Installation
The chiller requires a minimum cooling water differential pressure of 1.5 bar to operate correctly.
Ensures the cooling water supply system can provide adequate flow and pressure for heat rejection.
Source
“min. cooling water differential pressure 1,5 bar”
Installation
The maximum allowable cooling water pressure is 6 bar, so the supply must be regulated or protected against overpressure.
Prevents damage to the cooling water circuit components from excessive pressure.
Source
“max. cooling water pressure 6 bar”
Operation
The unit is designed for cooling water inlet temperatures between 5°C and 20°C; operation outside this range may require additional measures.
Defines the acceptable cooling water supply conditions for warranty and performance.
Source
“This temperature control unit is designed to operate with cooling water intake temperature between 5°C and 20°C.”
Installation
If cooling water temperature falls below the condensation point, the cooling water pipes inside the unit must be insulated.
Prevents condensation and corrosion inside the chiller when using cold cooling water.
Source
“When cooling water temperatures fall below the condensation point, it is essential to insulate the cooling water pipes in the unit.”
Performance
Cooling capacity decreases as cooling water temperature rises, and the required cooling water flow rate may increase.
Helps size the cooling water supply and predict performance under varying site conditions.
Source
“As the cooling water temperature increases, drop in the cooling power should be expected, and also an increased cooling water flow rate possible.”
Installation
The cooling water circuit contains copper, stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM, so only compatible cooling water may be used.
Guides water quality requirements to avoid corrosion or damage to wetted materials.
Source
“Materiels used in the cooling water circuit include; copper, Stainless steel 1.4401, MS, PA, PPE, PTFE and EPDM.”
Conformité
Voltage tolerance is ±5% only with simultaneous frequency tolerance of ±2%, and certain combinations are not allowed.
Ensures the electrical supply stays within safe operating limits for the compressor and electronics.
Source
“Voltage + / - 5% with a simultaneous frequency tolerance of + / - 2%”
Installation
Three-phase devices with current consumption less than 63A are supplied with a cable but without a plug.
Requires the installer to provide a suitable plug and connection to the site supply.
Source
“Three-phase devices with current consumption less than 63A --> with cable, without plug”
Installation
The unit requires a minimum ambient temperature of 5°C and a maximum of 40°C for proper operation.
Ensures the installation location maintains acceptable ambient conditions for reliable operation.
Source
“min. ambient temperature 5 °C”
Safety
The refrigerant R-449A has a GHS classification of A1, H280, indicating it is a pressurized gas that must be handled accordingly.
Informs about refrigerant safety classification and handling requirements during installation and maintenance.
Source
“R-449A (A1, H280)”
Selection
The chiller has a CO2 equivalent of 8.4 t based on 6 kg of R-449A with GWP 1397, relevant for environmental reporting.
Needed for compliance with F-gas regulations and environmental impact assessment.
Source
“CO2 equivalent 8,4 t”
Installation
The minimum filling capacity of the system is 12.7 liters, which must be considered when preparing the heat transfer circuit.
Ensures enough heat transfer fluid volume is available for safe and stable operation.
Source
“min. filling capacity 12,7 l”