Unistat 1015w Technical Data

Contents

  1. Overview p. 1
    Product introduction and general description of the Unistat 1015w unit
  2. Spec pp. 1-2
    Technical performance data, dimensions, and operating parameters
  3. Spec p. 2
    Detailed specifications according to DIN 12876 standard
  4. p. 2 table, 24 rows
  5. p. 1 table, 33 rows

Technical data according to DIN 12876

ParameterValue
Global Warming Potential (GWP)7380
Refrigerant quantity 3rd stage1,2 kg
CO2 equivalent 3rd stage8,9 t
Circulation pump:MK pump
max. delivery44 l/min
max. delivery pressure1,5 bar
Pump connectionM30x1,5 male
max. permissible kin. viscosity50 mm²/s
Cooling water connectionG1/2 male
Consumption at water 15°C, flow 0°C560 l/h
min. cooling water differential pressure3 bar
max. cooling water pressure6 bar
min. filling capacity7 l
Filling capacity expansion tank28 l
Overall dimensions WxDxH **950x1205x1650 mm
Net weight639 kg
Power supply requirement400V 3~ 50Hz
max. current27,5 A
Fuse3x32A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S594528

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unistat 1015w (Order-No.: 1064.0002.01)

CharacteristicValue
Operating temperature range-120...100 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power4 kW
Cooling power with DW-Therm at 100°C2,5 kW
Cooling power with DW-Therm at 50°C2,5 kW
Cooling power with DW-Therm at 20°C2,5 kW
Cooling power with Kryothermal S at 0°C2,5 kW
Cooling power with Kryothermal S at -20°C2,5 kW
Cooling power with Kryothermal S at -40°C2,5 kW
Cooling power with Kryothermal S at -60°C2,5 kW
Cooling power with Kryothermal S at -80°C2 kW
Cooling power with Kryothermal S at -100°C2 kW
Cooling power with Kryothermal S at -110°C1 kW
Cooling power with Kryothermal S at -120°C0,3 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-452A (A1, H280)
Global Warming Potential (GWP)2141
Refrigerant quantity3,2 kg
CO2 equivalent6,9 t
Refrigerant 2nd stage (ASHRAE, GHS)R-23 (A1, H280)
Global Warming Potential (GWP)14800
Refrigerant quantity 2nd stage1,7 kg
CO2 equivalent 2nd stage25,2 t
Refrigerant 3rd stage (ASHRAE, GHS)R-14 (A1, H280)

Значения приведены дословно по тексту страницы; строки охлаждающей мощности сведены в одну колонку характеристик с указанием теплоносителя и температуры.

Engineering Facts

13 facts · every claim linked to a page
Installation

The unit requires a 400 V three-phase supply with a 3x32 A fuse and draws up to 27.5 A, so the site electrical infrastructure must be sized accordingly.

Determines the electrical supply, cable and protection device needed at the installation site.

Source
“Power supply requirement 400V 3~ 50Hz max. current 27,5 A Fuse 3x32A”
Installation

Cooling water must be supplied at 3–6 bar differential pressure with a flow of about 560 l/h at 15 °C, and the intake temperature must stay between 5 °C and 20 °C.

Sizing of the cooling water supply and return lines and the facility water system depends on these limits.

Source
“Consumption at water 15°C, flow 0°C 560 l/h min. cooling water differential pressure 3 bar max. cooling water pressure 6 bar”
Installation

If cooling water temperature drops below the dew point, the cooling water pipes inside the unit must be insulated to prevent condensation.

Prevents condensation damage and electrical hazards when using cold cooling water.

Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Cooling capacity is only valid at 20 °C room temperature, 15 °C cooling water inlet and 3 bar differential pressure, and will drop if the cooling water gets warmer.

The published cooling power cannot be expected if site conditions differ from these reference values.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 3 bar differential pressure between cooling water inlet and -outlet.”
Installation

Voltage and frequency tolerances are ±5 % and ±2 % respectively, but a -5 % voltage combined with a +2 % frequency is not allowed.

The supply quality at the site must be checked against this combined tolerance rule before commissioning.

Source
“-5% voltage and +2% frequency -> not allowed!”
Safety

The equipment has a leakage current above 3.5 mA, which affects the choice of residual current protective device.

RCD selection and earthing design must account for high leakage current.

Source
“Attention: leakage current > 3,5mA”
Installation

Three-phase devices drawing less than 63 A are delivered with a cable but without a plug, so a suitable plug must be provided on site.

The installer must plan and supply the correct mains plug for commissioning.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation

The unit is water-cooled and uses R-452A, R-23 and R-14 refrigerants with a combined CO2 equivalent of about 41 t, which matters for leak monitoring and F-gas obligations.

Refrigerant charge and CO2 equivalent determine leak-check intervals and environmental compliance duties.

Source
“CO2 equivalent 6,9 t”
Selection

The unit is classified safety class III / FL according to DIN 12876 and has adjustable overtemperature protection, suitable for both externally closed and externally open applications.

Confirms suitability for open bath applications and the safety category required by the process.

Source
“With adjustable overtemperature protection according to DIN 12876.”
Installation

The pump connection is M30x1.5 male with a Y-shaped bore per DIN 3863, and hoses must use ball socket and sleeve nut per DIN 3863/3870.

Correct matching of tempering hoses and fittings avoids leaks and connection damage.

Source
“Pump connection M30x1,5 male”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 50 mm²/s, which limits fluid choice at low temperatures.

Selecting a fluid with too high viscosity at operating temperature can overload the pump.

Source
“max. permissible kin. viscosity 50 mm²/s”
Installation

The unit needs a minimum filling capacity of 7 l and has a 28 l expansion tank, and weighs 639 kg with dimensions 950x1205x1650 mm.

Determines fluid volume to prepare and the floor space and load capacity required.

Source
“min. filling capacity 7 l Filling capacity expansion tank 28 l”
Compliance

The equipment is EMC class A group 1 per EN55011, so it is intended for industrial environments and may cause interference in residential areas.

Installation location and EMC environment must be industrial to match the classification.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”