Unistat P645w Technical Data

Contents

  1. Overview p. 1
    Product introduction and general description of the Unistat P645w unit
  2. Spec pp. 1-2
    Technical performance data, dimensions, and operating parameters
  3. Spec p. 2
    Compliance specifications according to DIN 12876 standard
  4. p. 2 table, 19 rows
  5. p. 1 table, 29 rows

Technical data according to DIN 12876

ParameterValue
Delivery at 5,0 bar50 l/min
Pump connectionflange DN32 PN10/40 EN1092-1
max. permissible kin. viscosity50 mm²/s
Cooling water connectionflange DN32 PN10/40 EN1092-1
Consumption at water 15°C, flow 0°C6000 l/h
min. cooling water differential pressure3 bar
max. cooling water pressure6 bar
min. filling capacity30 l
Filling capacity expansion tank30 l
Overall dimensions WxDxH **2210x1300x2160 mm
Net weight2150 kg
Power supply requirement460V 3~ 60Hz
max. current70 A
Fuse3x80A
Pressure equipment categoryII
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.:S611392

** Please respect space requirements. See operating conditions at www.huber-online.com

Technical data according to DIN 12876 — Unistat P645w (Order-No.: 1063.0006.01)

CharacteristicValue
Operating temperature range-60...200 °C
Temperature stability at -10°C0,01 K
temperature set point / display5,7" colour Touchscreen
Resolution of display0,01 K
Internal temperature sensorPt100
Sensor external connectionPt100
Interface digitalEthernet, USB (Host u. Device), RS232
digital inputECS ONE
digital outputPOKO ONE
Alarm messageoptic, acoustic, relay
Safety classificationIII / FL
Heating power36 kW
Cooling power with Thermooil at 200°C45 kW
Cooling power with Thermooil at 100°C45 kW
Cooling power with Ethanol at 0°C45 kW
Cooling power with Ethanol at -20°C42 kW
Cooling power with Ethanol at -40°C21 kW
Cooling power with Ethanol at -60°C6 kW
Refrigeration machinewater-cooled, CFC- and HCFC-free
Refrigerant (ASHRAE, GHS)R-507 (A1, H280)
Global Warming Potential (GWP)3985
Refrigerant quantity24 kg
CO2 equivalent95,6 t
Circulation pump: MK pump max. delivery343 l/min
max. delivery pressure5,5 bar
Delivery at 1,0 bar300 l/min
Delivery at 2,0 bar250 l/min
Delivery at 3,0 bar191 l/min
Delivery at 4,0 bar135 l/min

Таблица приведена как напечатана (характеристика — значение); строки 'Cooling power with Thermooil/Ethanol' объединяют подзаголовок и температуру в одну характеристику.

Engineering Facts

12 facts · every claim linked to a page
Selection

The unit is water-cooled and requires a cooling water supply with a minimum differential pressure of 3 bar and maximum pressure of 6 bar.

Cooling water infrastructure must be verified before selection to ensure adequate pressure and flow.

Source
“min. cooling water differential pressure 3 bar”
Installation

The cooling water intake temperature must be between 5°C and 20°C, and pipes must be insulated if condensation occurs.

Ensures proper cooling performance and prevents condensation damage during installation.

Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation

The unit requires a 460V 3~ 60Hz power supply with a maximum current of 70 A and 3x80A fuses.

Electrical infrastructure must be sized accordingly before installation.

Source
“Power supply requirement 460V 3~ 60Hz”
Safety

Leakage current exceeds 3.5 mA, so external branch circuit protection according to UL 489 is required.

Mandatory for electrical safety compliance and proper breaker selection.

Source
“Attention: leakage current > 3,5mA”
Installation

Three-phase devices with current consumption greater than 63A are delivered without cable and without plug.

Installer must plan for on-site power cabling and connection.

Source
“Three-phase devices with current consumption greater than 63A --> without cable, without plug”
Operation

Cooling power drops as cooling water temperature rises, and cooling water flow rate may need to increase.

Operators must account for reduced performance at higher cooling water temperatures.

Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation

Pump connections use flange DN32 PN10/40 per EN1092-1, and pipework must use ball socket per DIN 3863 and sleeve nut per DIN 3870.

Correct mating hardware must be procured for leak-free installation.

Source
“Pump connections: Bore shape Y (60°) according to DIN 3863, pipework/flexible tempering hoses: Ball socket according to DIN 3863, sleeve nut according to DIN 3870.”
Selection

The refrigerant R-507 has a GWP of 3985 and a CO2 equivalent of 95.6 t, which matters for environmental compliance and reporting.

Refrigerant charge and GWP affect regulatory compliance and environmental reporting.

Source
“Global Warming Potential (GWP) 3985”
Operation

The unit operates within an ambient temperature range of 5°C to 40°C.

Site ambient conditions must be within this range for reliable operation.

Source
“min. ambient temperature 5 °C”
Installation

The unit has a protection degree of IP20, so it must be installed in a dry, protected environment.

Prevents ingress of water and dust that could damage electronics.

Source
“Degree of Protection IP20”
Selection

The maximum permissible kinematic viscosity of the heat transfer fluid is 50 mm²/s.

Ensures proper pump performance and avoids excessive pressure drop.

Source
“max. permissible kin. viscosity 50 mm²/s”
Installation

Voltage tolerance is ±5% with simultaneous frequency tolerance of ±2%, but combinations like -5% voltage and +2% frequency are not allowed.

Prevents improper power supply combinations that could damage the unit.

Source
“-5% voltage and +2% frequency -> not allowed!”