Product introduction and general description of the unit
Specp. 2
Technical data according to DIN 12876
p. 2table, 19 rows
p. 1table, 26 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
200 mm²/s
Cooling water connection
G3/4 male
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,9 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
918x963x1771 mm
Power supply requirement
400V 3~ 50Hz
Pressure equipment category
II
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
1.0/24
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Parameter
Value
Operating temperature range
-45...95 °C
Temperature stability at -10°C
0,05 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
24 kW
Cooling power with Water/ Glysantin 40/60 at 20°C
40 kW
Cooling power with Water/ Glysantin 40/60 at 0°C
35 kW
at -20°C
31 kW
at -30°C
23 kW
at -40°C
14 kW
Refrigeration machine
water-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)
R-744 (A1, H280)
Global Warming Potential (GWP)
1
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Delivery at 1,0 bar
179 l/min
Delivery at 2,0 bar
154 l/min
Engineering Facts
14 facts · every claim linked to a page
Selection
The unit is purpose-built for automotive applications using water-ethylene glycol mixtures with corrosion protection down to -45 °C, so it should be chosen for that fluid and duty rather than general-purpose use.
Confirms the intended fluid and application envelope before specifying the unit.
Source
“The Unimotive model series is specially designed for applications in the automotive industry.”
Selection
The temperature control systems are constructed for operation with water-ethylene glycol mixture including corrosion protection down to -45 °C, which defines the permissible heat transfer fluid.
Prevents selecting an incompatible fluid that could damage the circuit.
Source
“The temperature control systems are constructed for operation with Water-ethylene glycol mixture incl. corrosion protection (for example Glysantin®) down to -45°C.”
Installation
The cooling water intake temperature must be between 5 °C and 20 °C, so the site cooling water supply must be verified before installation.
Cooling water outside this range invalidates the published cooling capacity and may require site modifications.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature falls below the condensation point, the cooling water pipes in the unit must be insulated.
Prevents condensation and corrosion damage on the cooling water circuit.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Published cooling capacities are valid only at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure, so actual capacity will differ at other site conditions.
Allows correct derating of cooling power for the actual installation conditions.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -outlet.”
Performance
Higher cooling water temperature reduces cooling power and may increase the required cooling water flow rate.
Must be accounted for when sizing the cooling water supply and predicting performance.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit uses copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality and treatment to avoid corrosion of mixed materials.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Installation
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and the combination -5% voltage with +2% frequency is not allowed.
Defines the acceptable power supply quality for reliable operation.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
Three-phase devices drawing less than 63 A are supplied with cable but without a plug, so a suitable plug must be provided on site.
Affects electrical installation planning and the scope of supply.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
Three-phase devices drawing more than 63 A are supplied without cable and without plug, requiring full on-site cabling.
Affects electrical installation scope and cost.
Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Compliance
The equipment is classified Class A, Group 1 for electromagnetic disturbance to EN55011, which has implications for the installation environment.
Class A equipment may require EMC measures in residential or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation
Space requirements must be respected, with operating conditions referenced at the manufacturer's website.
Ensures adequate clearance for operation and maintenance.
Source
“** Please respect space requirements. See operating conditions at www.huber-online.com”
Safety
The unit uses R-744 (A1, H280) refrigerant, which is a high-pressure, asphyxiation-hazard substance requiring appropriate handling awareness.
Informs safety planning and refrigerant handling requirements.
Source
“R-744 (A1, H280)”
Operation
The unit has adjustable overtemperature protection according to DIN 12876, which must be set for the application.
Critical safety setting to protect the application and the unit.
Source
“With adjustable overtemperature protection according to DIN 12876.”