Installation
The chiller requires cooling water with a differential pressure between 3 and 6 bar, so the facility water supply must be sized accordingly.
Insufficient or excessive cooling water pressure will prevent proper operation or damage the unit.
Source
“min. cooling water differential pressure
3 bar
max. cooling water pressure
6 bar”
Installation
The unit is water-cooled and must be fed with cooling water between 5°C and 20°C; below the dew point the pipes must be insulated.
Cooling water temperature outside this range reduces cooling capacity or causes condensation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Safety
The refrigerant is R-290 (propane, A3, H220), a flammable natural refrigerant, so ignition sources and ventilation must be considered.
Flammable refrigerant classification affects room ventilation and electrical installation requirements.
Source
“R-290 (A3, H220)”
Operation
The plastic pump is not resistant to acetone or polyglycols, so these media must not be used without a more resistant pump option.
Using incompatible media will damage the pump and void reliable operation.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation
For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.
Prevents freezing and damage in the cooling circuit when operating below ambient freezing conditions.
Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation
The electrical supply must be 208–240 V single or two-phase at 50/60 Hz with a maximum current of 12 A and a 16 A fuse.
Determines the site power connection, cable sizing and breaker rating.
Source
“208-240V 1~/2~ 50/60Hz
max. current
12 A
Fuse
16 A”
Cumplimiento
Voltage and frequency tolerances are ±5% and ±2% respectively, but the combination of -5% voltage with +2% frequency is not allowed.
Ensures the supply quality at the installation site meets the unit's permissible operating envelope.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The unit has IP20 protection, so it must be installed in a dry indoor location protected from water ingress.
IP20 is not water-protected; installation environment must avoid splashing or condensation.
Source
“Degree of Protection
IP20”
Operation
Ambient temperature must stay between 5°C and 40°C for reliable operation.
Operating outside this range affects cooling performance and may trip protection.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Performance
Cooling power drops from 1 kW at +15°C to 0.35 kW at -20°C, so capacity must be selected for the lowest operating temperature.
Sizing on nominal capacity alone will underperform at low temperatures.
Source
“at 15°C
1 kW
at 0°C
0,8 kW
at -10°C
0,55 kW
at -20°C
0,35 kW”
Installation
The pump connections are M16x1 male and the cooling water connections are G1/2 male, so matching fittings are required.
Ensures correct hose adapters and fittings are ordered before installation.
Source
“Pump connection
M16x1 male
Cooling water connection
G1/2 male”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Incompatible water chemistry can corrode or foul the wetted materials.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”