Installation
The chiller requires a three-phase 400 V supply, so the site must provide a 3~ 50 Hz feed.
Determines electrical infrastructure and whether a suitable three-phase supply is available at the installation point.
Source
“Power supply (3 Phase) 400V 3~ 50Hz”
Installation
The unit is IP20, so it must be installed in a dry indoor location protected from water and dust ingress.
Affects placement and enclosure requirements; IP20 is not suitable for wet or dusty environments.
Source
“Degree of Protection IP20”
Installation
Ambient temperature at the installation site must stay between 5 °C and 40 °C.
Defines allowable room conditions and ventilation/cooling needs for reliable operation.
Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation
Cooling water supply must provide at least 1 bar differential pressure and must not exceed 6 bar.
Sizing the cooling water circuit and pump/valve selection depends on these pressure limits.
Source
“min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”
Installation
Cooling water inlet temperature must be between 5 °C and 20 °C, and pipes must be insulated if it can drop below the condensation point.
Prevents condensation and ensures rated cooling performance; affects facility water system design.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Rated cooling power is specified at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure.
Performance figures must be corrected if site conditions differ from these reference values.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and - outlet.”
Performance
Cooling capacity drops as cooling water temperature rises, and required cooling water flow may increase.
Prevents oversizing assumptions and ensures the water circuit can handle higher flow at warmer supply temperatures.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality should be used.
Guides water treatment and material compatibility to avoid corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation
Three-phase devices below 63 A are delivered with cable but without a plug, so a suitable plug must be provided on site.
Affects electrical installation scope and commissioning planning.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Compliance
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Ensures the supply quality is within the unit's allowed operating envelope and avoids invalid combinations.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety
The unit has adjustable overtemperature protection according to DIN 12876 and safety classification III / FL.
Relevant for safety assessment and setting protection limits for the application.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Selection
The refrigerant is R-449A with GWP 1397 and safety group A1, H280.
Affects environmental compliance, refrigerant handling and leak-detection requirements.
Source
“R-449A (A1, H280)”
Installation
Minimum filling capacity is 15 l and expansion volume is 22 l, which must be considered when sizing the external loop.
Determines heat transfer fluid volume and expansion tank adequacy for the installed system.
Source
“min. filling capacity 15 l Volume of expansion 22 l”
Installation
Pump connections are G1 1/4 male and cooling water connections are G3/4 male.
Needed to select matching hoses, couplings and adapters before installation.
Source
“Pump connection G1 1/4 male Cooling water connection G3/4 male”