Selection
The chiller is rated for an operating temperature range of -10 to 40 °C, so the process must stay within these limits.
Defines the usable process temperature window and excludes applications outside it.
Source
“Operating temperature range
-10...40 °C”
Safety
The unit uses flammable R-290 refrigerant (A3, H220), so installation must respect flammable-refrigerant safety rules.
Affects site safety classification, ventilation, and ignition-source control during installation.
Source
“R-290 (A3, H220)”
Installation
The refrigerant charge is only 0.22 kg with a GWP of 0.02, which simplifies leak reporting and environmental compliance.
Small charge and negligible CO2 equivalent reduce regulatory burden for the installation.
Source
“Refrigerant quantity
0,22 kg”
Performance
Cooling capacity drops from 2.5 kW at 15 °C to 1.2 kW at -10 °C, so sizing must use the capacity at the actual operating point.
Prevents undersizing when the process runs at low temperatures.
Source
“at 15°C
2,5 kW
at 0°C
2 kW
at -10°C
1,2 kW”
Performance
The pump delivers 25 l/min max and 6 l/min at 2.0 bar, so system pressure drop must be checked against the pump curve.
Ensures the circulation pump can overcome the actual hydraulic resistance of the loop.
Source
“max. delivery
25 l/min”
Installation
The pump connection is G3/4 male, so mating hoses and fittings must be G3/4 female.
Determines the connection hardware needed for plumbing the unit into the process.
Source
“Pump connection
G3/4 male”
Installation
The minimum filling capacity is 3.8 l with 1.7 l expansion volume, so the loop must be filled and expansion space respected.
Sets the minimum fluid volume and expansion vessel requirement for safe operation.
Source
“min. filling capacity
3,8 l”
Installation
The unit requires 220-240 V single-phase 50 Hz supply with 9 A max current and a 16 A fuse.
Defines the electrical supply and protection rating needed at the installation site.
Source
“Power supply requirement
220-240V 1~ 50Hz”
Installation
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and some combinations are not allowed.
Prevents connecting the unit to a supply outside the permitted combined tolerance.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
The degree of protection is IP20, so the unit must be installed in a dry, indoor environment.
Restricts installation location regarding moisture and dust ingress.
Source
“Degree of Protection
IP20”
Installation
Ambient temperature must stay between 5 °C and 40 °C, and cooling capacity may drop above 20 °C.
Defines the room conditions required for reliable operation and rated performance.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these fluids must be avoided or a more resistant pump ordered.
Prevents chemical attack on the pump and premature failure.
Source
“The plastic pump is not resistant against acetone and polyglycols”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.
Avoids freezing and damage when operating near or below 0 °C.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Compliance
The equipment is classified as Class A, Group 1 for electromagnetic disturbance to EN55011.
Affects EMC compatibility and installation in residential or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”