Product introduction and general description of the Unistat P527w unit
Specp. 2
Technical data according to DIN 12876 standard
p. 2table, 25 rows
p. 1table, 30 rows
Technical data according to DIN 12876
Parameter
Value
Delivery at 2,0 bar
154 l/min
Delivery at 3,0 bar
124 l/min
Delivery at 4,0 bar
87 l/min
Delivery at 5,0 bar
42 l/min
Pump connection
M38x1,5 male
max. permissible kin. viscosity
100 mm²/s
Cooling water connection
G3/4 male
Consumption at water 15°C, flow 0°C
880 l/h
min. cooling water differential pressure
1 bar
max. cooling water differential pressure
4 bar
max. cooling water pressure
6 bar
max. System pressure
6 bar
min. filling capacity
8,2 l
Filling capacity expansion tank
19,9 l
Overall dimensions WxDxH **
730x804x1738 mm
Net weight
444 kg
sound pressure level +/- 4 dB(A)
57 dB(A)
Power supply requirement
400V 3~ 50Hz
max. current
31,62 A
Fuse
3x32A
Pressure equipment category
I
Degree of Protection
IP20
min. ambient temperature
5 °C
max. ambient temperature
40 °C
from Serial-No.:
S602229
** Please respect space requirements. See operating conditions at www.huber-online.com
Technical data according to DIN 12876
Characteristic
Value
Operating temperature range
-55...250 °C
Temperature stability at -10°C
0,01 K
temperature set point / display
5,7" colour Touchscreen
Resolution of display
0,01 K
Internal temperature sensor
Pt100
Sensor external connection
Pt100
Interface digital
Ethernet, USB (Host u. Device), RS232
digital input
ECS ONE
digital output
POKO ONE
Interface analog
optional
Alarm message
optic, acoustic, relay
Safety classification
III / FL
Heating power
12 kW
Cooling power with Thermooil at 250°C
12 kW
Cooling power with Thermooil at 200°C
12 kW
Cooling power with Thermooil at 100°C
12 kW
Cooling power with Thermooil at 20°C
12 kW
Cooling power with Ethanol at 0°C
12 kW
Cooling power with Ethanol at -20°C
6 kW
Cooling power with Ethanol at -40°C
2 kW
Cooling power with Ethanol at -50°C
1 kW
Refrigeration machine
water-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)
R-452A (A1, H280)
Global Warming Potential (GWP)
2141
Refrigerant quantity
2,9 kg
CO2 equivalent
6,2 t
Circulation pump:
MK pump
max. delivery
201 l/min
max. delivery pressure
5,3 bar
Delivery at 1,0 bar
179 l/min
Order-No.: 5001.0002.01; Unistat P527w
Engineering Facts
12 facts · every claim linked to a page
Installation
The unit requires a 400 V three-phase supply with a 3x32 A fuse, so the electrical installation must be sized accordingly.
Determines the site power supply, cable cross-section and protection device needed before installation.
Source
“Power supply requirement 400V 3~ 50Hz max. current 31,62 A Fuse 3x32A”
Installation
The cooling water circuit must be supplied at 1–4 bar differential pressure and no more than 6 bar, with 880 l/h consumption at 15 °C.
Sizes the cooling water supply, return lines and pressure regulation needed for reliable operation.
Source
“Consumption at water 15°C, flow 0°C 880 l/h min. cooling water differential pressure 1 bar max. cooling water differential pressure 4 bar max. cooling water pressure 6 bar”
Operation
Cooling water inlet must stay between 5 °C and 20 °C, and pipes must be insulated if the water can drop below the dew point.
Prevents condensation, corrosion and loss of cooling performance in the water circuit.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C. When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling capacity drops sharply at low temperatures with ethanol, from 12 kW at 0 °C to 1 kW at -50 °C.
Allows the engineer to check whether the required heat load can be removed at the lowest process temperature.
Source
“at 0°C 12 kW at -20°C 6 kW at -40°C 2 kW at -50°C 1 kW”
Selection
The pump delivers 201 l/min maximum and 42 l/min at 5.0 bar, so high-pressure-drop loops must be checked against the pump curve.
Confirms whether the circulation pump can overcome the pressure drop of the external circuit.
Source
“max. delivery 201 l/min max. delivery pressure 5,3 bar Delivery at 5,0 bar 42 l/min”
Safety
The refrigerant R-452A is classified A1 with GHS H280, and the charge is 2.9 kg corresponding to 6.2 t CO2 equivalent.
Affects refrigerant handling, leak detection and F-gas reporting obligations.
Source
“R-452A (A1, H280) Global Warming Potential (GWP) 2141 Refrigerant quantity 2,9 kg CO2 equivalent 6,2 t”
Compliance
Voltage tolerance is ±5% only with a simultaneous frequency tolerance of ±2%, and opposite-sign deviations are not allowed.
Defines the acceptable power quality at the installation site and protects the compressor and electronics.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2% Example -5% voltage and +2% frequency -> not allowed!”
Installation
Three-phase devices below 63 A are delivered with cable but without a plug, so the customer must provide the plug and connection.
Clarifies the scope of supply and what the electrical contractor must provide on site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Operation
The unit is rated IP20 and must be operated between 5 °C and 40 °C ambient temperature.
Restricts installation location and prevents operation in wet or hot environments.
Source
“Degree of Protection IP20 min. ambient temperature 5 °C max. ambient temperature 40 °C”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible water quality may be used.
Guides water treatment and avoids corrosion or fouling of the heat exchanger.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM. Please use suitable cooling water.”
Selection
The maximum permissible kinematic viscosity of the heat transfer fluid is 100 mm²/s.
Limits the choice of heat transfer fluid, especially at low temperatures where viscosity rises.
Source
“max. permissible kin. viscosity 100 mm²/s”
Installation
The unit needs at least 8.2 l filling capacity and has a 19.9 l expansion tank.
Determines the minimum fluid charge and the expansion volume available for the external loop.
Source
“min. filling capacity 8,2 l Filling capacity expansion tank 19,9 l”