The unit requires a 400 V three-phase 50 Hz supply, so the site must provide a suitable three-phase power connection.
Determines electrical infrastructure and whether a plug or hard wiring is needed.
Source
“Power supply requirement 400V 3~ 50Hz”
| Parameter | Value |
|---|---|
| Delivery at 3,0 bar | 124 l/min |
| Delivery at 4,0 bar | 87 l/min |
| Delivery at 5,0 bar | 42 l/min |
| Pump connection | M38x1,5 male |
| max. permissible kin. viscosity | 100 mm²/s |
| Cooling water connection | G3/4 male |
| Consumption at water 15°C, flow 0°C | 2100 l/h |
| min. cooling water differential pressure | 1 bar |
| max. cooling water differential pressure | 4 bar |
| max. cooling water pressure | 6 bar |
| max. System pressure | 6 bar |
| min. filling capacity | 8,9 l |
| Filling capacity expansion tank | 19,9 l |
| Overall dimensions WxDxH ** | 730x804x1738 mm |
| Net weight | 600 kg |
| Power supply requirement | 400V 3~ 50Hz |
| Pressure equipment category | I |
| Degree of Protection | IP20 |
| min. ambient temperature | 5 °C |
| max. ambient temperature | 40 °C |
| from Serial-No.: | 1.0/24 |
** Please respect space requirements. See operating conditions at www.huber-online.com
| Parameter | Value |
|---|---|
| Operating temperature range | -50...200 °C |
| Temperature stability at -10°C | 0,01 K |
| temperature set point / display | 5,7" colour Touchscreen |
| Resolution of display | 0,01 K |
| Internal temperature sensor | Pt100 |
| Sensor external connection | Pt100 |
| Interface digital | Ethernet, USB (Host u. Device), RS232 |
| digital input | ECS ONE |
| digital output | POKO ONE |
| Interface analog | optional |
| Alarm message | optic, acoustic, relay |
| Safety classification | III / FL |
| Heating power | 12 kW |
| Cooling power with Thermooil at 200°C | 23 kW |
| Cooling power with Thermooil at 100°C | 23 kW |
| Cooling power with Thermooil at 20°C | 23 kW |
| Cooling power with Ethanol at 0°C | 20 kW |
| Cooling power with Ethanol at -20°C | 12,5 kW |
| Cooling power with Ethanol at -40°C | 5,5 kW |
| Cooling power with Ethanol at -50°C | 2,2 kW |
| Refrigeration machine | water-cooled, natural refrigerant |
| Refrigerant (ASHRAE, GHS) | R-744 (A1, H280) |
| Global Warming Potential (GWP) | 1 |
| Refrigerant quantity | 3,3 kg |
| CO2 equivalent | 0,0 t |
| Circulation pump: MK pump max. delivery | 201 l/min |
| Circulation pump: MK pump max. delivery pressure | 5,3 bar |
| Circulation pump: MK pump Delivery at 1,0 bar | 179 l/min |
| Circulation pump: MK pump Delivery at 2,0 bar | 154 l/min |
Значения приведены дословно; строки охлаждения сведены по параметру и среде (Thermooil/Ethanol) с указанием температуры.
The unit requires a 400 V three-phase 50 Hz supply, so the site must provide a suitable three-phase power connection.
Determines electrical infrastructure and whether a plug or hard wiring is needed.
“Power supply requirement 400V 3~ 50Hz”
Three-phase devices below 63 A are supplied with cable but without a plug, so the installer must provide a suitable connection.
Affects electrical installation planning and procurement of a plug or isolator.
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Cooling water must be supplied at 5–20 °C inlet temperature with 1–4 bar differential pressure and no more than 6 bar pressure.
Cooling water conditions directly affect cooling performance and safe operation.
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
If cooling water temperature can fall below the dew point, the cooling water pipes inside the unit must be insulated.
Prevents condensation and possible damage or electrical risk.
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Cooling capacity is rated at 20 °C room temperature, 15 °C cooling water inlet and 1 bar differential pressure, so actual capacity may differ on site.
Needed to correctly compare quoted cooling capacity with real site conditions.
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Higher cooling water temperature reduces cooling power and may require a higher cooling water flow rate.
Affects sizing of the cooling water supply and expected process performance.
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Prevents corrosion or damage from unsuitable water chemistry.
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Voltage and frequency tolerances are ±5% and ±2% respectively, but they must not be combined in opposite directions.
Defines acceptable supply quality for reliable operation and warranty.
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
The equipment is EMC class A group 1, which may require special precautions in residential or sensitive environments.
Affects installation location and possible interference with nearby equipment.
“Classification (disturbance) to EN55011: Class A, Group 1”
The unit is IP20 and must be installed where ambient temperature stays between 5 °C and 40 °C.
Determines environmental limits and protection against dust and water.
“Degree of Protection IP20”
The unit weighs 600 kg and measures 730×804×1738 mm, so floor loading and access routes must be checked.
Needed for transport, rigging and installation space planning.
“Overall dimensions WxDxH ** 730x804x1738 mm”
The pump connections are M38×1.5 male with bore shape Y (60°) per DIN 3863, requiring matching ball socket and sleeve nut fittings.
Ensures correct hose or pipe fittings are ordered and leak-free connections are made.
“Pump connection M38x1,5 male”
The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s.
Limits fluid selection and ensures pump performance and protection.
“max. permissible kin. viscosity 100 mm²/s”
The unit uses R-744 (CO2) refrigerant with GWP 1 and 3.3 kg charge, which has low global warming impact but requires high-pressure awareness.
Relevant for refrigerant handling, safety classification and environmental compliance.
“Refrigerant (ASHRAE, GHS) R-744 (A1, H280)”