Induztr
Resumen técnico Visor de documentos Modelos relacionados

Minichiller 600 OLÉ

Contenido

  1. Overview p. 1
    Product name and cover page of the datasheet
  2. Spec p. 2
    Technical data according to DIN 12876
  3. p. 2 table, 6 rows

Technical data according to DIN 12876

ParameterValue
max. Fuse16A
Pressure equipment categoryArt. 4.3 PED
Degree of ProtectionIP20
min. ambient temperature5 °C
max. ambient temperature40 °C
from Serial-No.S542486

Engineering Facts

13 facts · every claim linked to a page
Selection

The chiller uses flammable refrigerant R-290 (A3, H220), so the installation must account for refrigerant safety classification and ventilation.

A3 flammable refrigerant affects site safety assessment, ventilation, and ignition-source control during selection and installation.

Source
“Refrigerant (ASHRAE, GHS) R-290 (A3, H220)”
Installation

The unit requires a 110-120 V single-phase 60 Hz supply with 8.5 A max current and a minimum 10 A fuse.

Electrical supply and protection must be sized correctly before installation.

Source
“Power supply requirement 110-120V 1~ 60Hz”
Installation

The pump connection is M16x1 male, and hose connector NW12 plus sleeve nuts M16x1 are included, so mating hoses must match this thread.

Ensures correct hose/adaptor selection and leak-free connection at commissioning.

Source
“Pump connection M16x1 male”
Operation

The permissible return-line temperature is 80 °C, which limits the heat load returned to the chiller.

Exceeding return temperature can damage the unit or trip alarms; process heat loads must be checked.

Source
“Permissible temperature in return line 80 °C”
Operation

Cooling capacity is rated at 20 °C room temperature and may drop if ambient temperature rises.

Selection must derate cooling capacity for actual ambient conditions to avoid insufficient cooling.

Source
“Output data valid for: Room temperature 20°C. If the ambient temperature rises, the cooling capacity may drop.”
Installation

The unit is rated IP20 and must be installed in an environment between 5 °C and 40 °C ambient temperature.

IP20 offers no water protection and limited finger protection, so location and ambient conditions must be controlled.

Source
“Degree of Protection IP20”
Safety

The plastic pump is not resistant to acetone and polyglycols, so these fluids must be avoided or a more resistant pump specified.

Fluid compatibility determines pump life and leak risk; wrong fluid choice causes premature failure.

Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Operation

For freeze protection, water should be mixed with glysantine or ethylene glycol rather than relying on pure water.

Prevents freezing and damage in the cooling circuit when operating near or below 0 °C.

Source
“It is recommended that water is mixed with either glysantine or ethylene glycol for freeze protection.”
Installation

Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.

Site power quality must be verified; out-of-tolerance supply can cause malfunction or damage.

Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Cumplimiento

The equipment is EMC Class A Group 1, which is intended for industrial environments and may cause interference in residential areas.

Class A equipment may require additional EMC measures if installed near sensitive or residential equipment.

Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Installation

Single/two-phase devices are supplied with a power cable and country-specific plug, which must be specified at ordering.

Prevents delay and rework at installation due to missing or wrong plug type.

Source
“Single / two-phase devices (100V to 240V) --> with power cable and country-specific plug (please specify when ordering)”
Performance

Whisper mode reduces sound pressure to 51 dB(A) but also reduces pump delivery to 14 l/min and 0.2 bar.

Noise-sensitive installations may need whisper mode, but flow and pressure performance must be rechecked.

Source
“Reduced sound pressure level: 51 dB(A): +/- 4 dB(A)”
Maintenance

The minimum filling capacity is 2.8 l and the expansion tank is 2.2 l, which sets the required heat-transfer fluid volume.

Ensures correct fluid charge and expansion volume for safe operation and maintenance.

Source
“min. filling capacity 2,8 l”