Peter Huber Kältemaschinenbau Unichiller GL 750w
Peter Huber Kältemaschinenbau Unichiller GL 750w — Enfriadores de recirculación.
El Unichiller GL 750w es un enfriador recirculante refrigerado por agua que entrega 75 kW a 20 °C, opera de -20 a 40 °C con una bomba de presión de velocidad fija. Es la variante GL de gran capacidad de la serie Unichiller, distinguida por su potencia de 75 kW y sus conexiones de proceso G1 1/4. Sirve como fuente de refrigeración central para circuitos de proceso industriales cerrados externamente.
Peter Huber Kältemaschinenbau Unichiller Series — Model Comparison & Selection
| Modelo | Pump type | Safety class | Temperature range, °C | Power supply | Expansion volume, m³ | Minimum fill volume, m³ |
|---|---|---|---|---|---|---|
| Unichiller GL 750w Actual | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.05 | — |
| Unichiller 110T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 110Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 130T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 130Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | — | — |
| Unichiller 160T | C3 | I / NFL | -10–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160T-H | C3 | III / FL | -10–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 160Tw | C3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.01 | — |
| Unichiller 180-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 180Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 180Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 180w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 180w-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 200T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 200Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 210T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 210Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 230-H | E1 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w | E1 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller 230w-H | E1 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller 250T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 250Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 260T-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 260Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 260Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 300T | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.039 | 0.014 |
| Unichiller 300T-H | D3 | III / FL | -20–100 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 300Tw | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.022 | 0.015 |
| Unichiller 300Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 350T | D3 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.039 | 0.014 |
| Unichiller 350Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.022 | 0.015 |
| Unichiller 500Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 600Tw-H | D3 | III / FL | -20–100 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 700Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller 800Tw | D3 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.007 | — |
| Unichiller GL 1000w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.05 | — |
| Unichiller GL 200w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 250w | Pressure pump, speed not | I / NFL | -20–40 | 460V 3~ 60Hz | 0.03 | — |
| Unichiller GL 300w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller GL 400w | Pressure pump, speed not | I / NFL | -20–40 | 400V 3~ 50Hz | 0.03 | — |
| Unichiller P180 | E2 | I / NFL | -20–40 | — | 0.048 | 0.018 |
| Unichiller P180-H | E2 | III / FL | -20–100 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w | E2 | I / NFL | -20–40 | 400V 3~ 50Hz | 0.048 | 0.018 |
| Unichiller P180w-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230 | E2 | I / NFL | -20–40 | 460V 3~ 60Hz | 0.048 | 0.018 |
| Unichiller P230-H | E2 | III / FL | -20–100 | 460V 3~ 60Hz | 0.048 | 0.018 |
Especificaciones completas
| Volumen de expansión | 50 l |
| Conexión de bomba | G1 1/4 AG male |
| Velocidad de bomba ajustable | no |
| Tipo de bomba | Pressure pump, speed not variable |
| Conexión de sensor externo | Pt100 |
| Rango de temperatura | -20...40 °C |
| Alimentación | 400V 3~ 50Hz |
| Controlador | Pilot ONE |
| Interfaz digital | Ethernet, USB (Host u. Device), RS232 |
| Límite de temperatura ambiente | 5...40 °C |
| Capacidad de refrigeración | 75 kW (at 20 °C) |
| Conexión de agua de refrigeración | G1 1/4 male |
| Presión diferencial del agua de refrigeración | 1 bar (min) |
| Presión del agua de refrigeración | 6 bar (max) |
| Clase de protección | IP20 |
| Clase de seguridad | I / NFL |
Descripción
Construcción y posicionamiento en la serie
El GL 750w es un enfriador refrigerado por agua (no refrigerado por aire) con una capacidad de refrigeración de 75 kW a 20 °C y un rango de temperatura de -20…40 °C. Sus conexiones de proceso son G1 1/4 macho tanto en el lado de la bomba como en el del agua de refrigeración, y cuenta con un volumen de expansión de 50 l con una capacidad mínima de llenado de 17.5 l. Dentro de la serie Unichiller, los modelos hermanos listados (110T, 110T-H, 110Tw, 110Tw-H) son variantes refrigeradas por aire con niveles de ruido publicados; el GL 750w es refrigerado por agua y, por tanto, no tiene cifra de ruido de ventilador. La bomba de presión de velocidad fija entrega 320 l/min como máximo y 110 l/min a 4.0 bar, por lo que el circuito externo debe adaptarse a esta curva de bomba y no a una bomba de velocidad variable.
Comportamiento bajo carga y medios
La potencia nominal es válida solo a 20 °C de temperatura ambiente, 15 °C de entrada de agua de refrigeración y 1 bar de presión diferencial; en otras condiciones del emplazamiento la capacidad será distinta. El circuito de agua de refrigeración contiene cobre, acero inoxidable 1.4401, MS, PA, PPE, PTFE y EPDM, por lo que solo puede utilizarse agua compatible. La entrada de agua de refrigeración debe estar entre 5 °C y 20 °C; por debajo del punto de condensación deben aislarse las tuberías internas de agua de refrigeración. El refrigerante es R-744 (CO2), GWP 1, clase de seguridad A1/H280.
Instalación, control y operación
El controlador Pilot ONE proporciona interfaces Ethernet, USB (host y dispositivo) y RS232, además de una conexión para sensor externo Pt100. La protección contra sobretemperatura según DIN 12876 es ajustable, y el modo Process Safety libera la máxima capacidad de refrigeración cuando se alcanza el disparo de OT en lugar de desconectar. La respuesta ante fallo de alimentación es configurable como OFF/Standby, ON o Power Failure Auto. La unidad es IP20, EMC Clase A Grupo 1, y debe instalarse en interiores con al menos 300 lx de iluminancia y hasta 2000 m de altitud. Los dispositivos trifásicos por debajo de 63 A se entregan con cable pero sin enchufe.