Installation
The unit requires a 400 V three-phase supply with a 3x16 A fuse, so the electrical installation must be sized accordingly.
Determines the site power supply, cable and breaker rating needed before installation.
Source
“Power supply requirement 400V 3~ 50Hz max. current 13 A Fuse 3x16A”
Installation
The cooling water circuit must be supplied at 1 bar minimum differential pressure and no more than 6 bar, with G1/2 male connections.
Defines the required cooling water supply pressure and connection size for proper operation.
Source
“min. cooling water differential pressure 1 bar max. cooling water pressure 6 bar”
Operation
The unit is designed for cooling water intake between 5 °C and 20 °C, and lower temperatures require insulating the cooling water pipes.
Specifies the allowable cooling water temperature range and a condensation-prevention measure.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling capacity drops as cooling water temperature rises, and the required cooling water flow rate may increase.
Affects sizing of the cooling water supply and expected performance at the installation site.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Compliance
Voltage and frequency tolerances must be applied together: ±5% voltage with ±2% frequency, but opposite-sign deviations are not allowed.
Prevents connecting the unit to a supply whose combined voltage/frequency deviation exceeds the permitted envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Safety
The equipment has a leakage current greater than 3.5 mA, which must be considered for protective earthing and RCD selection.
Impacts electrical safety design and the choice of residual current protective devices.
Source
“Attention: leakage current > 3,5mA”
Installation
Three-phase devices drawing less than 63 A are delivered with a cable but without a plug, so a suitable plug must be provided on site.
Clarifies what electrical termination is included and what the installer must supply.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
The unit is rated IP20 and must be installed where ambient temperature stays between 5 °C and 40 °C.
Sets environmental limits and protection level for the installation location.
Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Selection
The pump delivers 91 l/min maximum and 1.5 bar maximum pressure, with flow falling as pressure rises.
Allows checking whether the pump curve suits the external circuit's flow and pressure drop.
Source
“max. delivery 91 l/min max. delivery pressure 1,5 bar”
Selection
The refrigerant R-452A has a GWP of 2141 and a charge of 0.97 kg, giving 2.1 t CO2 equivalent.
Relevant for refrigerant regulations, leak monitoring and environmental compliance.
Source
“Global Warming Potential (GWP) 2141 Refrigerant quantity 0,97 kg CO2 equivalent 2,1 t”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and material compatibility to avoid corrosion or fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Operation
The unit has a minimum filling capacity of 3.6 l and an expansion tank capacity of 3.3 l.
Determines the minimum heat transfer fluid volume needed for safe operation.
Source
“min. filling capacity 3,6 l Filling capacity expansion tank 3,3 l”