Product introduction and general description of the Unimotive 27w unit
Specp. 2
Technical data according to DIN 12876 including performance and dimensions
p. 2table, 25 rows
p. 1table, 26 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
1530 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Net weight
456 kg
Power supply requirement
400V 3~ 50Hz
max. current
57 A
Fuse
3x63A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S549354
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-45...95 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
35 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
25 kW
at -20°C
14,5 kW
at -30°C
6,5 kW
at -40°C
2,6 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
3,6 kg
CO2 equivalent
7,7 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Engineering Facts
12 facts · every claim linked to a page
Selection
The unit is designed for water-ethylene glycol mixtures with corrosion protection down to -45°C, so the heat transfer fluid must be selected accordingly.
Determines whether the unit suits the intended automotive test fluid and prevents corrosion or freezing issues.
Source
“constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C”
Installation
The cooling water intake must be between 5°C and 20°C, and pipes must be insulated if below the condensation point.
Cooling water outside this range reduces cooling power or causes condensation, affecting installation design.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
Cooling water differential pressure must be between 1 bar and 4 bar, with maximum cooling water pressure 6 bar.
Ensures the facility cooling water supply meets the unit's hydraulic requirements.
Source
“min. cooling water differential pressure 1 bar”
Installation
The unit requires a 400V 3~ 50Hz supply with max current 57 A and 3x63A fusing.
Electrical infrastructure and protection devices must be sized accordingly.
Source
“Power supply requirement 400V 3~ 50Hz”
Installation
Three-phase devices with current consumption less than 63A are delivered with cable but without plug.
The installer must provide a suitable plug or hard-wired connection.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
Leakage current exceeds 3.5 mA, which affects residual current device selection and earthing requirements.
Standard 30 mA RCDs may nuisance-trip; appropriate protective measures must be planned.
Source
“Attention: leakage current > 3,5mA”
Operation
Voltage and frequency tolerances are ±5% and ±2% respectively, but certain combinations are not allowed.
Prevents operation outside permissible supply conditions that could damage the unit.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The unit has IP20 protection and must be installed in an environment between 5°C and 40°C ambient temperature.
IP20 offers no water protection, so the installation location must be dry and within ambient limits.
Source
“Degree of Protection IP20”
Selection
Cooling power drops significantly at lower temperatures, from 35 kW at 20°C to 2.6 kW at -40°C.
Process heat loads at low temperatures must be checked against the reduced cooling capacity.
Source
“at -40°C 2,6 kW”
Installation
The pump connection is M38x1.5 male and requires ball socket per DIN 3863 and sleeve nut per DIN 3870.
Correct mating fittings must be procured for leak-free connection.
Source
“Pump connection M38x1,5 male”
Operation
The maximum permissible kinematic viscosity of the heat transfer fluid is 200 mm²/s.
Fluid selection must respect this limit to avoid pump overload.
Source
“max. permissible kin. viscosity 200 mm²/s”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water may be used.
Incompatible water chemistry can cause corrosion or fouling of the cooling circuit.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”