Selection
The chiller is intended only for externally closed applications, so an open bath or unsealed loop is not acceptable.
Determines whether the unit can be used with the planned external circuit and rules out open-tank operation.
Source
“For externally closed applications.”
Selection
The P models use high-discharge-pressure circulation pumps specifically for systems with high pressure drops.
Confirms the pump curve is suited to restrictive external loops and helps avoid undersized circulation.
Source
“Unichiller „P“ Models: Circulating pumps with a high discharge pressure for applications with high pressure drops.”
Performance
Cooling capacity is rated at 20 °C room temperature and will drop if ambient temperature rises.
Prevents overestimating available cooling in a warm plant room and supports proper derating.
Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation
The three-phase unit draws up to 19 A and requires 3x20 A fusing on a 400 V 3~ 50 Hz supply.
Sets the electrical supply, breaker and cable sizing for installation.
Source
“max. current (3 Phase) 19 A”
Installation
Three-phase devices below 63 A are delivered with cable but without a plug, so site wiring must provide the connection.
Avoids assuming a ready-to-plug unit and plans for site-side termination.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Voltage and frequency tolerances must be met simultaneously; a -5% voltage with +2% frequency is not allowed.
Prevents installing on a supply where combined tolerances exceed the EN60034-1 limits.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The unit is IP20 and must be installed where ambient temperature stays between 5 °C and 40 °C.
Defines the acceptable plant-room environment and protection against ingress.
Source
“max. ambient temperature 40 °C”
Safety
The refrigerant is R-449A with GHS hazard H280, so leak and ventilation precautions apply.
Flags the refrigerant safety class and hazard for risk assessment and room ventilation.
Source
“R-449A (A1, H280)”
Compliance
The equipment is EMC Class A Group 1, which is intended for industrial environments rather than residential use.
Affects installation location and potential interference obligations in non-industrial areas.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Safety
Overtemperature protection is adjustable according to DIN 12876 and must be set for the application.
Requires commissioning personnel to configure the safety limit for the process.
Source
“With adjustable overtemperature protection according to DIN 12876.”
Maintenance
The expansion tank is atmospheric open and has a cover, so level and venting checks are part of operation.
Indicates the tank is not pressurized and needs periodic level inspection.
Source
“atmospheric open expansion tank”
Selection
The unit has a digital level indicator, which supports monitoring of filling and expansion volume.
Useful for selecting the unit where fill-level monitoring is required.
Source
“With digital level indicator.”