Peter Huber Kältemaschinenbau Unichiller 260Tw-H
Peter Huber Kältemaschinenbau ·Made in Germany · In Active Production

Peter Huber Kältemaschinenbau Unichiller 260Tw-H

Peter Huber Kältemaschinenbau Unichiller 260Tw-H — Recirculating chillers.

The Unichiller 260Tw-H is a water-cooled recirculating chiller with a 2 kW heater and a fixed-speed D3 pressure pump, covering -20 to 100 °C. It is the high-capacity Tw-H modification in the Unichiller series, distinguished by its 400 V three-phase supply and G1 1/4 pump connection. It serves externally closed process loops requiring temperature control with cooling water available at 5–20 °C.

Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection

Model Pump typeSafety classTemperature range, °CPower supplyExpansion volume, m³Minimum fill volume, m³
Unichiller 260Tw-H Current D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 110T C3I / NFL-10–40400V 3~ 50Hz0.007—
Unichiller 110T-H C3III / FL-10–100400V 3~ 50Hz0.007—
Unichiller 110Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 130T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 130T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 130Tw C3I / NFL-20–40400V 3~ 50Hz——
Unichiller 160T C3I / NFL-10–40400V 3~ 50Hz0.0390.014
Unichiller 160T-H C3III / FL-10–100400V 3~ 50Hz0.0390.014
Unichiller 160Tw C3I / NFL-20–40400V 3~ 50Hz0.01—
Unichiller 180-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 180T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 180T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 180Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 180Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 180w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 180w-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 200T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 200Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 210T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 210T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 210Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 230-H E1III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller 230w E1I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller 230w-H E1III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller 250T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 250T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 250Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 260T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 260T-H D3III / FL-20–100400V 3~ 50Hz0.0390.014
Unichiller 260Tw D3I / NFL-20–40400V 3~ 50Hz0.0220.015
Unichiller 300T D3I / NFL-20–40400V 3~ 50Hz0.0390.014
Unichiller 300T-H D3III / FL-20–100460V 3~ 60Hz0.0390.014
Unichiller 300Tw D3I / NFL-20–40460V 3~ 60Hz0.0220.015
Unichiller 300Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 350T D3I / NFL-20–40460V 3~ 60Hz0.0390.014
Unichiller 350Tw-H D3III / FL-20–100400V 3~ 50Hz0.0220.015
Unichiller 500Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 600Tw-H D3III / FL-20–100400V 3~ 50Hz0.007—
Unichiller 700Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller 800Tw D3I / NFL-20–40400V 3~ 50Hz0.007—
Unichiller GL 1000w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.05—
Unichiller GL 200w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 250w Pressure pump, speed notI / NFL-20–40460V 3~ 60Hz0.03—
Unichiller GL 300w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 400w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.03—
Unichiller GL 750w Pressure pump, speed notI / NFL-20–40400V 3~ 50Hz0.05—
Unichiller P180 E2I / NFL-20–40—0.0480.018
Unichiller P180-H E2III / FL-20–100400V 3~ 50Hz0.0480.018
Unichiller P180w E2I / NFL-20–40400V 3~ 50Hz0.0480.018
Unichiller P180w-H E2III / FL-20–100460V 3~ 60Hz0.0480.018
Unichiller P230 E2I / NFL-20–40460V 3~ 60Hz0.0480.018
Unichiller P230-H E2III / FL-20–100460V 3~ 60Hz0.0480.018

Full specifications

Core Performance & Functional Specifications
Expansion volume 22 l
Heating capacity 2 kW
Minimum fill volume 15 l
Pump connection G1 1/4 AG male
Pump speed adjustable no
Pump type D3
External sensor connection Pt100
Temperature range -20...100 °C
Electrical, Power & Drive Specifications
Power supply 400V 3~ 50Hz
Interfaces, Connections & Control
Controller Pilot ONE
Digital interface Ethernet, USB (Host u. Device), RS232
Operating Conditions, Environment & Protection
Ambient temperature limit 5...40 °C
Cooling water connection G3/4 male
Cooling water differential pressure 1 bar (min)
Cooling Water Pressure 6 bar (max)
Protection rating IP20
Standards, Safety & General Data
Safety class III / FL

Description

Construction and series positioning

The Unichiller 260Tw-H is a water-cooled (W) recirculating chiller with heater (H) in the Unichiller series. Unlike the smaller 110T/110Tw siblings, this model is supplied from a 400 V three-phase 50 Hz feed and uses a fixed-speed D3 pressure pump with G1 1/4 male pump connections. The cooling water circuit connects via G3/4 male fittings. The unit is rated IP20 and safety class III / FL with adjustable overtemperature protection to DIN 12876. Refrigerant is R-449A (A1, H280, GWP 1397).

Working range and media behavior

The temperature range is -20 to 100 °C. Cooling water inlet must be 5–20 °C; rated cooling power is quoted at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure. As cooling water temperature rises, cooling capacity drops and required flow may increase. The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so water quality must be compatible. Minimum fill volume is 15 l and expansion volume is 22 l.

Installation and control

Installation is indoors only, at 5–40 °C ambient, at least 300 lx illuminance and up to 2000 m altitude, with 50–200 cm wall clearance per side for maintenance. The unit is not explosion-protected and must not be installed in an ATEX zone. Three-phase devices below 63 A are delivered with cable but without a plug. The Pilot ONE controller provides Ethernet, USB host/device and RS232 interfaces, a Pt100 external sensor connection, and configurable power-failure response (OFF/Standby, ON, Power Failure Auto). Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached.

Integration & Operating Notes

Electrical
Three-phase feed needs a site-supplied plug and stable frequency

The 400 V 3~ 50 Hz supply is delivered with cable but no plug for currents below 63 A, so a suitable plug and protection must be provided on site. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.

Unichiller 260Tw-H Chiller Datasheet, page 2
Process Limits
Cooling water must stay within 5–20 °C and 1–6 bar

The cooling water supply must provide at least 1 bar differential pressure and must not exceed 6 bar. Inlet temperature must be between 5 and 20 °C; below the condensation point, pipes must be insulated. Higher cooling water temperatures reduce capacity and may require increased flow.

Unichiller 260Tw-H Chiller Datasheet, pages 1–2
Mounting
Indoor site with 50–200 cm side clearance and leveling

Install indoors at 5–40 °C ambient, at least 300 lx, up to 2000 m altitude, with 50–200 cm wall clearance per side for maintenance. Before start-up, activate parking brakes and/or unscrew leveling feet. Electrical lines directly below the unit must be protected against liquid ingress from condensation.

Unichiller Operation Manual, pages 25, 28, 31
Safety
Process Safety mode releases max cooling on OT trigger

For exothermic processes, configure Process Safety so that maximum cooling capacity is released when the overtemperature trigger value is reached, instead of switching off all poles. The power-failure response can be set to OFF/Standby, ON, or Power Failure Auto via the Pilot ONE.

Unichiller Operation Manual, pages 18–19
Maintenance
Refrigerant circuit work only by approved contractors

Any work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. Check refrigerant charge against room size at installation to avoid exceeding the limit per m³ of ambient air. Shut off cooling water even for short downtimes such as overnight.

Unichiller Operation Manual, pages 15, 17, 28
Process Limits
Externally closed loop only; not for ATEX zones

The unit is designed for externally closed applications and must not be installed or started up inside an ATEX zone because it is not explosion-protected. Models with 'P' in the name are the ones suited to high pressure drop; this model uses a fixed-speed D3 pump.

Unichiller Operation Manual, pages 13, 34

Selection & Integration Q&A

When should I choose the 260Tw-H over the smaller 110T/110Tw siblings?

Choose the 260Tw-H when you need a 400 V three-phase feed, a 2 kW heater and the higher capacity implied by the 260 size code, with a fixed-speed D3 pump. The 110T/110Tw siblings are smaller and differ in noise level (74 vs 65 dB(A)); select them when their capacity and single-phase supply match the load.

What adjacent system parts and connections must I provide for this chiller?

Provide a 400 V 3~ 50 Hz supply with a site-fitted plug (cable supplied, no plug below 63 A), cooling water at 5–20 °C and 1–6 bar differential, G3/4 male cooling water fittings, and G1 1/4 male pump connections with compatible hoses. The external loop must hold at least 15 l fill and fit within 22 l expansion.

What mounting and duty-cycle limits apply from the manual?

Install indoors only at 5–40 °C ambient, at least 300 lx, up to 2000 m altitude, with 50–200 cm wall clearance per side. Activate parking brakes and leveling feet before start-up. Shut off cooling water even overnight. The unit is not ATEX-rated and is limited to externally closed applications.

What maintenance and accessories are not included in the base delivery?

The base delivery includes cable but no plug for three-phase units below 63 A. Refrigerant circuit work requires approved contractors. No consumables or spare parts are listed in the digests; plan for compatible cooling water treatment and hose/adapters for G1 1/4 and G3/4 connections separately.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Unichiller 260Tw-H Chiller Datasheet
Datasheet ·172,8 КБ ·2 pp.
View PDF
PDF
Unichiller Operation Manual
Manual ·2,8 МБ ·82 pp.
View PDF