Peter Huber Kältemaschinenbau Unichiller P025
Peter Huber Kältemaschinenbau Unichiller P025 — Recirculating chillers with Noise level 64 dB.
The Unichiller P025 is a single-phase recirculating chiller with a 'P' designation for high-pressure-drop loops, rated -10 to 40 °C and 2.5 kW at 15 °C. Its non-adjustable pump delivers 25 l/min max and 6 l/min at 2.0 bar, distinguishing it from lower-capacity siblings. It serves externally closed cooling circuits requiring G3/4 connections and Pilot ONE control.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Model | Noise level, dB | Controller | Safety class | Temperature range, °C | Interface | Power supply |
|---|---|---|---|---|---|---|
| Unichiller P025 Current | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller 015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 015w-H OLÉ | 54 | OLÉ | I / NFL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 017T | 64 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017T-H | 64 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 017Tw-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020T | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020T-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller 020Tw | 60 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 020Tw-H | 60 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 022-H | 65 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 022w-H | — | Pilot ONE | III / FL | -10–100 | — | — |
| Unichiller 022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller 025T | 74 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025T-H | 74 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025Tw-H | — | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 230V 1~ 50Hz |
| Unichiller 025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller 025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller 025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P007 | 58 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007-H | — | Pilot ONE | III / FL | -20–100 | — | — |
| Unichiller P007-H OLÉ | 58 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P007 OLÉ | 58 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 208-240V 1~/2~ 50/60Hz |
| Unichiller P010 | 57 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P010-H | 57 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010-H OLÉ | 57 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010 OLÉ | 57 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 110-120V 1~ 50/60Hz |
| Unichiller P010w | — | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P010w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 | 59 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 208V 2~ 60Hz |
| Unichiller P012-H | 59 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012-H OLÉ | 59 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012 OLÉ | 59 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H | — | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50/60Hz |
| Unichiller P012w-H OLÉ | — | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 208V 2~ 60Hz |
| Unichiller P012w OLÉ | — | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50/60Hz |
| Unichiller P015 | 63 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015-H | 63 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P015-H OLÉ | 63 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015 OLÉ | 63 | OLÉ | I / NFL | -20–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P015w | 54 | Pilot ONE | I / NFL | -20–40 | Ethernet, USB (Host u. D | 220-240V 1~/2~ 50Hz |
| Unichiller P015w-H | 54 | Pilot ONE | III / FL | -20–100 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P015w-H OLÉ | 54 | OLÉ | III / FL | -20–100 | USB (Device), RS232 Inte | 220-240V 1~/2~ 50Hz |
| Unichiller P022 | 65 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H | 65 | Pilot ONE | I / NFL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022-H OLÉ | 65 | OLÉ | I / NFL | -10–100 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P022 OLÉ | 65 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P022w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P022w-H | 60 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P022w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
| Unichiller P025-H | 64 | Pilot ONE | III / FL | -10–100 | Ethernet, USB (Host u. D | 220-240V 1~ 50Hz |
| Unichiller P025-H OLÉ | 64 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025 OLÉ | 64 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w | 60 | Pilot ONE | I / NFL | -10–40 | Ethernet, USB (Host u. D | 208-230V 1~/2~ 60Hz |
| Unichiller P025w-H OLÉ | 60 | OLÉ | III / FL | -10–100 | USB (Device), RS232 Inte | 220-240V 1~ 50Hz |
| Unichiller P025w OLÉ | 60 | OLÉ | I / NFL | -10–40 | USB (Device), RS232 Inte | 208-230V 1~/2~ 60Hz |
Full specifications
| Noise level | 64 dB(A) |
| Maximum delivery flow rate | 25 l/min (also 2, 5 bar pump pressure) |
| Pump connection | G3/4 AG male |
| Pump speed adjustable | no |
| Pump type | B |
| External sensor connection | Pt100 |
| Temperature range | -10...40 °C |
| Weight | 82 kg |
| Current consumption | 9 A |
| Fuse rating | 16 A |
| Power supply | 220-240V 1~ 50Hz |
| Controller | Pilot ONE |
| Digital interface | Ethernet, USB (Host u. Device), RS232 |
| Ambient temperature limit | 5...40 °C |
| Protection rating | IP20 |
| Safety class | I / NFL |
Description
Construction and series positioning
The Unichiller P025 sits in the Unichiller Bis 25 kW series alongside 015 variants (015, 015-H, 015-H OLÉ, 015 OLÉ). The 'P' in the model name marks it as particularly suitable for applications requiring high pressure drops, per the operation manual. It is a free-standing, indoor-only unit (IP20) with a plastic pump (type B, non-adjustable speed) and G3/4 male pump connections. The refrigerant is R-290 (A3, H220) with a 0.22 kg charge and GWP 0.02. The controller is Pilot ONE with Ethernet, USB host/device, and RS232 interfaces; an external Pt100 sensor can be connected.
Behavior under load and media
Cooling capacity is strongly temperature-dependent: 2.5 kW at 15 °C, 2.0 kW at 0 °C, and 1.2 kW at -10 °C, so sizing must use the capacity at the actual operating point. The pump curve gives 25 l/min max and 6 l/min at 2.0 bar; system pressure drop must be checked against this curve. The unit is intended only for externally closed applications. The plastic pump is not resistant to acetone or polyglycols. For freeze protection below 0 °C, water should be mixed with glysantine or ethylene glycol. Ambient temperature must stay between 5 and 40 °C, and cooling capacity may drop above 20 °C.
Installation, control and operation
Electrical supply is 220–240 V 1~ 50 Hz with 9 A max current and a 16 A fuse; voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and some combinations are not allowed. The unit must not be installed in an ATEX zone. A wall clearance of 50 to 200 cm per side is required for maintenance. Leveling feet must be activated and parking brakes applied before start-up. The Pilot ONE allows configuration of power-failure response (OFF/Standby, ON, or Power Failure Auto) and a Process Safety mode that releases maximum cooling capacity when the overtemperature trigger is reached. Refrigerant circuit work must be performed by approved refrigeration/air-conditioning contractors.
Integration & Operating Notes
Sizing must use the capacity at the actual operating temperature: 2.5 kW at 15 °C, 2.0 kW at 0 °C, and 1.2 kW at -10 °C. Selecting based on the 15 °C figure will undersize the unit for low-temperature duty and risk insufficient cooling.
The standard plastic pump (type B) is not resistant to acetone or polyglycols. If the process fluid contains either, a more resistant pump must be ordered or the fluid changed; otherwise premature pump failure is likely.
For operation near or below 0 °C, water should be mixed with glysantine or ethylene glycol to prevent freezing and damage. Pure water must not be used at low temperatures.
The unit is not explosion-protected and must not be installed or started up inside an ATEX zone. Site classification must be checked before installation; flammable refrigerant R-290 (A3) adds further requirements.
A wall clearance of 50 to 200 cm per side is required for maintenance on free-standing models. The unit must be indoors with illuminance at least 300 lx and at altitude up to 2000 m.
The supply must be 220–240 V 1~ 50 Hz with 9 A max current and a 16 A fuse. Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and some combinations are not allowed; verify site supply quality before connection.
The Pilot ONE allows power-failure response as OFF/Standby, ON, or Power Failure Auto. For exothermic processes, Process Safety mode releases maximum cooling capacity when the overtemperature trigger is reached instead of switching off all poles.
Work on the refrigerant circuit must be carried out by approved refrigeration/air-conditioning system contractors. The R-290 charge is 0.22 kg with GWP 0.02; leak reporting and environmental compliance are simplified but not eliminated.
Cooling water supply must be shut off even for short downtimes such as overnight to prevent water damage and corrosion. Electrical lines directly below a water-cooled unit must be protected against liquid ingress from condensation.
Selection & Integration Q&A
Choose the P025 when the process loop has high pressure drop (the 'P' designation) and requires up to 2.5 kW cooling at 15 °C. The 015 variants offer lower capacity and are not specifically suited to high-pressure-drop applications.
Pump connections are G3/4 male, so hoses and fittings must be G3/4 female. Minimum filling capacity is 3.8 l with 1.7 l expansion volume; the loop must be filled accordingly and expansion space respected.
The base unit does not include freeze-protection additives (glysantine or ethylene glycol) or G3/4 female hoses. Refrigerant circuit work requires approved contractors. Cooling water supply must be shut off even overnight.