Unichiller 700Tw Technical Data

Contents

  1. Overview p. 1
    Introduces the Unichiller 700Tw chiller unit and its main features
  2. Spec p. 2
    Lists technical data according to DIN 12876 standard
  3. p. 2 table, 12 rows
  4. p. 1 table, 35 rows

Technical data according to DIN 12876

ParameterValue
min. filling capacity12,7 l
Volume of expansion7 l
Overall dimensions WxDxH **1000x1100x1635 mm
Net weight600 kg
Power supply (3 Phase)400V 3~ 50Hz
max. current (3 Phase)45 A
Fuse (3 phase)3x50A
Pressure equipment categoryI
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S458898

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterUnichiller 700Tw
Order-No.3032.0003.01
Operating temperature range-20...40 °C
temperature set point / display5,7" colour Touchscreen
Internal temperature sensorPt100
Sensor external connectionPt100
Temperature stability at -10°C0,5 K
Interface digitalEthernet, USB (Host u. Device), RS232
Safety classificationI / NFL
Cooling power at 15°C70 kW
Cooling power at 0°C50 kW
Cooling power at -10°C30 kW
Cooling power at -20°C20 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-449A (A1, H280)
Global Warming Potential (GWP)1397
Refrigerant quantity5 kg
CO2 equivalent7,0 t
Circulation pumpD3
max. delivery234 l/min
max. delivery pressure4,9 bar
Delivery at 1,3 bar197 l/min
Delivery at 1,5 bar192 l/min
Delivery at 2,0 bar178 l/min
Delivery at 2,5 bar158 l/min
Delivery at 3,0 bar137 l/min
Delivery at 3,5 bar115 l/min
Delivery at 4,0 bar86 l/min
Delivery at 4,5 bar40 l/min
Pump connectionG1 1/4 male
Cooling water connectionG1 1/4 male
Consumption at water 15°C, flow 15°C3780 l/h
Consumption at water 15°C, flow 0°C2940 l/h
Consumption at water 15°C, flow -10°C1980 l/h
min. cooling water differential pressure1,5 bar
max. cooling water pressure6 bar

Engineering Facts

12 facts · every claim linked to a page
Installation

The chiller requires cooling water inlet between 5°C and 20°C, and if water temperature drops below the condensation point, the cooling water pipes inside the unit must be insulated.

Defines the allowable cooling water supply temperature range and a mandatory insulation measure to prevent condensation inside the unit.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C. When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance

Rated cooling capacity is valid only at 20°C room temperature, 15°C cooling water inlet, and 1.5 bar differential pressure, so actual capacity will differ if site conditions deviate.

Engineers must verify site conditions match these reference values or expect reduced cooling power and higher water flow.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1,5 bar differential pressure between cooling water inlet and -outlet.”
Installation

The minimum cooling water differential pressure is 1.5 bar and maximum cooling water pressure is 6 bar, so the site water supply must fall within these limits.

Ensures the cooling water circuit can deliver adequate flow without exceeding the unit's pressure rating.

Source
“min. cooling water differential pressure 1,5 bar”
Installation

The unit is water-cooled and requires a cooling water flow of 3780 l/h at 15°C water and 15°C flow, which must be available at the site.

Sizing the cooling water supply and drainage is critical; insufficient flow will degrade performance.

Source
“Consumption at water 15°C, flow 15°C 3780 l/h”
Installation

The cooling water circuit materials include copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water quality should be used.

Prevents corrosion or fouling by ensuring the cooling water is chemically compatible with the wetted materials.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Installation

Three-phase devices with current consumption less than 63A are supplied with cable but without a plug, so the installer must provide a suitable plug or hard-wired connection.

Affects electrical installation planning and procurement of the correct plug or connection hardware.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Compliance

Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations such as -5% voltage and +2% frequency are not allowed.

Defines the acceptable power supply quality; out-of-tolerance supply may void warranty or cause malfunction.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Safety

The refrigerant is R-449A with GHS classification A1, H280, and a global warming potential of 1397, so leak detection and ventilation requirements apply.

Informs safety and environmental planning for refrigerant handling and leak response.

Source
“R-449A (A1, H280)”
Installation

The unit has a protection degree of IP20, so it must be installed in a dry indoor environment protected from water ingress.

Prevents installation in wet or dusty locations that could damage electrical components.

Source
“Degree of Protection IP20”
Operation

The ambient temperature must be between 5°C and 40°C for proper operation.

Ensures the chiller is installed in a location with adequate ventilation and temperature control.

Source
“min. ambient temperature 5 °C”
Installation

The unit weighs 600 kg and measures 1000x1100x1635 mm, so floor loading and access clearance must be verified.

Critical for rigging, floor strength, and doorway clearance during installation.

Source
“Overall dimensions WxDxH ** 1000x1100x1635 mm”
Compliance

The equipment is classified as Class A, Group 1 for electromagnetic disturbance to EN55011, so it may cause radio interference in residential areas.

Alerts to potential EMC issues and the need for filtering or separation from sensitive equipment.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”