Selection
The chiller's cooling capacity drops as ambient temperature rises, so selection must account for actual room conditions.
Cooling capacity ratings are valid only at 20°C room temperature; higher ambient reduces available capacity.
Source
“If the ambient temperature rises, the cooling capacity may drop.”
Installation
Three-phase units under 63A are supplied with cable but no plug, so the installer must provide a suitable plug.
Determines what electrical termination hardware must be procured and installed on site.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
External branch circuit protection per UL 489 is mandatory and must be specified from the electrical schematics.
The unit does not include branch protection; the site electrical design must provide it.
Source
“External branch circuit protection according to UL 489 required.”
Installation
Voltage and frequency tolerances are interdependent: -5% voltage with +2% frequency is not allowed.
Supply quality must be checked against the combined tolerance rule, not voltage alone.
Source
“-5% voltage and +2% frequency -> not allowed!”
Installation
The unit requires minimum clearance and specific operating conditions that must be respected during siting.
Air-cooled refrigeration needs adequate airflow clearance; ignoring this degrades capacity and reliability.
Source
“Please respect space requirements. See operating conditions at www.huber-online.com”
Safety
The refrigerant R-449A is classified A1 with GHS hazard H280, so refrigerant handling and ventilation precautions apply.
A1 classification and H280 (pressurized gas) affect service procedures and room ventilation requirements.
Source
“R-449A (A1, H280)”
Conformité
The equipment emits Class A, Group 1 disturbances per EN55011, which constrains its use in residential environments.
Class A equipment is intended for industrial environments and may cause interference in residential areas.
Source
“Classification (disturbance) to EN55011: Class A, Group 1”
Operation
The unit is rated IP20, so it must be installed in a dry, protected location away from water ingress.
IP20 offers no water protection; installation location must avoid splashes and condensation.
Source
“Degree of Protection
IP20”
Operation
The ambient operating window is 5°C to 40°C, limiting where and when the chiller can run reliably.
Operation outside this range risks poor performance or equipment damage.
Source
“min. ambient temperature
5 °C
max. ambient temperature
40 °C”
Selection
The pump delivers 210 l/min at zero head but only 31 l/min at 4.5 bar, so system pressure drop must be matched to the pump curve.
External circuit pressure drop determines actual flow; oversizing the loop starves flow.
Source
“max. delivery
210 l/min
max. delivery pressure
4,7 bar”
Installation
The pump connection is G1 1/4 male, so mating hoses and fittings must match this thread.
Thread mismatch prevents connection; correct couplings must be ordered.
Source
“Pump connection
G1 1/4 male”
Operation
The expansion vessel volume is 39 l with a minimum filling capacity of 14 l, defining the minimum system fill.
Underfilling below 14 l or exceeding expansion volume causes poor temperature control or overflow.
Source
“min. filling capacity
14 l
Volume of expansion
39 l”
Selection
Temperature stability is 0.5 K at -10°C, which sets the achievable control accuracy for the process.
Processes requiring tighter than ±0.5 K need a different model or control upgrade.
Source
“Temperature stability at -10°C
0,5 K”
Operation
The unit is designed for externally closed applications, so an open external loop is not permitted.
Using an open loop risks evaporation, contamination, and loss of temperature control.
Source
“For externally closed applications.”