BINDER MKF 1020
BINDER ·Made in Germany · In Active Production

BINDER MKF 1020

BINDER MKF 1020 — Climate chambers with Temperature -40…180 °C.

The BINDER MKF 1020 is a 991 L alternating climate chamber with a working range of -40 to +180 °C and 10–98 % RH, designed for rapid temperature cycling at up to 5.5 K/min heating and 5.0 K/min cooling. Its 12.5 kW heating and 1.5 kW heat compensation at 400 V 3 N/PE 50 Hz distinguish it as the largest standard 400 V model in the MKF series, excluding the CO₂ variant. It is used for reproducible climatic testing of large components and batch loads in laboratory and industrial qualification processes.

Temperature
-40…180 °C

BINDER MKF Series — Model Comparison & Selection

Model Temperature, °CHeight, cmInterior volume, LLoad per rack, kgMax heat compensation, WNominal power, kW
MKF 1020 Current -40–180200.599140150012.5
MKF 1020 CO₂ -48–180200.599140140011.5
MKF 115 -40–180172.5115304004.8
MKF 240 -40–180171.5228304006.8
MKF 240 CO₂ -50...180171.3228309006.8
MKF 400 -40–180171417308008
MKF 400 CO₂ -50...180172.74173016007.9
MKF 56 -40–180144.560152502.8
MKF 720 -40–180200.573440100011
MKF 720 CO₂ -48–180200.573440110011

Full specifications

Core Performance & Functional Specifications
Temperature -40...180 °C
Interior volume 991 L (MKF1020-400V, 50 Hz)
Load per rack 40 kg (MKF1020-400V, 50 Hz)
Maximum heat compensation 1500 W
Nominal power 12.5 kW (MKF1020-400V, 50 Hz)
Article Number mfr 9020
Dimensions, Weight & Mechanical Design
Depth 1480 mm (MKF1020-400V, 50 Hz)
Height 2005 mm (MKF1020-400V, 50 Hz)
Interior height 1020 mm (MKF1020-400V, 50 Hz)
Interior width 1200 mm (MKF1020-400V, 50 Hz)
Width 1580 mm (MKF1020-400V, 50 Hz)
Electrical, Power & Drive Specifications
Power frequency 50 Hz
Rated voltage 400 V
Unit fuse 32.0 A (MKF1020-400V, 50 Hz)
Operating Conditions, Environment & Protection
Humidity range 10...98 % RH
Cooling down time from 180°C to -40°C mfr 120 min
Humidity fluctuation with humidity dependent on set value mfr 2.5 % r.F.
Standards, Safety & General Data
Average heating-up rate according to IEC 60068-3-5 between -40°C and 180°C mfr 5.5 K/min

Description

Construction and series positioning

Behavior under load and in different media

Installation, connection and control

Integration & Operating Notes

Electrical
Requires 400 V 3 N/PE 50 Hz supply with 32 A fuse

The 12.5 kW nominal power demands a dedicated three-phase supply with neutral and earth; the unit fuse rating is 32 A. Verify that the building supply and cabling can sustain this load continuously, and include the chamber in the annual electrical safety inspection per EN 50678/VDE 0701 and EN 50699/VDE 0702.

Data Sheet Model MKF 1020 en.pdf; Operating Manual MKF/MKFT (E5) 10/2026, Technical Data
Mounting
Plan water supply and drainage before commissioning

Humidity control requires a freshwater connection (automatic via pipe or manual via internal can from size 115 on) and a wastewater drain. If the water cooling option is ordered, cooling water inlet and outlet must also be provided. Ensure the water circle lever for condensate recycling is configured if required.

Operating Manual MKF/MKFT (E5) 10/2026, Section: Installation and connections
Control & I/O
Both main and rear power switches must be on for operation

From size 115 upward, the chamber has a rear power switch in addition to the main power switch. During commissioning and troubleshooting, confirm that both switches are in the on position; otherwise the chamber will not power up even if the main switch is on.

Operating Manual MKF/MKFT (E5) 10/2026, p.24-25, p.135
Process Limits
Humidity sensor is damaged by ammonia and ozone above limits

The humidity sensor has resistance limits including ammonia (max. 20 ppm workplace threshold, permanent load 5500 ppm) and ozone (0.1 ppm). Process atmospheres or cleaning agents releasing these substances must be kept below the listed concentrations to avoid sensor degradation and invalid humidity readings.

Operating Manual MKF/MKFT (E5) 10/2026, p.20 table
Maintenance
Annual maintenance and leak test are mandatory

Regular maintenance is required at least once a year, including a leak test per Regulation (EU) 517/2014. The steam humidifier must also be serviced annually, with intervals depending on water quality and steam output. Document all service in the log book.

Operating Manual MKF/MKFT (E5) 10/2026, p.134
Maintenance
Service message at 8760 hours or two years requires BINDER reset

After 8760 operating hours or two years, a service message appears; after confirmation it reappears every two weeks until reset by BINDER Service. Plan a service intervention at this interval to avoid recurring alarms and to maintain warranty compliance.

Operating Manual MKF/MKFT (E5) 10/2026, p.135
Maintenance
Replace door gasket only when cold

The door gasket must be replaced only when the chamber is cold. Attempting replacement at elevated temperatures can damage the gasket and impair sealing, leading to humidity and temperature control errors.

Operating Manual MKF/MKFT (E5) 10/2026, p.134

Selection & Integration Q&A

When should I choose the MKF 1020 instead of the MKF 1020 CO₂ or a smaller MKF model?

Choose the MKF 1020 for large-volume testing (991 L) down to -40 °C with humidity. The MKF 1020 CO₂ extends to -48 °C but is otherwise similar; smaller MKF 115/240 suit lower throughput. Select the CO₂ only if lower temperatures are essential.

What are the electrical supply requirements for the MKF 1020, and can it be integrated with a site controller?

It requires 400 V 3 N/PE 50 Hz, 12.5 kW, 32 A fuse. For 480 V 60 Hz sites, specify the MKF1020-480V-C with voltage/frequency changer. Integration is via RS485, Ethernet, USB, analog outputs, and zero-voltage switching outputs on the MB2 controller.

What maintenance is required and what accessories are not included in the base delivery?

Annual maintenance and leak test are mandatory; steam humidifier serviced annually; condenser cleaned every 1–2 years. Base delivery excludes the water cooling option, water circle lever, compressed air dryer, RS485 interface, analog outputs, and APT-COM™ software. These must be ordered separately.

Dimensional Drawings & Technical Documentation

Technical documentation

PDF
Data Sheet Model MKF 1020 en
Datasheet ·925,1 КБ ·9 pp.
View PDF
PDF
MKF+MKFT (E5) 10 2026 en
Manual ·18,1 МБ ·179 pp.
View PDF