Product name and model identification for the Unichiller 130Tw
Specp. 2
Technical data table according to DIN 12876 standard
p. 2table, 5 rows
Technical data according to DIN 12876
Parameter
Value
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S467101
Engineering Facts
12 facts · every claim linked to a page
Installation
The chiller requires cooling water inlet temperature between 5°C and 20°C, and pipes must be insulated if water temperature can drop below the condensation point.
Determines cooling water supply design and insulation requirements to avoid condensation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power drops and cooling water flow rate may increase as cooling water temperature rises, so size the water supply accordingly.
Affects selection of cooling water supply capacity and pump sizing.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water must be used.
Guides water quality and material compatibility to prevent corrosion.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Compliance
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Ensures the electrical supply stays within acceptable limits for warranty and safe operation.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
Three-phase devices with current consumption less than 63A are delivered with cable but without plug, so a suitable plug must be provided on site.
Affects electrical installation planning and procurement of the mating plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The unit is classified as Class A, Group 1 for electromagnetic disturbance, which may require EMC measures in sensitive environments.
Informs EMC compliance planning and potential need for filtering or separation.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Selection
The refrigerant R-449A has a GWP of 1397 and a CO2 equivalent of 2.9 t, which matters for environmental compliance and leak reporting.
Needed for refrigerant regulations, leak checks and environmental impact assessment.
Source
“Global Warming Potential (GWP) 1397”
Installation
The minimum cooling water differential pressure is 1 bar and maximum cooling water pressure is 6 bar, so the water supply must stay within these limits.
Prevents insufficient cooling or overpressure damage to the water circuit.
Source
“min. cooling water differential pressure 1 bar”
Operation
The unit is intended for externally closed applications, which defines the hydraulic circuit configuration.
Ensures the chiller is applied in the correct loop type and avoids open-tank operation.
Source
“For externally closed applications.”
Installation
The unit has IP20 protection, so it must be installed in a dry indoor environment protected from water ingress.
Determines suitable installation location and enclosure requirements.
Source
“Degree of Protection IP20”
Operation
Ambient temperature must be between 5°C and 40°C for proper operation.
Affects room ventilation and placement to avoid overheating or condensation.
Source
“min. ambient temperature 5 °C”
Selection
The pump delivers up to 96 l/min at 5.6 bar, which must be checked against the external circuit pressure drop.
Ensures the circulation pump can overcome the external loop resistance.