly.
Determines the mains connection, cable and protection device needed at the installation site.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation
The unit is water-cooled and needs a cooling water supply with at least 1.5 bar differential pressure and no more than 6 bar.
Cooling water pressure must be verified before installation to ensure sufficient flow and avoid overpressure damage.
Source
“min. cooling water differential pressure 1,5 bar”
Installation
Cooling water inlet temperature must be kept between 5 °C and 20 °C, and pipes must be insulated if below the condensation point.
Out-of-range cooling water temperature affects cooling capacity and can cause condensation and corrosion.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power drops significantly as the working temperature decreases, from 7 kW at 15 °C to 2.5 kW at -10 °C.
Process heat load must be matched to the available cooling capacity at the actual operating temperature.
Source
“at 15°C 7 kW”
Performance
The circulation pump delivers 84 l/min maximum, but flow falls sharply at higher pressure, down to 7 l/min at 5.5 bar.
External circuit pressure drop must be checked against the pump curve to ensure adequate flow.
Source
“max. delivery 84 l/min”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280, and the charge is 1.35 kg with a CO2 equivalent of 1.9 t.
Refrigerant safety class and charge affect room ventilation, leak detection and environmental reporting obligations.
Source
“R-449A (A1, H280)”
Operation
The unit is rated IP20 and must be operated between 5 °C and 40 °C ambient temperature.
Ambient conditions in the installation room must be controlled to avoid overheating or condensation.
Source
“max. ambient temperature 40 °C”
Installation
The chiller is intended for externally closed applications and has an atmospheric open expansion tank.
The hydraulic circuit must be designed as a closed loop; open baths or unsealed circuits are not suitable.
Source
“For externally closed applications.”
Compliance
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Site power quality must be checked to avoid invalid supply combinations that could damage the unit.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
Three-phase devices below 63 A are supplied with cable but without a plug, so a suitable plug must be provided on site.
The electrical installer must plan for a matching plug and socket, not assume a ready-to-plug unit.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality may be used.
Water chemistry must be compatible with these materials to prevent corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Selection
The unit has a minimum filling capacity of 5.9 l and an expansion volume of 7.5 l, which sets the minimum external circuit volume.
External loop volume and expansion must be considered when selecting and commissioning the system.
Source
“min. filling capacity 5,9 l”