Unistat GL 560w Technical Data

Contents

  1. Overview p. 1
    Product introduction and general description of the Unistat GL 560w
  2. Spec pp. 1-2
    Technical specifications and performance data according to DIN 12876
  3. p. 2 table, 13 rows
  4. p. 1 table, 32 rows

Technical data according to DIN 12876

ParameterValue
min. cooling water differential pressure1 bar
max. cooling water differential pressure4 bar
max. cooling water pressure6 bar
max. System pressure6 bar
min. filling capacity8,9 l
Filling capacity expansion tank19,9 l
Overall dimensions WxDxH **918x963x1771 mm
Power supply requirement400V 3~ 50Hz
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:1.0/24

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876

ParameterValue
Operating temperature range-50...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Interface analogoptional
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power24 kW
Cooling power with Thermooil at 200°C41 kW
Cooling power with Thermooil at 100°C41 kW
Cooling power with Thermooil at 20°C41 kW
Cooling power with Ethanol at 0°C37 kW
Cooling power with Ethanol at -20°C30 kW
Cooling power with Ethanol at -40°C15 kW
Cooling power with Ethanol at -50°C8 kW
Refrigeration machinewater-cooled, natural refrigerant
Refrigerant (ASHRAE, GHS)R-744 (A1, H280)
Global Warming Potential (GWP)1
Circulation pump: MK pump max. delivery196 l/min
Circulation pump: MK pump max. delivery pressure2,5 bar
Delivery at 0,5 bar175 l/min
Delivery at 1,0 bar152 l/min
Delivery at 1,5 bar123 l/min
Delivery at 2,0 bar86 l/min
Pump connectionM38x1,5 male
max. permissible kin. viscosity100 mm²/s
Cooling water connectionG3/4 male

Engineering Facts

14 facts · every claim linked to a page
Installation

The unit requires a 400 V three-phase 50 Hz supply, so the electrical installation must be planned for three-phase power.

Determines the site power infrastructure and whether a three-phase connection is available.

Source
“Power supply requirement 400V 3~ 50Hz”
Installation

The cooling water circuit must be supplied at 1–4 bar differential pressure and no more than 6 bar, so the building water system must be checked against these limits.

Incorrect cooling water pressure can prevent rated cooling performance or damage the unit.

Source
“min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Installation

The unit is designed for cooling water intake between 5 °C and 20 °C, and pipes must be insulated if water temperature can fall below the condensation point.

Cooling water temperature outside this range affects cooling capacity and may cause condensation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance

Rated cooling power is valid only at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure, so site conditions must match these for the published data.

Prevents overestimating cooling capacity when site conditions differ from the rating basis.

Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Installation

The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.

Guides water quality and material compatibility to avoid corrosion or fouling.

Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Installation

The pump connection is M38x1.5 male and the cooling water connection is G3/4 male, so matching hoses and fittings must be ordered.

Ensures correct connection hardware is available before installation.

Source
“Pump connection M38x1,5 male”
Installation

The cooling water connection is G3/4 male, so the site must provide a matching G3/4 connection.

Avoids delays and leaks from mismatched cooling water fittings.

Source
“Cooling water connection G3/4 male”
Operation

The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s, so fluid selection must respect this limit.

Too-viscous fluid can overload the pump and reduce circulation performance.

Source
“max. permissible kin. viscosity 100 mm²/s”
Installation

The unit has IP20 protection and must be installed in an environment between 5 °C and 40 °C ambient temperature.

IP20 is not water-protected, so the installation location must be dry and within the ambient temperature range.

Source
“Degree of Protection IP20”
Installation

The ambient temperature must be between 5 °C and 40 °C, which constrains the installation room conditions.

Operation outside this range may affect performance and reliability.

Source
“min. ambient temperature 5 °C max. ambient temperature 40 °C”
Installation

The unit uses refrigerant R-744 with GWP 1, which is relevant for environmental compliance and refrigerant handling.

Low-GWP refrigerant simplifies environmental compliance compared with high-GWP alternatives.

Source
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280)”
Installation

The unit is water-cooled with a natural refrigerant, so a cooling water supply is mandatory for operation.

Confirms that no air-cooled option exists and cooling water must be available.

Source
“Refrigeration machine water-cooled, natural refrigerant”
Compliance

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.

Ensures the site power quality meets the unit's input requirements.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation

Three-phase devices below 63 A are delivered with cable but without plug, so a suitable plug must be provided on site.

Prevents installation delays because the plug is not included.

Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”