The chiller is water-cooled and requires a cooling water supply with at least 1 bar differential pressure and no more than 6 bar.
Cooling water pressure must be verified at the installation site to ensure adequate flow and avoid overpressure damage.
Source
“min. cooling water differential pressure 1 bar”
Installation
Cooling water inlet temperature must be kept between 5°C and 20°C; below the condensation point the cooling water pipes inside the unit must be insulated.
Defines the permissible cooling water supply conditions and required insulation to prevent condensation.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Performance
Cooling power ratings are valid only at 20°C room temperature, 15°C cooling water inlet and 1 bar differential pressure; higher cooling water temperature reduces cooling power.
Selection must account for actual site conditions because published cooling capacity is conditional.
Source
“Output data valid for: Room temperature 20°C, cooling water inlet 15°C and 1 bar differential pressure between cooling water inlet and -”
Operation
The plastic pump is not resistant to acetone and polyglycols, so water with glycine or ethylene glycol is recommended for freeze protection.
Prevents selection of incompatible heat transfer fluids that would damage the pump.
Source
“The plastic pump is not resistant against acetone and polyglycols (depending on the manufacturer).”
Installation
The unit requires a 208-230V single or two-phase 60Hz supply with a 16A fuse and maximum current of 12.5A.
Electrical supply and protection must be sized accordingly before installation.
Source
“Power supply requirement 208-230V 1~/2~ 60Hz”
Installation
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations such as -5% voltage with +2% frequency are not allowed.
Site power quality must be checked to avoid operating outside the permitted supply envelope.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
Three-phase devices below 63A are delivered with cable but without plug, so a suitable plug must be provided on site.
Affects electrical installation planning and procurement of the mating plug.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280, and the unit contains 0.43 kg corresponding to 0.6 t CO2 equivalent.
Refrigerant safety classification and charge affect handling, labeling and environmental compliance.
Source
“R-449A (A1, H280)”
Operation
The minimum filling capacity is 3.8 l and the expansion tank volume is 1.7 l, which must be considered when charging the loop.
Ensures the external circuit is filled to the minimum required volume for safe operation.
Source
“min. filling capacity 3,8 l”
Installation
The unit has IP20 protection and must be operated within 5°C to 40°C ambient temperature.
Restricts installation location to dry indoor environments within the ambient temperature range.
Source
“Degree of Protection IP20”
Cumplimiento
The equipment is classified Class A, Group 1 for electromagnetic disturbance to EN55011.
Class A equipment may require additional EMC measures in residential or sensitive environments.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Maintenance
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only suitable cooling water may be used.
Cooling water quality must be compatible with these materials to avoid corrosion and fouling.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”