BINDER VDL 56
BINDER ·Made in Germany · In Active Production

BINDER VDL 56

BINDER VDL 56 — Drying ovens with Temperature 9…110 °C.

The BINDER VDL 56 is a 55-litre vacuum drying chamber with a microprocessor program controller MB2, built for drying flammable solvents under reduced pressure. It operates from +9 °C above ambient to 110 °C and is distinguished within the VDL series by its mid-size 55 L interior, between the 23 L and 115 L siblings. It serves as the solvent-safe drying stage in laboratory and pilot processes requiring controlled vacuum, temperature and compressed-air flushing.

Temperature
9…110 °C

BINDER VDL Series — Model Comparison & Selection

Model Temperature, °CDepth, mmHeating up time to 100 c, minHeight, cmInterior volume, LPermitted load, kg
VDL 56 Current 9–11046114081.55560
VDL 115 9–11058117094.211970
VDL 23 9–11041311069.82450

Full specifications

Core Performance & Functional Specifications
Temperature 9...110 °C
Heating time to 100°C 140 min
Interior volume 55 L (VDL 56)
Leak rate 0.01 bar/h
Load per rack 20 kg (VDL 56)
Nominal power 1.4 kW
Permitted load 60 kg (VDL 56)
Pressure fluctuation over time 1 mbar
Temperature fluctuation 0.1 K
Temperature uniformity 1.2 K
Rear wall clearance 100 mm (VDL 56)
Side wall clearance 70 mm (VDL 56)
Article Number mfr 9630
Pressure fluctuation over time at 400 mbar mfr 70 mbar
Dimensions, Weight & Mechanical Design
Depth 461 mm (VDL 56)
Height 815 mm (VDL 56)
Width 638 mm (VDL 56)
Electrical, Power & Drive Specifications
Power frequency 50 Hz
Rated voltage 200...230 V
Unit fuse 8.0 A
Phase (Nominal voltage) mfr 1
Interfaces, Connections & Control
Vacuum connection with small flange mfr 16 mm

Description

Construction and series positioning

Behaviour under load and in process media

Installation, control and operation

Integration & Operating Notes

Process Limits
Heater is locked out below 100 mbar internal pressure

The chamber must not heat up until the pressure threshold of 100 mbar is reached; no heater release occurs below this threshold. Process recipes must therefore sequence evacuation before any temperature setpoint is expected to take effect, and pressure setpoints must be chosen below 100 mbar only for non-heating phases.

Operating Manual VDL (E3.1), Section 26.2 / p.170
Mounting
Chamber must not be sited in Zone 0 or Zone 1

The chamber must not be installed in potentially explosive areas of Zone 1 or Zone 0. Site selection must follow the explosion protection document, and technical ventilation must cover both the oven installation area and the vacuum pump area before commissioning.

Operating Manual VDL (E3.1), Section 1.8.1.2 / p.15 and Section 1.8.1.5 / p.16
Process Limits
Compressed-air flushing requires 2 bar at the chamber inlet

An inlet pressure of 2 bar must be provided for compressed air flushing of the electrical equipment area. The supply line must be sized and regulated to deliver this pressure at the chamber inlet, and the manometer function for compressed air flushing should be checked during reference measurements.

Operating Manual VDL (E3.1), Section 1.8.2 / p.17
Electrical
Verify 230 V variant and 8.0 A fuse before power-up

The 230 V variant requires 200...230 V single-phase supply at 50/60 Hz and is protected by an 8.0 A unit fuse. If the chamber remains permanently off, the chamber fuse and the supply voltage (115 V or 230 V) must be checked before contacting service; connecting the 120 V variant to a 230 V supply is not permissible.

Operating Manual VDL (E3.1), Section 26.2 / p.170; Data Sheet Model VDL 56
Maintenance
Electrical and explosion protection tests required after service

An annual repeat electrical inspection is required, plus a test prior to initial startup and prior to resuming operation after maintenance or repair; EN 50678/VDE 0701 and EN 50699/VDE 0702 are recommended. Explosion protection testing is also required before initial commissioning, before restart after maintenance or repair, and at recurring intervals per the operator's explosion protection concept.

Operating Manual VDL (E3.1), Section 26.1 / p.169
Control & I/O
Safety controller alarm indicates setpoint/value mismatch

The safety controller value must be set appropriately relative to the temperature setpoint; if the inner chamber temperature reaches the safety controller value, the controller responds with the alarm message 'Safety controller'. On this alarm, check the temperature setpoint and safety controller value settings before restarting the process.

Operating Manual VDL (E3.1), Section 26.2 / p.170; Section 14.2 / p.122
Maintenance
Slow heating may require controller calibration, not repair

If the set-point temperature is not reached after the specified time, the controller must be calibrated and adjusted. Before concluding a hardware fault, verify the door gasket condition and door closure, since a defective or improperly closed door gasket also prevents heating.

Operating Manual VDL (E3.1), Section 26.2 / p.170

Selection & Integration Q&A

When should I choose the VDL 56 rather than the VDL 23 or VDL 115?

Choose the VDL 56 when the 55 L interior fits the batch: it sits between the 23 L VDL 23 and 115 L VDL 115, all rated +9 °C above ambient to 110 °C. The 56 offers 20 kg per rack and 60 kg total load, so pick the 23 for small loads and the 115 for larger batches or heavier total loads.

What vacuum pump and supply conditions must the adjacent vacuum system meet?

The vacuum pump must be ATEX Directive 2014/34/EU compliant and suitable for suction from Zone 0 or Zone 1. The BINDER VP 5 EX accessory is limited to a maximum gas inlet temperature of 40 °C. Compressed air for flushing must be regulated to 2 bar at the chamber inlet, and the pump installation area must be covered by technical ventilation.

What maintenance and accessories are required beyond the base chamber delivery?

Annual electrical inspection (EN 50678/VDE 0701, EN 50699/VDE 0702) and explosion protection tests before commissioning and after any service are mandatory. The base delivery excludes the vacuum pump (e.g. VP 5 EX), pump module, connection kits, APT-COM 4 software, analog outputs and the flexible Pt 100 sensor, which must be ordered separately.

Dimensional Drawings & Technical Documentation

Dimensional drawings

VDL 56 — drawing 1

Click drawing to inspect vector dimensions

Technical documentation

PDF
Data Sheet Model VDL 56 en
Datasheet ·382,2 КБ ·7 pp.
View PDF
PDF
VDL (E3.1) 05 2026 en
Manual ·10,8 МБ ·197 pp.
View PDF