Introduces the Unimotive GL 50w-XT unit and its main features
Specp. 2
Lists technical data according to DIN 12876 standard
p. 2table, 19 rows
p. 1table, 26 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
12 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/24
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-45...150 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
I / NFL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
40 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
35 kW
at -20°C
31 kW
at -30°C
23 kW
at -40°C
14 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Engineering Facts
14 facts · every claim linked to a page
Selection
The unit is purpose-built for automotive applications using water-ethylene glycol mixtures down to -45°C, so it should be chosen only for such media and duty.
Confirms the intended heat transfer fluid and low-temperature capability before specifying the unit.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling machine is water-cooled, so a cooling water supply with adequate differential pressure must be provided at the installation site.
Dictates that cooling water infrastructure is mandatory for installation.
Cooling water connections are G3/4 male and require a differential pressure between 1 and 4 bar, which must be verified in the plant piping design.
Ensures the site cooling water loop meets the minimum pressure requirement for proper operation.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit requires a 400 V three-phase 50 Hz supply, so the electrical installation must be sized accordingly.
Determines the electrical supply and cabling needed at the installation site.
Source
“Power supply requirement 400V 3~ 50Hz”
Installation
Three-phase devices below 63 A are delivered with cable but without plug, so a suitable plug must be sourced and fitted on site.
Prevents delays at commissioning by planning the plug and connection in advance.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation
The unit is designed for cooling water intake between 5°C and 20°C, and higher intake temperatures reduce cooling power and may increase flow demand.
Sets the allowable cooling water temperature window and warns of performance loss outside it.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.
Prevents condensation and corrosion damage when cold cooling water is used.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Installation
Cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and treatment to avoid corrosion of the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.
Ensures the site power quality is checked against the permitted tolerance envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Compliance
The equipment is classified as EN55011 Class A Group 1, which has implications for electromagnetic compatibility in the installation environment.
Class A equipment may require EMC measures depending on the installation location.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation
The unit has IP20 protection and must be installed in an ambient temperature between 5°C and 40°C.
Defines the environmental limits and ingress protection for the installation room.
Source
“max. ambient temperature 40 °C”
Installation
The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s, which limits fluid selection at low temperatures.
Prevents pump overload and ensures proper circulation when selecting the fluid.
Source
“max. permissible kin. viscosity 200 mm²/s”
Safety
The unit has a maximum system pressure of 12 bar and pressure equipment category II, which must be respected in the external circuit design.
Sets the pressure limit for connected pipework and components.
Source
“max. System pressure 12 bar”
Operation
The refrigerant is R-744 (A1, H280) with GWP 1, which is relevant for safety classification and environmental compliance.
Informs refrigerant safety handling and environmental reporting requirements.